Plan Review Details - Permit 09010287
Plan Review Stops For Permit 09010287
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-01-28 Cont ID  
Sent By kstevens Date 2009-01-28 Time 10:31 Rev Time 0.00
Received By kstevens Date 2009-01-28 Time 10:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-01-23 Cont ID  
Sent By kstevens Date 2009-01-23 Time 07:23 Rev Time 0.00
Received By kstevens Date 2009-01-22 Time 16:55 Sent To  
Notes
2009-01-23 07:30:33DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS
 PERMIT:
  
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. SHOW THE MATERIAL
 FOR ALL SECTIONS OF PIPE. ONLY 2 SECTIONS OF PIPE ARE
 SHOWN. ARE THE RISERS FROM THE PE PIPE COPPER? INDICATE
 IF THE COPPER LINE IS UNDERGROUND. PER SECTION 404.8,
 METALLIC PIPE OR TUBING EXPOSED TO CORROSIVE ACTION,
 SUCH AS SOIL CONDITION OR MOISTURE, SHALL BE PROTECTED
 IN AN APPROVED MANNER. IF THE COPPER IS UNDERGROUND,
 PLEASE INDICATE HOW IT WILL BE PROTECTED.
  
 B. TYPE OF GAS, (LP OR NATURAL).
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). INDICATE TOTAL BTU LOAD.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 E. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 G. SUBMIT MANUF. SPECIFICATION SHEETS FOR THE
 REGULATORS AND INDICATE MODEL NUMBER (S). REGULATORS
 SHALL SHOW A LISTING AND INDICATE THE OUTLET BTU LIMIT.
 SECTIONS 106.2.1 (MORE INFORMATION REQUIRED) &
 410.2(1).
  
 2. ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE PRINTED
 NAME AND SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN. SECTION 104.2.1.
  
 3. CORRECT ADDRESS ON PLAN, (215 FLORIDA AVE) TO
 REFLECT THE ADDRESS INDICATED ON THE APPLICATION, (1215
 FLORIDA AVE). SECTION 106.1.1.
  
 4. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE
 VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR, MATERIALS AND DESIGN.
 PER (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT
 VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURAL, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  