| Plan Review Stops For Permit 09010286 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-06-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-06-12 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-06-12 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2009-06-12 14:01:33 | REVISION FOR FURRING CEILING IS OK. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-03-10 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-03-10 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2009-03-10 10:20:24 | BUILDING PROVISO | | | | | | 1) THIS UNIT IS LOCATED IN A BUILDING OF TYPE I | | | CONSTRUCTION. THEREFORE, INTERIOR NON-BEARING WALL | | | FRAMING ARE REQUIRED TO BE OF NONCOMBUSTIBLE MATERIALS. | | | METAL OR FIRE-RETARDANT-TREATED WOOD STUDS ARE ALLOWED. | | | FBC 602.2 AND 603. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2009-02-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-02-03 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-02-03 |
Time |
11:41 |
Sent To |
E |
|
| Notes |
| 2009-02-03 13:12:05 | BUILDING PROVISO | | | | | | 1) THIS UNIT IS LOCATED IN A BUILDING OF TYPE I | | | CONSTRUCTION. THEREFORE, INTERIOR NON-BEARING WALL | | | FRAMING ARE REQUIRED TO BE OF NONCOMBUSTIBLE MATERIALS. | | | METAL OR FIRE-RETARDANT-TREATED WOOD STUDS ARE ALLOWED. | | | FBC 602.2 AND 603. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-03-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-03-09 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-03-09 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-02-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-02-04 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-02-04 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2009-02-04 16:52:40 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | ALL COMMENTS RELATE TO SHEET #3, UNLESS OTHERWISE | | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | | OTHERWISE NOTED. | | | | | | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1).THE NEW BATHROOM DOES NOT | | | COMPLY. LIST THIS CIRCUIT IN THE PANEL SCHEDULE. | | | | | | 2} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. INDICATE GFI | | | ON THE PLANS AND CORRECT THE SPACING. | | | | | | 3} THE REFRIGERATOR CIRCUIT WAS NOT MOVED TO THE NEW | | | REFRIGERATOR LOCATION ACCORDING TO THE RECEPTACLE | | | NUMBER. 408.4. | | | | | | 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS | | | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING | | | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE | | | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE | | | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE | | | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE | | | INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-03-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-03-17 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-03-17 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2009-03-17 11:02:41 | AS PER FIRST REVIEW, LIFE SAFETY TO COMPLY WITH NFPA | | | 101, 2006. RED LINED PLANS TO REFLECT CORRECT EDITION. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-02-10 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-02-10 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-02-10 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2009-02-10 13:19:10 | ***DENIED*** | | | | | | 1) PLANS SUBMITTED AFTER DEC.31, 2008 SHALL COMPLY WITH | | | NFPA 101, 2006 EDITION. | | | | | | 2) PLEASE SHOW THE LOCATIONS OF THE EXISTING AND OR NEW | | | HARD WIRED SMOKE ALARMS THAT SHALL BE INTERCONNECTED TO | | | CAUSE THE ACTIVATION OF (1) SMOKE ALARM TO ACTIVATE ALL | | | THE SMOKE ALARMS. 101, SEC. 9.6.2.9. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-06-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-06-11 |
Time |
18:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-06-11 |
Time |
18:09 |
Sent To |
|
|
| Notes |
| 2009-06-11 18:09:27 | BLDG REVISION TO RM DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-05-01 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2009-05-01 15:53:49 | SENT TO RON'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-02-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-25 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-25 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2009-02-25 16:56:41 | TO "BOB"#11 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-02-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-15 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-01-30 |
Time |
16:28 |
Sent To |
PC |
|
| Notes |
| 2009-02-05 08:19:54 | 2/5/09--TO "BOB"#8 | | 2009-01-30 16:31:54 | TO "SFR" "E" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-05-15 |
Time |
15:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-03-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-03-25 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-03-25 |
Time |
09:25 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-02-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-15 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-15 |
Time |
10:05 |
Sent To |
PC |
|
| Notes |
| 2009-02-15 10:18:49 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. THE SCOPE OF A/C WORK AS SHOWN ON PLANS IS NOT | | | CLEAR. ONLY AN "EXISTING HVAC" PLAN IS PROVIDED WITH NO | | | CHANGES SHOWN ON PLANS. PLEASE SHOW ON PLANS WHICH | | | PARTS OF THE A/C SYSTEM ARE BEING REMOVED AS WELL AS | | | WHICH WORK IS TO BE NEW IN ACCORDANCE WITH FBCB | | | 106.1.1. | | | | | | 2. PLEASE CLARIFY ALL DUCT SIZES SHOWN ON PLANS. ONE | | | DUCT IS MARKED WITH A SIZE OF "MX6." IT IS NOT CLEAR | | | WHAT THE SIZE OF THIS DUCT IS. ALSO, PLEASE INDICATE | | | SIZES AT ALL DUCT TRANSITIONS TO CLARIFY THE DUCT SIZE | | | ON BOTH SIDES OF THE TRANSITIONS IN ACCORDANCE WITH | | | FBCM 603.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-03-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-12 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-12 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2009-03-12 14:15:01 | PER ENGINEER, NO PLUMBING CHANGES TO SANITARY OR WATER | | | LINES. NEW FIXTURES ONLY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-05 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-05 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2009-02-05 10:32:16 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT 1 OF 3 EXISTING SANITARY RISER DIAGRAM FOR THE | | | LAVS SHOW DOES NOT MEET CODE REQUIREMENTS NOR DOES IT | | | REFLECT THE FLOOR PLAN. THE LAV IS NOT VENTED AND THE | | | RISER SHOWS A 3RD WATER CLOSET, NOT TWO LAVS. (SEE RED | | | LINE CORRECTION). | | | | | | 2. SUBMIT A SANITARY RISER DIAGRAM FOR THE NEW LAV | | | SHOWING THE CONNECTION TO THE EXISTING SANITARY, SHOW | | | ALL PIPE SIZES, TRAPS AND VENTS. SECTIONS | | | 106.3.5.1.3(4)(6)(13), 701.1, 901.2.1 & 1002.1. | | | | | | 3. MORE INFORMATION IS REQUIRED FOR THE KITCHEN. THE | | | EXISTING FLOOR PLAN DOES NOT INDICATE THE LOCATION OF | | | THE KITCHEN SINK. PLEASE INDICATE THE LOCATION AS | | | EXISTING, AND IF THE KITCHEN SINK IS MOVED TO A NEW | | | LOCATION, THEN A SANITARY RISER DIAGRAM FOR THE KITCHEN | | | SINK SHALL BE SUBMITTED SHOWING THE POINT OF | | | CONNECTION, THE PIPE SIZE, TRAP & VENT. SECTIONS | | | 106.3.5.1.3(4)(6)(13), 701.1, 901.2.1 & 1002.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2009-02-12 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2009-02-12 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|