| 2009-02-09 15:45:14 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. THIS WORK IS NOT WITHIN THE SCOPE OF AN ELECTRICAL |
| | CONTRACTOR'S LICENSE. FS 489.505 (12) "ELECTRICAL |
| | CONTRACTOR" OR "UNLIMITED ELECTRICAL CONTRACTOR" MEANS |
| | A PERSON WHO CONDUCTS BUSINESS IN THE ELECTRICAL TRADE |
| | FIELD AND WHO HAS THE EXPERIENCE, KNOWLEDGE, AND SKILL |
| | TO INSTALL, REPAIR, ALTER, ADD TO, OR DESIGN, IN |
| | COMPLIANCE WITH LAW, ELECTRICAL WIRING, FIXTURES, |
| | APPLIANCES, APPARATUS, RACEWAYS, CONDUIT, OR ANY PART |
| | THEREOF, WHICH GENERATES, TRANSMITS, TRANSFORMS, OR |
| | UTILIZES ELECTRICAL ENERGY IN ANY FORM, INCLUDING THE |
| | ELECTRICAL INSTALLATIONS AND SYSTEMS WITHIN PLANTS AND |
| | SUBSTATIONS, ALL IN COMPLIANCE WITH APPLICABLE PLANS, |
| | SPECIFICATIONS, CODES, LAWS, AND REGULATIONS. THE TERM |
| | MEANS ANY PERSON, FIRM, OR CORPORATION THAT ENGAGES IN |
| | THE BUSINESS OF ELECTRICAL CONTRACTING UNDER AN EXPRESS |
| | OR IMPLIED CONTRACT; OR THAT UNDERTAKES, OFFERS TO |
| | UNDERTAKE, PURPORTS TO HAVE THE CAPACITY TO UNDERTAKE, |
| | OR SUBMITS A BID TO ENGAGE IN THE BUSINESS OF |
| | ELECTRICAL CONTRACTING; OR THAT DOES ITSELF OR BY OR |
| | THROUGH OTHERS ENGAGE IN THE BUSINESS OF ELECTRICAL |
| | CONTRACTING. |
| | |
| | 2. PLEASE INCLUDE WIND DESIGN CRITERIA FBC1609. |
| | |
| | 3. PLEASE INCLUDE GOVERNING CODE INCLUDING 2007 |
| | REVISIONS/SUPPLEMENTS. |
| | |
| | 4. PLEASE SHOW COMPLIANCE WITH FBC 3105.1.1. NO SITE |
| | PLAN SHOWING PROPERTY LINES PROVIDED. |
| | |
| | 5. NO STRUCTURAL INFORMATION PROVIDED TO SHOW |
| | COMPLIANCE WITH FBC3105.4. DESIGN CRITERIA NOT CLEAR. |
| | |
| | 6. IF THIS IS TO BE REMOVABLE, REMOVAL INSTRUCTIONS |
| | REQUIRED TO SHOW COMPLIANCE WITH FBC3105.4.2.1. |
| | |
| | 7. IF THIS IS TO BE REMOVABLE, . PER BUILDING OFFICIAL, |
| | WE ARE TO PUT ON THE PERMIT FILE A LETTER, OR |
| | CONTRACTORS FORM, SIGNED BY THE OWNER (NOT THE TENANT) |
| | TO ACKNOWLEDGE THEIR RESPONSIBILITY TO HAVE THE AWNING |
| | COVER REMOVED PRIOR TO ANY WIND EVENT WITH PROJECTED |
| | WIND SPEEDS OF 75 MPH OR GREATER. THE LETTER/FORM MUST |
| | BE SIGNED BY THE OWNER BUT IT NEED NOT BE NOTARIZED. |
| | |
| | 8. SHOW COMPLIANCE WITH FBC3105.3. |
| | |
| | 9. PROVIDE A STRUCTURAL DETAIL FOR THE EXISTING FRAME. |
| | |
| | |
| | |