Plan Review Details - Permit 09010187
Plan Review Stops For Permit 09010187
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-02-04 Cont ID  
Sent By jnguyen Date 2009-02-04 Time 17:21 Rev Time 0.00
Received By jnguyen Date 2009-02-03 Time 15:28 Sent To  
Notes
2009-02-04 17:04:11THE ADDRESS WAS ACTUALLY CORRECT FOR THE COLUMBIA
 HOSPITAL AS 2201 45TH ST, BUT THIS PERMIT WAS BEING
 ATTACHED TO THE WRONG PCN# 74434306000001010 (REAR HALF
 OF THE COLUMBIA HOSPITAL BUILDING). THE SITE PLAN SHOWS
 THAT THE AREA OF RENOVATION TO BE TAKING PLACE ON THE
 2ND FLOOR, WHICH PERTAINS TO THE FRONT HALF OF THE
 COLUMBIA HOSPITAL BUILDING & THUS FALLS WITHIN THE
 BOUNDARIES OF THE PARCEL TO THE SOUTH (PCN#
 74434306000001030). AFTER PHYSICALLY CHECKING OUT THE
 LOCATION & ITS SURROUNDING BUILDINGS IN THE NEARBY
 PARCELS THIS MORNING, I CAME TO THE REALIZATION THAT
 OUR GIS & COMMUNITYPLUS DATABASES HAD SEVERE
 INACCURACIES AS TO WHAT WAS REALLY OUT THERE. FOR
 EXAMPLE, OUR GIS & COMMUNITYPLUS DATABASES INCORRECTLY
 RECOGNIZED THE ADDRESS OF 4631 N CONGRESS AVE FOR THE
 COLUMBIA HOSPITAL ON PCN# 74434306000001030 WHEN IT
 SHOULD HAVE INSTEAD BEEN 2201 45TH ST (AS THE
 ARCHITECT, LES CZACZYK & ENGINEER, CHRISTOPHER HUDSON
 SHOWED ON THEIR SITE PLANS). 4631 N CONGRESS AVE
 ACTUALLY INSTEAD APPLIED TO THE COLUMBIA MEDICAL ARTS
 PREMIER RESEARCH INSTITITUE BUILDING ON PCN#
 74434306000001210 & 4601 N CONGRESS AVE WAS VISIBLY
 ATTACHED TO THE PALM BEACH MEDICAL GROUP BUILDING ON
 PCN# 74434306000001010 (WHEREAS WE HAD THAT ADDRESS OUT
 IN SPACE ON PCN# 74434306000001030). I IMPLEMENTED A
 SERIES OF CORRECTIONS FOR THESE PARCELS OUT THERE (I.E,
 E-MAILING PAPA TO ADJUST THE PRIMARY ADDRESS ON THEIR
 WEB SITE FROM 4631 N CONGRESS AVE TO THE CONFIRMED 2201
 45TH ST FOR PCN# 74434306000001030). UNDER PCN#
 74434306000001030, I HAVE CREATED THE SEQUENTIAL UNIT
 RECORD 0009 FOR THE 2ND FLOOR OF THE COLUMBIA HOSPTIAL
 LOCATED AT 2201 45TH ST, SO PLEASE MOVE THIS PERMIT
 RECORD TO REFERENCE THAT PARTICULAR LOCATION (AS I DO
 NOT HAVE AUTHORIZATION IN COMMUNITYPLUS TO MAKE THIS
 CHANGE). I HAVE TAKEN CARE OF CHANGING IT ON THE
 ORIGINAL PERMIT APPLICATION FROM PCN# 74434306000001010
 TO PCN# 74434306000001030. I HAVE ALSO RETURNED THE
 SITE PLANS TO COMMUNITY BOARD #56.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-26 Cont ID  
Sent By jwitmer Date 2009-01-26 Time 14:13 Rev Time 2.22
Received By jwitmer Date 2009-01-23 Time 15:39 Sent To  
Notes
2009-01-26 15:33:52BUILDING PLAN REVIEW
 PERMIT: 09010187
 ADD: 2201 45TH ST
 CONT: MAJOR WORKING DRAWING REVIEW/ PLAN REVIEW
 TEL: (561)635-6935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) SHEET A.010 THE DOOR SCHEDULE INDICATES DOOR# 242 AS
 A PAIR OF 7'-0" DOUBLE SWING DOUBLE EGRESS DOORS, SHEET
 G.001 EXIT CALCULATIONS AT 2ND FLOOR INDICATES THE
 MINIMUM CLEAR OPENING AT EXIT DOORS TO BE 44". DOOR#
 242 IS ONLY 42" WIDE WITH A CLEAR WIDTH OF 40". SECTION
 1008.1.1 WHEN THE MOVEMENT OF BEDS IS REQUIRED THE
 MINIMUM CLEAR WIDTH OF THE DOOR IS TO BE 41.5".
  
 3) A6.02 DETAIL# 1 THE FAMILY ROOM INDICATES THE USE OF
 A MICROWAVE PLEASE INDICATE COMPLIANCE WITH 11-4.27.3
 HEIGHT. THE HIGHEST OPERABLE PART OF CONTROLS,
 DISPENSERS, RECEPTACLES, AND OTHER OPERABLE EQUIPMENT
 SHALL BE PLACED WITHIN AT LEAST ONE OF THE REACH RANGES
 SPECIFIED IN SECTIONS 11-4.2.5 AND 11-4.2.6.
 11-4.2.5 FORWARD REACH.
 IF THE CLEAR FLOOR SPACE ONLY ALLOWS FORWARD APPROACH
 TO AN OBJECT, THE MAXIMUM HIGH FORWARD REACH ALLOWED
 SHALL BE 48 INCHES (1220 MM). THE MINIMUM LOW FORWARD
 REACH IS 15 INCHES (380 MM) [SEE FIGURE 5(A)]. IF THE
 HIGH FORWARD REACH IS OVER AN OBSTRUCTION, REACH AND
 CLEARANCES SHALL BE AS SHOWN IN FIGURE 5(B).
 11-4.2.6 SIDE REACH.
 IF THE CLEAR FLOOR SPACE ALLOWS PARALLEL APPROACH BY A
 PERSON IN A WHEELCHAIR, THE MAXIMUM HIGH SIDE REACH
 ALLOWED SHALL BE 54 INCHES (1370 MM) AND THE LOW SIDE
 REACH SHALL BE NO LESS THAN 9 INCHES (230 MM) ABOVE THE
 FLOOR [SEE FIGURE 6(A) AND FIGURE 6(B)]. IF THE SIDE
 REACH IS OVER AN OBSTRUCTION, THE REACH AND CLEARANCES
 SHALL BE AS SHOWN IN FIGURE 6(C).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-05 Cont ID  
Sent By dpalmer Date 2009-02-05 Time 09:40 Rev Time 0.00
Received By dpalmer Date 2009-02-05 Time 09:40 Sent To  
Notes
2009-02-05 09:40:31** DENIED **
  
  
 1) NOTE: ** IMPORTANT***
 THE PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW.
 UNDER PLAN REVIEW THIS DOES NOT LOCK ANY PROJECT UNDER
 THIS CURRENT SET OF CODES. IT SHOULD BE KNOWN THAT AS
 OF MARCH 1ST, 2009 THE STATE OF FLORIDA WILL BE
 ADOPTING THE NEW SET OF CODES. THIS WILL INCLUDE THE
 2007 FBC ALONG WITH SEVERAL NEW ADOPTED CODES. ONLY
 PLANS SUBMITTED UNDER **PERMIT APPLICATION* WITH
 LICENSED CONTRACTOR AND APPLICABLE FEES PAID BEFORE
 MARCH 1ST, 2009 WILL LOCK IN PROJECT UNDER THE CURRENT
 CODES.
 IT IS ALSO IMPORTANT TO KNOW THAT PER THE STATE FIRE
 MARSHAL. THE 2007 FLORIDA FIRE PREVENTION CODE AS OF
 DECEMBER 31ST, 2008 HAS BEEN ADOPTED. THE 2006 NFPA-101
 IS NOW IN EFFECT. PLEASE ADJUST CODE DESIGN AND CODE ON
 PLANS.
  
 2) NOTE: PLEASE PROVIDE MORE IDENTIFICATION ON RISER.
 IS ALL OF THIS EXISTING TO REMAIN? SOME ITEMS ARE
 SPECIFIC ON RISER AS BEING EXISTING HOWEVER NOT ALL.
 IF THE ENTIRE RISER IS EXISTING NOT EACH AN EVERY ITEM
 NEEDS TO BE NOTED IF THE MAIN DESCRIPTION WHICH STATES
 *ELECTRICAL ONE-LINE DIAGRAM* STATES IT IS EXISTING.
 IF SOME OF THESE ITEMS ARE NEW THEN RISER NEEDS MORE
 INFORMATION FOR REVIEW OF CONDUCTORS ETC.
 215.5,230,220,310.16 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1,
 13-415.1.ABC.1.1,.1.2, .1.3. ALL NEW DEVICES BEING
 INSTALLED NEED TO MEET THE SECTIONS NOTED. ** THIS IS
 FOR NEW BEING INSTALLED ONLY.
  
 4) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2
 FOR LIGHTING PERFORMANCE CALCULATIONS NEEDED. NO NEW
 LIGHTING MAY BE ADDED UNLESS EXISTING IS BELOW
 ALLOWANCE LEVELS AND NEW LIGHTING BEING DESIGNED DOES
 NOT EXCEED THE LEVELS IN TABLES SET FORTH IN THE FBC.
 *** IF THERE ARE QUESTIONS, PLEASE CALL TO GO OVER.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-02-17 Cont ID  
Sent By mwennerg Date 2009-02-17 Time 13:27 Rev Time 0.00
Received By mwennerg Date 2009-02-17 Time 13:27 Sent To  
Notes
2009-02-17 13:36:07PLEASE NOTE THAT PLANS WILL REMAIN IN FAILED STATUS
 UNTIL REVIEWED AND APPROVED FOR PERMIT APPLICATION.
 PLEASE SEE THE FOLLOWING:
  
 1) LIFE SAFETY SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 2007 EDITION TO INCLUDE NFPA 101, 2006
 AND NFPA 1, 2006. THIS CURRENT ADOPTED CODE HAS BEEN IN
 EFFECT SINCE DECEMBER 31, 2008.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL PRIOR TO
 EQUIPMENT INSTALLATION.
  
 3) FIRE SPRINKLER SYSTEM TO COMPLY WITH NFPA 13, 2002
 EDITION. SHEET F001, NOTE #1
  
 4) DUCT SMOKE DETECTORS TO BE WIRED INTO FIRE ALARM
 SYSTEM THAT UPON ACTIVATION WILL CAUSE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-20 Cont ID  
Sent By kstevens Date 2009-02-20 Time 14:34 Rev Time 0.00
Received By kstevens Date 2009-01-15 Time 10:25 Sent To  
Notes
2009-01-15 10:29:56TO "COMM" BD#56

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-02-15 Cont ID  
Sent By rregueir Date 2009-02-15 Time 17:23 Rev Time 0.00
Received By rregueir Date 2009-02-15 Time 17:23 Sent To  
Notes
2009-02-15 17:25:43**PLAN CHECK ONLY**
  
 PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED. REVIEW WILL REMAIN IN FAIL STATUS PENDING
 ACTUAL APPLICATION FOR PERMIT.
  
 NOTE: APPLICATIONS FOR PERMIT SUBMITTED AFTER MARCH 1,
 2009 WILL BE SUBJECT TO THE NEW 2007 FLORIDA BUILDING
 CODE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2009-02-20 Cont ID  
Sent By kstevens Date 2009-02-20 Time 14:20 Rev Time 0.00
Received By kstevens Date 2009-02-20 Time 14:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-02-20 Cont ID  
Sent By kstevens Date 2009-02-20 Time 14:20 Rev Time 0.00
Received By kstevens Date 2009-02-20 Time 14:20 Sent To  
Notes
2009-02-20 14:34:38DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH LCA ARCHITECTURE INC TITLE BLOCK.
 THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS INCORRECT. PLEASE SEE ATTACHED
 SHEET. PLEASE CORRECT THE BUSINESS NUMBER ON EACH
 SHEET. FAC 61G1-16.004(2) & FS 481.219.
  
 2. SHT A.601 DETAIL 6 INDICATE COMPLIANCE WITH SECTION
 11-4.19.4 EXPOSED PIPES & SURFACES. -- ALSO A NOTE AT
 THE LAVATORY DIAGRAM REFERENCES "DASHED LINES". THESE
 ARE NOT SHOWN AT THE LAV. PLEASE CLARIFY. SECTION
 106.1.1 & CHAPTER 11.
  
 3. SHT A.601 DETAIL 2 SHOWS CONTROL AREA FROM 39" TO
 49". PER FIGURE 37 IN CHAPTER 11, THE CONTROL AREA IS
 REQUIRED TO BE FROM 38" TO 48". PLEASE SHOW COMPLIANCE.
 -- THE SHOWER UNIT IS REQUIRED TO BE A MINIMUM 60" PER
 SECTION 11-4.21.6. PLEASE INDICATE ON DETAIL. -- THE
 CURB SHALL BE A MAXIMUM 1/2" PER SECTION 11-4.21.7.
 PLEASE INDICATE ON DETAIL.
  
 4. SHT P202 PARTIAL SANITARY WASTE PLAN & THE SANITARY
 WASTE RISER. HORIZONTAL DRY VENTS ARE PROHIBITED PER
 SECTIONS 905.3 & 905.4. (SEE CONNECT TO (E) 2"VENT LEFT
 SIDE OF (E) 4" WASTE STACK. (LAV IS VENTING W/C &
 SHOWER).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-02 Cont ID  
Sent By eschneid Date 2009-02-02 Time 16:09 Rev Time 0.50
Received By eschneid Date 2009-02-02 Time 16:09 Sent To  
Notes
2009-02-02 16:12:54FAILED PLAN REVIEW
  
 1) PLEASE NOTE THAT THE ADDRESS AND PCN ARE INCORRECT.
 THE LIMITS OF WORK ARE IN THE BUILDING LOCATED AT 4631
 N. CONGRESS WITH PCN 74434306000001030.
  
 2) NOTE THAT IF THE VALUE OF THIS PERMIT, WHEN ADDED TO
 OTHER PERMITS WITHIN THE LAST YEAR TOTAL 50% OF THE
 VALUE OF THE BUILDING, THEN A LANDSCAPE PLAN VERIFYING
 THAT THE SITE CONFORMS TO THE LANDSCAPE CODE IS
 REQUIRED.
  
 3) PLAN OTHERWISE COMPLIES WITH ZONING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.