Plan Review Details - Permit 09010325
Plan Review Stops For Permit 09010325
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-04-07 Cont ID  
Sent By mawillia Date 2009-04-07 Time 17:33 Rev Time 0.00
Received By mawillia Date 2009-04-07 Time 15:38 Sent To  
Notes
2009-04-07 16:19:26*****APPROVED W/PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS FA/01 THRU FA/06 WERE
 STAMPED, INITIALED, AND APPROVED. READY FOR PERMIT
 ISSUANCE.
  
 THE SOUNDER BASES (SB) SMOKE DETETION SYSTEM IS
 ACCEPTABLE TO THE AHJ PROVIDING THAT: THE CEILING SPACE
 BETWEEN THE SLEEPING AREA AND THE LIVING AREA SHALL BE
 CONTINUOUS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-03-31 Cont ID  
Sent By mawillia Date 2009-03-31 Time 10:09 Rev Time 0.00
Received By mawillia Date 2009-03-31 Time 09:47 Sent To  
Notes
2009-03-30 23:09:56*****UNSAT*****
  
 ** THE FOLLOWING THREE OF FOUR COMMENTS FROM THE
 PREVIOUS PLAN REVIEW (2/6/09)STILL NEED TO BE ADDRESSED
 AND/OR ACKNOWLEDGED:
  
 2. THE ACTUAL PROJECT SITE ADDRESS SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3. THE FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED FOR
 CENTRAL STATION SERVICE.
  
 4. ON SHEET FA/07, A LETTER IS ATTACHED IN REFERENCE TO
 THE SMOKE DETECTORS WITH SOUNDER BASES HAVING BEEN
 DESIGNED/PROGRAMMED TO GIVE A A LOCAL ALARM TO COMPLY
 WITH NFPA 2006. HOWEVER THIS LETTER SHALL CONTAIN THE
 PROJECT SITE ADDRESS AND BE SIGNED AND SEALED BY THE
 ENGINEER OF RECORD AS ITS INTENDED USE. BETTER YET,
 INCLUDE IN THE FIRE ALARM SYSTEM'S SEQUENCE OF
 OPERATION.
  
 **NEW COMMENT
  
 A. WHERE IS THE SEQUENCE OF OPERATIONS FOR THIS FIRE
 ALARM SYSTEM?
  
 B. PROVIDE SPECIFICATIONS FOR THE DEVICES/EQUIPMENT
 THAT ARE PERTINENT AND/OR SPECIFIC FOR THE FIRE ALARM
 SYSTEM AT THIS PROJECT SITE ONLY.
  
 C. PLANS ARE TO BE SIGNED AND SEALED BY THE ENGINEER OF
 RECORD.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-02-06 Cont ID  
Sent By mwennerg Date 2009-02-06 Time 14:03 Rev Time 0.00
Received By mwennerg Date 2009-02-06 Time 14:03 Sent To  
Notes
2009-02-06 14:24:36***DENIED***
  
 1) A COMPLETE FIRE PLAN REVIEW CAN NOT BE CONDUCTED AT
 THIS TIME. IT IS DIFFICULT TO DETERMINE THE ACTUAL
 LOCATION OF THE DEVICES AS THEY RELATE TO THE BUILDING.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS. FBC 106.1.1
  
 2) THE ADDRESS IN THE TITLE BLOCK INDICATES PALM BEACH,
 FL. THE CORRECT JURISDICTION IS WEST PALM BEACH, FL.
 PLEASE CORRECT THE INFORMATION AND ADD THE BUILDING
 NUMERICAL TO EACH SHEET OF THE DRAWINGS.
  
 3) FIRE ALARM SHALL BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE.
  
 4) THE PLANS SUGGEST THAT THE APPLIANCES INSIDE THE
 GUEST ROOMS ARE DETECTORS ACCORDING TO THE SYMBOL
 LEGEND. PLEASE CLARIFY AS NFPA 101, 2006 SEC. 28.3.4.5
 REQUIRES APPROVED SINGLE STATION SMOKE ALARMS THAT WILL
 NOT INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH
 9.6.2.9.4, 101.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-17 Cont ID  
Sent By adarroug Date 2009-03-17 Time 16:18 Rev Time 0.00
Received By adarroug Date 2009-03-17 Time 16:18 Sent To FIRE
Notes
2009-03-17 16:18:59TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-06 Cont ID  
Sent By mwennerg Date 2009-02-06 Time 14:30 Rev Time 0.00
Received By mwennerg Date 2009-01-23 Time 15:46 Sent To  
Notes
2009-01-23 15:46:27TO "F" BOX