| | BUILDING PLAN REVIEW |
| | PERMIT: 09010077 |
| | ADD: 817 7TH STREET |
| | CONT: ORANGE SUN INC. |
| | TEL: (954)545-3215 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE |
| | PLANS. |
| | |
| | 3) THE PLANS NEED TO CLEARLY SHOW ALL AREAS WHERE THE |
| | WOOD SIDING WILL BE REPLACED; THE PLANS SUBMITTED SHOW |
| | ONE SECTION WHERE THE SIDING WILL BE REPLACED. IF MORE |
| | AREAS OF THE BUILDING WILL HAVE THE SIDING REPLACED, |
| | THEY SHALL BE INDICATED ON THE PLANS. PROVIDE A FULL |
| | SET OF DRAWINGS TO SHOW ALL AREAS OF PROPOSED WORK. |
| | |
| | 4) THE APPLICATION STATES REMOVE AND REPLACE WINDOWS |
| | BUT, IT IS NOT CLEAR HOW MANY WINDOWS WILL BE REPLACED. |
| | THE PLANS NEED TO CLEARLY SHOW THE LOCATION AND THE |
| | SIZE OF EACH WINDOW TO BE REPLACED. IF THE AGGREGATE |
| | AREA OF THE GLAZING EXCEEDS 25 PERCENT OF THE AGGREGATE |
| | AREA OF THE GLAZED OPENINGS IN THE BUILDING, IMPACT |
| | PROTECTION SHALL BE PROVIDED FOR EACH OPENING FBC |
| | (EXISTING) 507.3. |
| | |
| | 5) PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THE IMPACT |
| | PROTECTION OF THE WINDOWS. IF THE EXISTING WINDOWS |
| | ALREADY HAVE IMPACT PROTECTION, THIS INFORMATION SHALL |
| | BE SHOWN ON THE PLANS FBC (RESIDENTIAL) R301.2.1.2. |
| | |
| | 6) THE NEW WINDOW HEADER DETAIL ON SHEET A1.0 SHALL BE |
| | CONSTRUCTED IN ACCORDANCE WITH FIGURE R602.2 (2). |
| | DETAIL #6 DOES NOT COMPLY WITH THIS SECTION. THE |
| | DRAWINGS SHALL ALSO STATE THE SPECIES AND GRADE OF WOOD |
| | BEING USED FOR THE FRAMING REPAIRS. THE GALVANIZED |
| | STEEL CHANNEL FOR THE SHUTTERS SHALL BE SECURED TO |
| | STRUCTURE OF THE BUILDING IN ACCORDANCE WITH THE |
| | PRODUCT APPROVAL. |
| | |
| | 7) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 8) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |