Plan Review Details - Permit 09010251
Plan Review Stops For Permit 09010251
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-29 Cont ID  
Sent By jwitmer Date 2009-04-29 Time 15:48 Rev Time 0.77
Received By jwitmer Date 2009-04-29 Time 15:18 Sent To  
Notes
2009-04-29 15:49:13SKETCH# 18 -OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-01 Cont ID  
Sent By jwitmer Date 2009-04-01 Time 16:09 Rev Time 0.77
Received By jwitmer Date 2009-04-01 Time 16:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-11 Cont ID  
Sent By jwitmer Date 2009-02-11 Time 10:46 Rev Time 1.22
Received By jwitmer Date 2009-02-11 Time 10:46 Sent To P
Notes
2009-02-11 12:16:56BUILDING PLAN REVIEW
 PERMIT: 09010251
 ADD: 301 LAMBERTON DR
 CONT: ANDERSON & MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) SK-17 HANSON PROFESSIONAL SERVICES, INC. 481.219
 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE BLOCK FOR
 ANY SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING
 UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
 PLEASE INCLUDE ON THE NEXT SUBMITTAL.
  
 3) THE CAST IRON PIPE THAT IS ILLUSTRATED ON SK-17 DOES
 NOT PROVIDE ENOUGH INFORMATION:
  
 3A) PROVIDE THE DIMENSIONS OF THE 2HR RATED SHAFT
 ENCLOSURE AND WALL TYPE ASSEMBLY. 707.4 SHAFT
 ENCLOSURES.
  
 3A) PLEASE PROVIDE THE LOCATION OF THE PIE AND
 ENCLOSURE IN EACH STAIRWAY ILLUSTRATING THAT THE CLEAR
 PATH OF THE STAIRWAY HAS NOT BEEN IMPEDED. THE CITY SET
 OF PLANS INDICATE THE STAAIRWAYS TO BE 4'-31/2" WIDE,
 1009.4 REQUIRES EVERY LANDING SHALL HAVE A MINIMUM
 DIMENSION MEASURED IN THE DIRECTION OF TRAVEL EQUAL TO
 THE WIDTH OF THE STAIRWAY. PLEASE DEPICT AN ARC WITH A
 RADIUS EQUAL TO THE ACTUAL STAIRWAY WIDTH ALSO DEPICT
 THE NEW SHAFT WITHIN THE STAIRWELL AND NOT EMPEDING THE
 MEANS OF EGRESS. PLEASE PROVIDE THIS INFORMATION FOR
 EACH OF THE TWO STAIRWELLS.
  
 3B) PLEASE PROVIDE ADDITIONAL INFORMATION HOW THE JOINT
 BETWEEN THE NEW SHAFTWALL AND EXISTING STAIRWELL WALL
 WILL BE SEALED.
 713.1 GENERAL. JOINTS INSTALLED IN OR BETWEEN
 FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING
 ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL
 BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME
 PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE
 RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH
 IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE
 TESTED IN ACCORDANCE WITH SECTION 713.3. THE VOID
 CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY
 AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713.4.
 713.2 INSTALLATION. FIRE-RESISTANT JOINT SYSTEMS SHALL
 BE SECURELY INSTALLED IN OR ON THE JOINT FOR ITS ENTIRE
 LENGTH SO AS NOT TO DISLODGE, LOOSEN OR OTHERWISE
 IMPAIR ITS ABILITY TO ACCOMMODATE EXPECTED BUILDING
 MOVEMENTS AND TO RESIST THE PASSAGE OF FIRE AND HOT
 GASES.
  
 3C) THE OTHER ISSUE WHICH I DO NOT SEE ADDRESSED IS THE
 ROOF DRAIN IS CENTERED WITHIN THE STAIRWAY, A DROPPED
 CEILING WOULD NEED TO CREATED A 2HR RATED ENCLOSURE TO
 KEEP THE CAST IRON PIPE OUT OF THE STAIRWELL. 019.1.2
 PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH AN
 EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 712. THERE SHALL BE NO
 PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 12:35 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 12:35 Sent To B
Notes
2009-04-29 12:35:18TO JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-27 Cont ID  
Sent By adarroug Date 2009-03-27 Time 11:18 Rev Time 0.00
Received By adarroug Date 2009-03-27 Time 11:18 Sent To B
Notes
2009-03-27 11:18:28TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 10:19 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 10:19 Sent To B
Notes
2009-02-10 16:48:26GAVE TO JIM
2009-02-09 10:19:51TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-23 Cont ID  
Sent By kstevens Date 2009-02-23 Time 15:00 Rev Time 0.00
Received By kstevens Date 2009-01-20 Time 15:43 Sent To  
Notes
2009-01-20 15:43:56TO "Z" BOX

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-02-06 Cont ID  
Sent By rkussner Date 2009-02-06 Time 10:58 Rev Time 0.00
Received By rkussner Date 2009-02-06 Time 10:56 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-02-23 Cont ID  
Sent By kstevens Date 2009-02-23 Time 15:00 Rev Time 0.00
Received By kstevens Date 2009-02-23 Time 15:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-02-05 Cont ID  
Sent By lfranco Date 2009-02-05 Time 18:07 Rev Time 0.00
Received By lfranco Date 2009-02-05 Time 18:07 Sent To  
Notes
***NONE***