Plan Review Details - Permit 09010324
Plan Review Stops For Permit 09010324
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-02-06 Cont ID  
Sent By mwennerg Date 2009-02-06 Time 13:29 Rev Time 0.00
Received By mwennerg Date 2009-02-06 Time 13:29 Sent To  
Notes
2009-02-06 13:31:37PLANS APPROVED AND STAMPED WITH THE FOLLOWING
 REQUIREMENTS:
  
 1) FIRE ALARM TO BE UL CERTIFICATED FOR CENTRAL STATION
 SERVICE.
 2) FIRE ALARM SYSTEM SHALL BE CLASS A OR FULLY
 ADDRESSABLE.
 3) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-06 Cont ID  
Sent By mwennerg Date 2009-02-06 Time 13:31 Rev Time 0.00
Received By mwennerg Date 2009-01-23 Time 15:45 Sent To  
Notes
2009-01-23 15:45:47TO "F" BOX