Plan Review Details - Permit 09010224
Plan Review Stops For Permit 09010224
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-01-23 Cont ID  
Sent By mwennerg Date 2009-01-23 Time 14:12 Rev Time 0.00
Received By mwennerg Date 2009-01-23 Time 14:12 Sent To  
Notes
2009-01-23 14:14:44PLANS APPROVED AND STAMPED
  
 1) FIRE ALARM SHALL BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE PRIOR TO FINAL INSPECTION.
 2) FIRE ALARM SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE.
 3) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-23 Cont ID  
Sent By mwennerg Date 2009-01-23 Time 14:14 Rev Time 0.00
Received By mwennerg Date 2009-01-20 Time 10:22 Sent To  
Notes
2009-01-20 10:22:52TO "F" BOX