Plan Review Details - Permit 09010160
Plan Review Stops For Permit 09010160
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-02-04 Cont ID  
Sent By rmcdouga Date 2009-02-04 Time 13:42 Rev Time 0.00
Received By rmcdouga Date 2009-02-04 Time 13:42 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-26 Cont ID  
Sent By rmcdouga Date 2009-01-26 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2009-01-26 Time 11:24 Sent To M
Notes
2009-01-26 11:48:182004 FBC W/2007 REVISIONS
 ADDITION TO KITCHEN
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED. PHONE:
 561-233-5025
  
 3) SHOW COMPLIANCE WITH R602.1.2 FIREBLOCKING REQUIRED.
 FIREBLOCKING SHALL BE PROVIDED TO CUT OFF ALL CONCEALED
 DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND TO
 FORM AN EFFECTIVE FIRE BARRIER BETWEEN STORIES, AND
 BETWEEN A TOP STORY AND THE ROOF SPACE. FIREBLOCKING
 SHALL BE PROVIDED IN WOOD-FRAME CONSTRUCTION IN THE
 FOLLOWING LOCATIONS.
 1. IN CONCEALED SPACES OF STUD WALLS AND PARTITIONS,
 INCLUDING FURRED SPACES AND PARALLEL ROWS OF STUDS OR
 STAGGERED STUDS; AS FOLLOWS:
 1.1. VERTICALLY AT THE CEILING AND FLOOR LEVELS.
 1.2. HORIZONTALLY AT INTERVALS NOT EXCEEDING 10 FEET
 (3048 MM).
 2. AT ALL INTERCONNECTIONS BETWEEN CONCEALED VERTICAL
 AND HORIZONTAL SPACES SUCH AS OCCUR AT SOFFITS, DROP
 CEILINGS AND COVE CEILINGS.
 3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT THE
 TOP AND BOTTOM OF THE RUN. ENCLOSED SPACES UNDER STAIRS
 SHALL COMPLY WITH SECTION R311.2.2.
 4. AT OPENINGS AROUND VENTS, PIPES, AND DUCTS AT
 CEILING AND FLOOR LEVEL, WITH AN APPROVED MATERIAL TO
 RESIST THE FREE PASSAGE OF FLAME AND PRODUCTS OF
 COMBUSTION.
 5. FOR THE FIREBLOCKING OF CHIMNEYS AND FIREPLACES, SEE
 SECTION R1001.16.
 6. FIREBLOCKING OF CORNICES OF A TWO-FAMILY DWELLING IS
 REQUIRED AT THE LINE OF DWELLING UNIT SEPARATION.
  
 4) SHOW COMPLIANCE WITH R320.1. TERMITE PROTECTION
 SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING
 SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS
 OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION (SEE SECTION 202,
 REGISTERED TERMITICIDE). UPON COMPLETION OF THE
 APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE
 BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ???THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.???
  
 5) R506.2.3 VAPOR RETARDER. A 6 MIL (0.006 INCH)
 POLYETHYLENE OR APPROVED VAPOR RETARDER WITH JOINTS
 LAPPED NOT LESS THAN 6 INCHES (152 MM) SHALL BE PLACED
 BETWEEN THE CONCRETE FLOOR SLAB AND THE BASE COURSE OR
 THE PREPARED SUBGRADE WHERE NO BASE COURSE EXISTS.
  
 6) SPECIFY HOW THE 2 X 4 WOOD FRAME WALL WILL BE
 ATTACHED TO THE EXISTING CONCRETE BLOCK WALL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-02-04 Cont ID  
Sent By btrobaug Date 2009-02-04 Time 14:51 Rev Time 0.00
Received By btrobaug Date 2009-02-04 Time 14:44 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-01-20 Cont ID  
Sent By btrobaug Date 2009-01-20 Time 13:48 Rev Time 0.00
Received By btrobaug Date 2009-01-20 Time 13:07 Sent To G
Notes
2009-01-20 13:48:04 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE
 OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8).
  
 2} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED***
 RELOCATING THE FLOOD AS SHOWN ON SHEET D-1.0 AND
 EXTENDING THE EXHAUST FAN CIRCUIT, SHEET A-2.0
  
 3} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. ADD THIS
 NOTE TO THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2009-02-04 Cont ID  
Sent By kstevens Date 2009-02-04 Time 15:22 Rev Time 0.00
Received By kstevens Date 2009-02-04 Time 15:22 Sent To  
Notes
2009-02-04 15:23:29SEPARATE GAS PERMIT REQUIRED. PLANS SHALL BE SUBMITTED
 WHEN APPLYING FOR PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-02-02 Cont ID  
Sent By kstevens Date 2009-02-02 Time 14:18 Rev Time 0.00
Received By kstevens Date 2009-02-02 Time 14:12 Sent To  
Notes
2009-02-02 14:32:06DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. TWO 17" X 11" FLOOR PLAN SHEETS A-1.0 SHOWING GAS
 LINE LOCATION WITH THE ARCHITECTS TITLE BLOCK SHALL BE
 SIGNED & SEALED PER SECTION 106.1, FAC 61G1-16.003 & FS
 481.2055. (NOT REQUIRED IF HAND DRAWN SHEETS
 SUBMITTED).
  
 2. TWO HAND DRAWN 8.5" X 11" GAS LINE SHEETS REQUIRE
 THE PRINTED NAME AND SIGNATURE OF THE PERSON DRAWING
 THE PLANS. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-02-03 Cont ID  
Sent By adarroug Date 2009-02-03 Time 16:18 Rev Time 0.00
Received By adarroug Date 2009-02-03 Time 16:18 Sent To E
Notes
2009-02-03 16:18:58TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 11:20 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 11:20 Sent To E
Notes
2009-01-20 11:20:21TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-02 Cont ID  
Sent By rregueir Date 2009-02-02 Time 14:32 Rev Time  
Received By kstevens Date 2009-01-13 Time 11:44 Sent To  
Notes
2009-01-13 11:47:43TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-02-01 Cont ID  
Sent By rregueir Date 2009-02-01 Time 09:14 Rev Time 0.00
Received By rregueir Date 2009-02-01 Time 09:10 Sent To G
Notes
2009-02-01 09:13:54*******PROVISO*********
  
 1. REQUIRED CLEARANCES TO COMBUSTIBLE CONSTRUCTION
 SHALL BE IN ACCORDANCE WITH KITCHEN EQUIPMENT AND HOOD
 LISTING AND SHALL BE VERIFIED BY FIELD INSPECTOR.
  
 2. PROVIDE DETAIL FOR ATTACHMENT OF FAN AND CURB FOR
 WIND RESISTANCE PRIOR RO INSPECTION PER FBCM 301.13.
  
 3. SEPARATE MECHANICAL PERMIT REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2009-01-15 Cont ID  
Sent By mcruz Date 2009-01-15 Time 11:51 Rev Time 0.00
Received By mcruz Date 2009-01-15 Time 11:40 Sent To I
Notes
***NONE***