| Plan Review Stops For Permit 09010116 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-07-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-07-15 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-07-15 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2009-07-15 11:32:41 | ***PROVISO*** | | | | | | WHEN RESUBMITTING, PROVIDE TWO DISTINCT COLLATED SETS | | | FOR PERMIT ISSUANCE. | | | ONE SET OF OLD SHEETS TO BE SUBMITTED FOR REFERENCE, | | | MARKED "VOID." | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-04-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-04-08 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-04-08 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2009-04-08 16:02:07 | BUILDING PLAN REVIEW | | | PERMIT:09010116 | | | ADD: 7915 S. DIXIE HWY | | | CONT: CHINCHOR ELECTRIC INC. | | | TEL: (386)774-1020 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 4-8-09 | | | REVIEW: 2ND | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) NO RESPONSE NOT ADDRESSED: SHEET S-1 SHOWS TWO | | | DIFFERENT TYPES OF BEAMS. DETAIL #1 SHOW A "BOND | | | BEAM"WITH 2 #5 REINFORCING BARS AND THE TYPICAL MASONRY | | | WALL CONSTRUCTION DETAIL SHOW A CAST IN PLACE | | | REINFORCED CONCRETE TIE BEAM WITH NO DIMENSIONS. | | | CLEARLY STATE WHICH BEAM DETAIL WILL BE USED? THE | | | FOUNDATION PLAN DETAIL FAIL TO SHOW THE LOCATION OF THE | | | VERTICAL REINFORCING BARS AS STATED IN THE NOTE BELOW. | | | ON SHEET S-1, PLEASE INDICATE THE TYPE AND SIZE OF THE | | | MATERIALS FOR EACH DETAIL. SHOW THE BRACING DETAIL FOR | | | THE MASONRY CONSTRUCTION PER FBC 2104.1.9 | | | | | | 3) NO RESPONSE NOT ADDRESSED: SHEET E-3 SHOWS | | | ADDITIONAL STRUCTURAL INFORMATION THAT IS NOT SHOWN ON | | | THE SHEET (S-1), EXAMPLE THE DOORS AND BOLLARDS WITH | | | THE DOT GUARDRAIL. THE NEW MASONRY WALL NEEDS TO SHOW A | | | HEADER DETAIL FOR THE TWO DOORS. WILL THE DOOR HEADER | | | BE CONSTRUCTED WITH A REINFORCED CONCRETE OR WILL A | | | LINTEL BE USED? IF THE LINTEL WILL BE USED, PROVIDE THE | | | PRODUCT APPROVAL INDICATING THE SIZE OF THE LENTIL. | | | PROVIDE PRODUCT APPROVAL FOR THE TWO DOORS AND INDICATE | | | OR HI-LIGHT ALL INFORMATION PERTAINING TO THE | | | INSTALLATION OF THE DOORS FROM THE INSTALLATION | | | INSTRUCTIONS ON EACH PAGE OF THE PRODUCT APPROVAL. | | | | | | 4) NO RESPONSE NOT ADDRESSED: SHEET E-3 AND S-1 HAVE | | | DIFFERENT ENGINEERS, THEREFORE THE WIND DESIGN | | | INFORMATION SHALL BE SHOWN BY EACH ENGINEER IN | | | ACCORDANCE WITH 1603.1.4 AND 1609.1.3. IS THE GUARDRAIL | | | ATTACHED TO THE BOLLARDS? IF SO, PROVIDE A DETAIL FOR | | | THE ATTACHMENT. THERE IS A NOTE AT THE TOP LEFT SECTION | | | OF SHEET E-3 STATING "8" HIGH BLOCK WALL PAINT TO | | | MATCH", ISN'T THIS A 14' HIGH WALL? CLARIFY. | | | | | | 5) OK | | | | | | 6) SUBMIT THE SOIL REPORT PER FBC 1802.6 | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | PHONE (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-01-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-01-30 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-01-30 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2009-01-30 08:57:08 | BUILDING PLAN REVIEW | | | PERMIT:09010116 | | | ADD: 7915 S. DIXIE HWY | | | CONT: CHINCHOR ELECTRIC INC. | | | TEL: (386)774-1020 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1-30-09 | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) SHEET S-1 SHOWS TWO DIFFERENT TYPES OF BEAMS. DETAIL | | | #1 SHOW A "BOND BEAM" WITH 2 #5 REINFORCING BARS AND | | | THE TYPICAL MASONRY WALL CONSTRUCTION DETAIL SHOW A | | | CAST IN PLACE REINFORCED CONCRETE TIE BEAM WITH NO | | | DIMENSIONS. CLEARLY STATE WHICH BEAM DETAIL WILL BE | | | USED? THE FOUNDATION PLAN DETAIL FAIL TO SHOW THE | | | LOCATION OF THE VERTICAL REINFORCING BARS AS STATED IN | | | THE NOTE BELOW. ON SHEET S-1, PLEASE INDICATE THE TYPE | | | AND SIZE OF THE MATERIALS FOR EACH DETAIL. SHOW THE | | | BRACING DETAIL FOR THE MASONRY CONSTRUCTION PER FBC | | | 2104.1.9. | | | | | | 3) SHEET E-3 SHOWS ADDITIONAL STRUCTURAL INFORMATION | | | THAT IS NOT SHOWN ON THE SHEET (S-1), EXAMPLE THE DOORS | | | AND BOLLARDS WITH THE DOT GUARDRAIL. THE NEW MASONRY | | | WALL NEEDS TO SHOW A HEADER DETAIL FOR THE TWO DOORS. | | | WILL THE DOOR HEADER BE CONSTRUCTED WITH A REINFORCED | | | CONCRETE OR WILL A LINTEL BE USED? IF THE LINTEL WILL | | | BE USED, PROVIDE THE PRODUCT APPROVAL INDICATING THE | | | SIZE OF THE LENTIL. PROVIDE PRODUCT APPROVAL FOR THE | | | TWO DOORS AND INDICATE OR HI-LIGHT ALL INFORMATION | | | PERTAINING TO THE INSTALLATION OF THE DOORS FROM THE | | | INSTALLATION INSTRUCTIONS ON EACH PAGE OF THE PRODUCT | | | APPROVAL. | | | | | | 4) SHEET E-3 AND S-1 HAVE DIFFERENT ENGINEERS, | | | THEREFORE THE WIND DESIGN INFORMATION SHALL BE SHOWN BY | | | EACH ENGINEER IN ACCORDANCE WITH 1603.1.4 AND 1609.1.3. | | | IS THE GUARDRAIL ATTACHED TO THE BOLLARDS? IF SO, | | | PROVIDE A DETAIL FOR THE ATTACHMENT. THERE IS A NOTE AT | | | THE TOP LEFT SECTION OF SHEET E-3 STATING "8" HIGH | | | BLOCK WALL PAINT TO MATCH", ISN'T THIS A 14'HIGH WALL? | | | CLARIFY. | | | | | | 5) NOTE: THE EXISTING EMERGENCY GENERATOR LOCATED IN | | | THE ELECTRICAL AND MECHANICAL ROOM SHALL BE LOCATED IN | | | A SEPARATE ROOM ENCLOSED WITH A 2-HOUR | | | FIRE-RESISTANCE-RATED FIRE BARRIER ASSEMBLY. SEE SHEET | | | E-3. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | PHONE (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2009-09-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-09-29 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-09-29 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2009-09-29 10:40:24 | NEEDS SETS OF PLANS TO BE MADE INTO TWO COMPLETE SETS. | | | MAY NOT HAVE SUB BASE LP TANK AS SHOWN ON PLANS. | | | STILL NEEDS LP REVIEW | | | VALUE FOR SCOPE NEEDS TO INCREASE AS SCOPE OF WORK HAS | | | SUBSTANTIALLY INCREASED FROM ORIGINAL APPLICATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-07-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-07-08 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-07-08 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-04-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-04-29 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-04-28 |
Time |
15:23 |
Sent To |
PC |
|
| Notes |
| 2009-04-30 09:01:18 | | | | | | | | | | | | | PROVISO | | | | | | THE "MAIN BONDING JUMPER" SHOWN INSTALLED IN THE | | | GENERATOR, SHEET "E-4" MUST NOT BE INSTALLED AS IT | | | CREATES A PARALLEL PATH BETWEEN THE GENERATOR NEUTRAL | | | AND THE SYSTEM EQUIPMENT GROUND. THE EQUIPMENT GROUND | | | AND NEUTRAL MUST REMAIN ISOLATED, 250.6 NEC, UNLESS THE | | | GENERATOR WAS A SEPARATELY DERIVED SYSTEM, WHICH WOULD | | | REQUIRE A 4 POLE ATS. | | | | | | SUBMIT MANUFACTURERS SPECIFICATIONS FOR THE NEW 60KW | | | EMERGENCY GENERATOR SHOWN ON SHEET E-1. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-01-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-01-28 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-01-27 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2009-01-28 16:20:08 | | | | | | | | | | APPLICATION #09010116 ELECTRICAL PLAN REVIEW | | | 7915 S. DIXIE HIGHWAY 1/28/09 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE EMERGENCY GENERATOR AS IT CURRENTLY EXISTS IS IN | | | VIOLATION OF THE FOLLOWING CODES: | | | | | | A) 700.12(B)(3) DUAL SUPPLIES- PRIME MOVERS SHALL NOT | | | BE SOLELY DEPENDENT ON A PUBLIC UTILITY GAS SYSTEM FOR | | | THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY FOR THEIR | | | COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR | | | AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO | | | ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED. | | | B) NFPA-110 7.2 LOCATION. 7.2.1.1 THE ROOM SHALL HAVE A | | | MINIMUM 2-HOUR FIRE RATING OR BE LOCATED IN AN ADEQUATE | | | ENCLOSURE LOCATED OUTSIDE THE BUILDING CAPABLE OF | | | RESISTING THE ENTRANCE OF SNOW OR RAIN AT A MAXIMUM | | | WIND VELOCITY REQUIRED BY LOCAL BUILDING CODES. | | | C) 7.2.1.2 NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL | | | APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE, | | | SHALL BE PERMITTED IN THIS ROOM. | | | D) 7.2.2 EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE | | | SAME ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT | | | IS INSTALLED. | | | | | | NOTE: IF THERE ARE NO LEGALLY REQUIRED SYSTEMS IN THE | | | BUILDING BEING FED FROM THE EXISTING GENERATOR THEN IT | | | ALSO BECOMES AN "OPTIONAL STANDBY SYSTEM" AND NONE OF | | | THE ABOVE COMMENTS APPLY. AS I DISCUSSED WITH MR. | | | VARGAS WHEN I REVIEWED THE PLANS PREVIOUSLY, IF THE | | | REQUIRED EMERGENCY LIGHTING WHERE BATTERY BACK UP ALL | | | ISSUES ARE SOLVED. | | | | | | 2} THE "EXISTING SINGLE LINE DIAGRAM" ON SHEET E-1 DOES | | | NOT CORRELATE WITH THE ELECTRICAL | | | RISER DIAGRAM SUBMITTED FOR PERMIT NUMBER 08040571, | | | WHICH SHOWS PANEL "CP" FED FROM THE "EM" PANEL. | | | | | | 3} IT IS NOT CLEAR IN THE SPECIFICATIONS IF THE ATS IS | | | CAPABLE OF DISCONNECTING UTILITY POWER AND GENERATOR | | | POWER. THAT APPEARS FUNCTION TO BE AN OPTION, PLEASE | | | CLARIFY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-04-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-04-15 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-15 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2009-04-15 12:46:09 | *****PROVISO***** | | | | | | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | | THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2009-02-02 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-02-02 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-02-02 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2009-02-02 15:07:11 | *****PROVISO***** | | | | | | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | | THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
1 |
Status |
P |
Date |
2009-04-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-04-16 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-04-16 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2009-04-16 08:05:51 | PREVIOUS REVIEW PASSED UNDER MECHANICAL REVIEW STOP. | | | PLEASE BE SURE TO RETURN TWO COPIES OF PLANS WHICH WERE | | | STAMPED AND APPROVED BY PALM BEACH COUNTY DERM WHEN | | | RESUBMITTING PLANS. ONE IS REQUIRED FOR THE PERMIT | | | RECORDS AND ONE FOR THE FIELD SET. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-05 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-05 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2009-02-05 11:46:28 | GENERATOR FUEL DIESEL ONLY. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-06-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-06-17 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-06-17 |
Time |
08:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-04-06 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-04-06 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2009-04-06 16:03:43 | TO "B18" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-04-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-02-09 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-01-22 |
Time |
09:02 |
Sent To |
PC |
|
| Notes |
| 2009-01-27 09:05:23 | | | | | | | | | | | | | RESET "I" STOP TO 1/22/09, THE DATE AVAILABLE FOR | | | REVIEW AFTER THE CONTRACTOR BROUGHT THEM BACK FROM THE | | | COUNTY FOR DERM REVIEW./WRT. | | 2009-01-26 08:55:48 | 1/26/09--TO "BOB"#13/ PLANS PULLED FROM REVIEW AND | | | SUBMITTED BACK IN ON 1/22/09 | | 2009-01-13 09:01:08 | TO "BOB"#1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-05 |
Time |
19:30 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-05 |
Time |
19:30 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-09-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-29 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2009-09-29 10:38:02 | THIS STOP TO PREVENT ISSUANCE OF PERMIT UNTIL NEW GAS | | | REVIEW IS COMPLETE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-06-30 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-06-30 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-06-30 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2009-06-30 15:33:40 | | | | PLANNING AND ZONING: **** FAILED **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. THIS PROPERTY IS PART OF THE SHOPPES AT PALM COAST | | | PLAZA DEVELOPMENT OF SIGNIFICANT IMPACT (" DSI"), AN | | | APPLICATION FOR A MINOR AMENDMENT TO THE DSI SHOWING | | | THE PROPOSED GENERATOR (+/-10 HIGH W/O SLAB) AND NEW | | | GAS TANK FOR THE WINN DIXIE GROCERY STORE WILL BE | | | REQUIRED TO BE FILED TO THE PLANNING AND ZONING | | | DEPARTMENT AND APPROVED PRIOR TO THE BUILDING PERMIT | | | BEING APPROVED. SEE | | | HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER | | | DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR DSI | | | AMENDMENT. | | | | | | THE COMMENTS BELOW REFLECT THE INFORMATION NEEDED ON | | | SITE PLAN, PRIOR TO SUBMITTAL OF THE MINOR AMENDMENT TO | | | THE DSI. | | | | | | 3. THE SITE PLAN SHALL INCLUDE THE FOLLOWING: | | | | | | A. PROVIDE ELEVATIONS WITH DIMENSIONS INCLUDING TOTAL | | | HEIGHT OF GENERATOR AND TANK TO INCLUDE SLAB. PROVIDE A | | | FLOOR PLAN OF SCREENING AND LANDSCAPING DETAIL. INCLUDE | | | WALL/FENCE HEIGHT, ETC., | | | B. PROVIDE SETBACK DISTANCE FROM PROPERTY LINE. | | | | | | NOTE: PROVIDE DETAIL OF ALL ENCLOSURES WITH LANDSCAPING | | | ON THE SITE PLAN/FLOOR PLANS. | | | | | | 4. PURSUANT TO SECTION 94-444(B) OPEN SPACE | | | STANDARDS: | | | | | | (B) FUEL OR OIL OR PROPANE TANKS, GENERATORS SHALL NOT | | | BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED. | | | SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE | | | CONCRETE, OTHER | | | DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND | | | STEEL. | | | | | | WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES | | | PLANTED AT TWO-FOOT INTERVALS. PROVIDE TYPE OF | | | LANDSCAPING TO BE INSTALLED. A FOUR-SIDED ENCLOSURE | | | WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN | | | OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN | | | APPROVAL. | | | | | | THE SCREENING SHALL ENCLOSE BOTH THE GENERATOR AND GAS | | | TANK INCLUDING ROOFTOP EXHAUST. | | | | | | 5. PURSUANT TO SECTION 94-305(B)(4) SETBACKS (B)(4) | | | SETBACK ENCROACHMENT: | | | MECHANICAL EQUIPMENT SHALL NOT PROJECT MORE THAN 4 FEET | | | INTO A SETBACK. | | | | | | 6. THE PROPOSED GENERATOR AND GAS TANK ARE PROPOSED ON | | | TOP OF EXISTING PARKING STALLS. IF THESE ARE REQUIRED | | | PARKING SPACES, WHERE ARE THE PARKING SPACES PROPOSED | | | TO BE MITIGATED/RELOCATED? OTHERWISE, A NEW LOCATION | | | FOR THE GENERATOR/GAS TANK WILL HAVE TO BE PROVIDED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | | | | | | | | | | |
|
|