Plan Review Details - Permit 09010116
Plan Review Stops For Permit 09010116
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 11:30 Rev Time 0.00
Received By shill Date 2009-07-15 Time 11:30 Sent To  
Notes
2009-07-15 11:32:41***PROVISO***
  
 WHEN RESUBMITTING, PROVIDE TWO DISTINCT COLLATED SETS
 FOR PERMIT ISSUANCE.
 ONE SET OF OLD SHEETS TO BE SUBMITTED FOR REFERENCE,
 MARKED "VOID."
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-08 Cont ID  
Sent By mjacobs Date 2009-04-08 Time 16:19 Rev Time 0.00
Received By mjacobs Date 2009-04-08 Time 16:19 Sent To  
Notes
2009-04-08 16:02:07BUILDING PLAN REVIEW
 PERMIT:09010116
 ADD: 7915 S. DIXIE HWY
 CONT: CHINCHOR ELECTRIC INC.
 TEL: (386)774-1020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-8-09
 REVIEW: 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NO RESPONSE NOT ADDRESSED: SHEET S-1 SHOWS TWO
 DIFFERENT TYPES OF BEAMS. DETAIL #1 SHOW A "BOND
 BEAM"WITH 2 #5 REINFORCING BARS AND THE TYPICAL MASONRY
 WALL CONSTRUCTION DETAIL SHOW A CAST IN PLACE
 REINFORCED CONCRETE TIE BEAM WITH NO DIMENSIONS.
 CLEARLY STATE WHICH BEAM DETAIL WILL BE USED? THE
 FOUNDATION PLAN DETAIL FAIL TO SHOW THE LOCATION OF THE
 VERTICAL REINFORCING BARS AS STATED IN THE NOTE BELOW.
 ON SHEET S-1, PLEASE INDICATE THE TYPE AND SIZE OF THE
 MATERIALS FOR EACH DETAIL. SHOW THE BRACING DETAIL FOR
 THE MASONRY CONSTRUCTION PER FBC 2104.1.9
  
 3) NO RESPONSE NOT ADDRESSED: SHEET E-3 SHOWS
 ADDITIONAL STRUCTURAL INFORMATION THAT IS NOT SHOWN ON
 THE SHEET (S-1), EXAMPLE THE DOORS AND BOLLARDS WITH
 THE DOT GUARDRAIL. THE NEW MASONRY WALL NEEDS TO SHOW A
 HEADER DETAIL FOR THE TWO DOORS. WILL THE DOOR HEADER
 BE CONSTRUCTED WITH A REINFORCED CONCRETE OR WILL A
 LINTEL BE USED? IF THE LINTEL WILL BE USED, PROVIDE THE
 PRODUCT APPROVAL INDICATING THE SIZE OF THE LENTIL.
 PROVIDE PRODUCT APPROVAL FOR THE TWO DOORS AND INDICATE
 OR HI-LIGHT ALL INFORMATION PERTAINING TO THE
 INSTALLATION OF THE DOORS FROM THE INSTALLATION
 INSTRUCTIONS ON EACH PAGE OF THE PRODUCT APPROVAL.
  
 4) NO RESPONSE NOT ADDRESSED: SHEET E-3 AND S-1 HAVE
 DIFFERENT ENGINEERS, THEREFORE THE WIND DESIGN
 INFORMATION SHALL BE SHOWN BY EACH ENGINEER IN
 ACCORDANCE WITH 1603.1.4 AND 1609.1.3. IS THE GUARDRAIL
 ATTACHED TO THE BOLLARDS? IF SO, PROVIDE A DETAIL FOR
 THE ATTACHMENT. THERE IS A NOTE AT THE TOP LEFT SECTION
 OF SHEET E-3 STATING "8" HIGH BLOCK WALL PAINT TO
 MATCH", ISN'T THIS A 14' HIGH WALL? CLARIFY.
  
 5) OK
  
 6) SUBMIT THE SOIL REPORT PER FBC 1802.6
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-30 Cont ID  
Sent By mjacobs Date 2009-01-30 Time 08:57 Rev Time 0.00
Received By mjacobs Date 2009-01-30 Time 08:57 Sent To  
Notes
2009-01-30 08:57:08BUILDING PLAN REVIEW
 PERMIT:09010116
 ADD: 7915 S. DIXIE HWY
 CONT: CHINCHOR ELECTRIC INC.
 TEL: (386)774-1020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1-30-09
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SHEET S-1 SHOWS TWO DIFFERENT TYPES OF BEAMS. DETAIL
 #1 SHOW A "BOND BEAM" WITH 2 #5 REINFORCING BARS AND
 THE TYPICAL MASONRY WALL CONSTRUCTION DETAIL SHOW A
 CAST IN PLACE REINFORCED CONCRETE TIE BEAM WITH NO
 DIMENSIONS. CLEARLY STATE WHICH BEAM DETAIL WILL BE
 USED? THE FOUNDATION PLAN DETAIL FAIL TO SHOW THE
 LOCATION OF THE VERTICAL REINFORCING BARS AS STATED IN
 THE NOTE BELOW. ON SHEET S-1, PLEASE INDICATE THE TYPE
 AND SIZE OF THE MATERIALS FOR EACH DETAIL. SHOW THE
 BRACING DETAIL FOR THE MASONRY CONSTRUCTION PER FBC
 2104.1.9.
  
 3) SHEET E-3 SHOWS ADDITIONAL STRUCTURAL INFORMATION
 THAT IS NOT SHOWN ON THE SHEET (S-1), EXAMPLE THE DOORS
 AND BOLLARDS WITH THE DOT GUARDRAIL. THE NEW MASONRY
 WALL NEEDS TO SHOW A HEADER DETAIL FOR THE TWO DOORS.
 WILL THE DOOR HEADER BE CONSTRUCTED WITH A REINFORCED
 CONCRETE OR WILL A LINTEL BE USED? IF THE LINTEL WILL
 BE USED, PROVIDE THE PRODUCT APPROVAL INDICATING THE
 SIZE OF THE LENTIL. PROVIDE PRODUCT APPROVAL FOR THE
 TWO DOORS AND INDICATE OR HI-LIGHT ALL INFORMATION
 PERTAINING TO THE INSTALLATION OF THE DOORS FROM THE
 INSTALLATION INSTRUCTIONS ON EACH PAGE OF THE PRODUCT
 APPROVAL.
  
 4) SHEET E-3 AND S-1 HAVE DIFFERENT ENGINEERS,
 THEREFORE THE WIND DESIGN INFORMATION SHALL BE SHOWN BY
 EACH ENGINEER IN ACCORDANCE WITH 1603.1.4 AND 1609.1.3.
 IS THE GUARDRAIL ATTACHED TO THE BOLLARDS? IF SO,
 PROVIDE A DETAIL FOR THE ATTACHMENT. THERE IS A NOTE AT
 THE TOP LEFT SECTION OF SHEET E-3 STATING "8" HIGH
 BLOCK WALL PAINT TO MATCH", ISN'T THIS A 14'HIGH WALL?
 CLARIFY.
  
 5) NOTE: THE EXISTING EMERGENCY GENERATOR LOCATED IN
 THE ELECTRICAL AND MECHANICAL ROOM SHALL BE LOCATED IN
 A SEPARATE ROOM ENCLOSED WITH A 2-HOUR
 FIRE-RESISTANCE-RATED FIRE BARRIER ASSEMBLY. SEE SHEET
 E-3.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-09-29 Cont ID  
Sent By dpalmer Date 2009-09-29 Time 10:38 Rev Time 0.00
Received By dpalmer Date 2009-09-29 Time 10:38 Sent To  
Notes
2009-09-29 10:40:24NEEDS SETS OF PLANS TO BE MADE INTO TWO COMPLETE SETS.
 MAY NOT HAVE SUB BASE LP TANK AS SHOWN ON PLANS.
 STILL NEEDS LP REVIEW
 VALUE FOR SCOPE NEEDS TO INCREASE AS SCOPE OF WORK HAS
 SUBSTANTIALLY INCREASED FROM ORIGINAL APPLICATION.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-07-08 Cont ID  
Sent By btrobaug Date 2009-07-08 Time 10:58 Rev Time 0.00
Received By btrobaug Date 2009-07-08 Time 08:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-29 Cont ID  
Sent By btrobaug Date 2009-04-29 Time 16:12 Rev Time 0.00
Received By btrobaug Date 2009-04-28 Time 15:23 Sent To PC
Notes
2009-04-30 09:01:18 
  
  
  
 PROVISO
  
 THE "MAIN BONDING JUMPER" SHOWN INSTALLED IN THE
 GENERATOR, SHEET "E-4" MUST NOT BE INSTALLED AS IT
 CREATES A PARALLEL PATH BETWEEN THE GENERATOR NEUTRAL
 AND THE SYSTEM EQUIPMENT GROUND. THE EQUIPMENT GROUND
 AND NEUTRAL MUST REMAIN ISOLATED, 250.6 NEC, UNLESS THE
 GENERATOR WAS A SEPARATELY DERIVED SYSTEM, WHICH WOULD
 REQUIRE A 4 POLE ATS.
  
 SUBMIT MANUFACTURERS SPECIFICATIONS FOR THE NEW 60KW
 EMERGENCY GENERATOR SHOWN ON SHEET E-1.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-01-28 Cont ID  
Sent By btrobaug Date 2009-01-28 Time 16:35 Rev Time 0.00
Received By btrobaug Date 2009-01-27 Time 08:47 Sent To  
Notes
2009-01-28 16:20:08 
  
  
 APPLICATION #09010116 ELECTRICAL PLAN REVIEW
 7915 S. DIXIE HIGHWAY 1/28/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE EMERGENCY GENERATOR AS IT CURRENTLY EXISTS IS IN
 VIOLATION OF THE FOLLOWING CODES:
  
 A) 700.12(B)(3) DUAL SUPPLIES- PRIME MOVERS SHALL NOT
 BE SOLELY DEPENDENT ON A PUBLIC UTILITY GAS SYSTEM FOR
 THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY FOR THEIR
 COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR
 AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO
 ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED.
 B) NFPA-110 7.2 LOCATION. 7.2.1.1 THE ROOM SHALL HAVE A
 MINIMUM 2-HOUR FIRE RATING OR BE LOCATED IN AN ADEQUATE
 ENCLOSURE LOCATED OUTSIDE THE BUILDING CAPABLE OF
 RESISTING THE ENTRANCE OF SNOW OR RAIN AT A MAXIMUM
 WIND VELOCITY REQUIRED BY LOCAL BUILDING CODES.
 C) 7.2.1.2 NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE,
 SHALL BE PERMITTED IN THIS ROOM.
 D) 7.2.2 EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE
 SAME ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT
 IS INSTALLED.
  
 NOTE: IF THERE ARE NO LEGALLY REQUIRED SYSTEMS IN THE
 BUILDING BEING FED FROM THE EXISTING GENERATOR THEN IT
 ALSO BECOMES AN "OPTIONAL STANDBY SYSTEM" AND NONE OF
 THE ABOVE COMMENTS APPLY. AS I DISCUSSED WITH MR.
 VARGAS WHEN I REVIEWED THE PLANS PREVIOUSLY, IF THE
 REQUIRED EMERGENCY LIGHTING WHERE BATTERY BACK UP ALL
 ISSUES ARE SOLVED.
  
 2} THE "EXISTING SINGLE LINE DIAGRAM" ON SHEET E-1 DOES
 NOT CORRELATE WITH THE ELECTRICAL
 RISER DIAGRAM SUBMITTED FOR PERMIT NUMBER 08040571,
 WHICH SHOWS PANEL "CP" FED FROM THE "EM" PANEL.
  
 3} IT IS NOT CLEAR IN THE SPECIFICATIONS IF THE ATS IS
 CAPABLE OF DISCONNECTING UTILITY POWER AND GENERATOR
 POWER. THAT APPEARS FUNCTION TO BE AN OPTION, PLEASE
 CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-04-15 Cont ID  
Sent By mawillia Date 2009-04-15 Time 12:47 Rev Time 0.00
Received By mawillia Date 2009-04-15 Time 12:35 Sent To  
Notes
2009-04-15 12:46:09*****PROVISO*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-02-02 Cont ID  
Sent By mawillia Date 2009-02-02 Time 15:07 Rev Time 0.00
Received By mawillia Date 2009-02-02 Time 14:55 Sent To  
Notes
2009-02-02 15:07:11*****PROVISO*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2009-04-16 Cont ID  
Sent By rregueir Date 2009-04-16 Time 08:03 Rev Time 0.00
Received By rregueir Date 2009-04-16 Time 08:02 Sent To  
Notes
2009-04-16 08:05:51PREVIOUS REVIEW PASSED UNDER MECHANICAL REVIEW STOP.
 PLEASE BE SURE TO RETURN TWO COPIES OF PLANS WHICH WERE
 STAMPED AND APPROVED BY PALM BEACH COUNTY DERM WHEN
 RESUBMITTING PLANS. ONE IS REQUIRED FOR THE PERMIT
 RECORDS AND ONE FOR THE FIELD SET.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2009-02-05 Cont ID  
Sent By kstevens Date 2009-02-05 Time 11:46 Rev Time 0.00
Received By kstevens Date 2009-02-05 Time 11:45 Sent To  
Notes
2009-02-05 11:46:28GENERATOR FUEL DIESEL ONLY.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-06-17 Cont ID  
Sent By shill Date 2009-06-17 Time 08:43 Rev Time 0.00
Received By shill Date 2009-06-17 Time 08:43 Sent To  
Notes
2009-06-17 08:43:23C 25
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-06 Cont ID  
Sent By adarroug Date 2009-04-06 Time 16:03 Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 16:03 Sent To  
Notes
2009-04-06 16:03:43TO "B18"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-29 Cont ID  
Sent By btrobaug Date 2009-02-09 Time 16:12 Rev Time 0.00
Received By btrobaug Date 2009-01-22 Time 09:02 Sent To PC
Notes
2009-01-27 09:05:23 
  
  
  
 RESET "I" STOP TO 1/22/09, THE DATE AVAILABLE FOR
 REVIEW AFTER THE CONTRACTOR BROUGHT THEM BACK FROM THE
 COUNTY FOR DERM REVIEW./WRT.
2009-01-26 08:55:481/26/09--TO "BOB"#13/ PLANS PULLED FROM REVIEW AND
 SUBMITTED BACK IN ON 1/22/09
2009-01-13 09:01:08TO "BOB"#1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-02-05 Cont ID  
Sent By rregueir Date 2009-02-05 Time 19:30 Rev Time 0.00
Received By rregueir Date 2009-02-05 Time 19:30 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-09-29 Cont ID  
Sent By kstevens Date 2009-09-29 Time 10:37 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
2009-09-29 10:38:02THIS STOP TO PREVENT ISSUANCE OF PERMIT UNTIL NEW GAS
 REVIEW IS COMPLETE.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-06-30 Cont ID  
Sent By lfranco Date 2009-06-30 Time 15:33 Rev Time 0.00
Received By lfranco Date 2009-06-30 Time 15:33 Sent To  
Notes
2009-06-30 15:33:40 
 PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THIS PROPERTY IS PART OF THE SHOPPES AT PALM COAST
 PLAZA DEVELOPMENT OF SIGNIFICANT IMPACT (" DSI"), AN
 APPLICATION FOR A MINOR AMENDMENT TO THE DSI SHOWING
 THE PROPOSED GENERATOR (+/-10 HIGH W/O SLAB) AND NEW
 GAS TANK FOR THE WINN DIXIE GROCERY STORE WILL BE
 REQUIRED TO BE FILED TO THE PLANNING AND ZONING
 DEPARTMENT AND APPROVED PRIOR TO THE BUILDING PERMIT
 BEING APPROVED. SEE
 HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER
 DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR DSI
 AMENDMENT.
  
 THE COMMENTS BELOW REFLECT THE INFORMATION NEEDED ON
 SITE PLAN, PRIOR TO SUBMITTAL OF THE MINOR AMENDMENT TO
 THE DSI.
  
 3. THE SITE PLAN SHALL INCLUDE THE FOLLOWING:
  
 A. PROVIDE ELEVATIONS WITH DIMENSIONS INCLUDING TOTAL
 HEIGHT OF GENERATOR AND TANK TO INCLUDE SLAB. PROVIDE A
 FLOOR PLAN OF SCREENING AND LANDSCAPING DETAIL. INCLUDE
 WALL/FENCE HEIGHT, ETC.,
 B. PROVIDE SETBACK DISTANCE FROM PROPERTY LINE.
  
 NOTE: PROVIDE DETAIL OF ALL ENCLOSURES WITH LANDSCAPING
 ON THE SITE PLAN/FLOOR PLANS.
  
 4. PURSUANT TO SECTION 94-444(B) OPEN SPACE
 STANDARDS:
  
 (B) FUEL OR OIL OR PROPANE TANKS, GENERATORS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND
 STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. PROVIDE TYPE OF
 LANDSCAPING TO BE INSTALLED. A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH THE GENERATOR AND GAS
 TANK INCLUDING ROOFTOP EXHAUST.
  
 5. PURSUANT TO SECTION 94-305(B)(4) SETBACKS (B)(4)
 SETBACK ENCROACHMENT:
 MECHANICAL EQUIPMENT SHALL NOT PROJECT MORE THAN 4 FEET
 INTO A SETBACK.
  
 6. THE PROPOSED GENERATOR AND GAS TANK ARE PROPOSED ON
 TOP OF EXISTING PARKING STALLS. IF THESE ARE REQUIRED
 PARKING SPACES, WHERE ARE THE PARKING SPACES PROPOSED
 TO BE MITIGATED/RELOCATED? OTHERWISE, A NEW LOCATION
 FOR THE GENERATOR/GAS TANK WILL HAVE TO BE PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  
  