Plan Review Details - Permit 09010050
Plan Review Stops For Permit 09010050
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-15 Cont ID  
Sent By mjacobs Date 2009-01-15 Time 12:07 Rev Time 0.00
Received By mjacobs Date 2009-01-15 Time 12:07 Sent To  
Notes
2009-01-15 12:07:32 
 BUILDING PLAN REVIEW
 PERMIT: 09010050
 ADD: 435 SOUTHERN BLVD
 CONT: ALTMAN BROTHERS, LLC
 TEL: (561)694-1651
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1-15-09
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) 106.1.2 ADDITIONAL INFORMATION IS REQUIRED TO DO AN
 ADEQUATE REVIEW. THE PLANS NEED TO STATE A) THE TYPE OF
 CONSTRUCTION AS DEFINED IN CHAPTER 6 /TABLE 601 AND
 TABLE 503.
 B) THE USE AND OCCUPANCY IN ACCORDANCE WITH CHAPTER 3
 C) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED,
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 5) OUR SYSTEM SHOWS THE TYPE OF LICENSE FOR THIS
 ADDRESS IS FOR THE ?SALE OF CABINETRY? NOT
 MANUFACTURING. IF ANY MANUFACTURING IS CARRIED OUT AT
 THIS LOCATION, THE APPROPRIATE LICENSE WILL BE REQUIRED
 AND CAN BE OBTAIN FROM THIS OFFICE.
  
 NOTE: THIS REVIEW WILL BE COMPLETED WITH THE FOLLOWING
 ASSUMPTION, THE WOOD WORKING SHOP WILL BE CONSIDERED
 FACTORY-INDUSTRIAL F1 SINCE SECTION 306 OF THE BUILDING
 CODE DOES LIST MILLWORK (SASH & DOOR) AS A F1
 OCCUPANCY.
  
 THE NEXT ISSUE WILL BE HOW TO CLASSIFY THE SAWDUST THAT
 IS CREATED WHEN WORK IS BEING COMPLETED. THE WOOD
 BEFORE IT IS CUT IS A MINOR HAZARD BUT WHEN SAWDUST IS
 CREATED, THE SAWDUST IS VERY COMBUSTIBLE AND CREATES A
 HIGH HAZARD OR H-2 OCCUPANCY. TABLE 307.7(1) IS FOR THE
 MAXIMUM ALLOWABLE QUANTITIES OF MATERIAL ALLOWED PER
 CONTROL AREA THAT POSES A PHYSICAL HAZARD. WHEN YOU
 SCAN THE TABLE THERE IS NO CATEGORY FOR COMBUSTIBLE
 DUST, THERE IS FOR COMBUSTIBLE DUST INTO AN H-2
 CATEGORY. SEE 415.7 GROUP H-2.
  
 415.7.1 COMBUSTIBLE DUSTS, GRAIN PROCESSING AND
 STORAGE.
 THE PROVISIONS OF SECTIONS 415.7.1.1 THROUGH 415.7.1.5
 SHALL APPLY TO BUILDINGS IN WHICH MATERIALS THAT
 PRODUCE COMBUSTIBLE DUSTS ARE STORED OR HANDLED.
 BUILDINGS THAT STORE OR HANDLE COMBUSTIBLE DUSTS SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF NFPA 61, NFPA
 120, NFPA 651, NFPA 654, NFPA 655, NFPA 664 AND NFPA
 85, AND THE FLORIDA FIRE PREVENTION CODE.
  
 NFPA 664 IS THE STANDARD FOR THE PREVENTION OF FIRE AND
 EXPLOSIONS IN WOOD PROCESSING FACILITIES 2007 EDITION.
 THE DUST COLLECTION SYSTEM SHALL BE DESIGN AND
 CONSTRUCTED IN ACCORDANCE WITH NFPA 664. THE DESIGNER
 AND INSTALLER QUALIFICATIONS SHALL BE IN ACCORDANCE
 WITH SECTION 4.4.
  
 PLEASE PROVIDE INFORMATION ON THE BULK STORAGE TANK
 SIZE IN WIDTH DEPTH AND HEIGHT AS WELL AS CUBIC FEET.
 PROVIDE DOCUMENTATION ON THE HOUSE KEEPING AND
 INSPECTION PROGRAMS AND MAINTENANCE OF THE UNIT. 11.1
 GENERAL REQUIREMENTS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (805) 805-6676
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-01-13 Cont ID  
Sent By btrobaug Date 2009-01-13 Time 11:36 Rev Time 0.00
Received By btrobaug Date 2009-01-13 Time 09:51 Sent To  
Notes
2009-01-13 11:36:00 
  
 APPLICATION #09010050 ELECTRICAL PLAN REVIEW
 435 SOUTHERN BLVD.
 WEST PALM BEACH, FL. 1/13/09
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE 40 HP 3 PHASE, 208 VOLT MOTOR SHOWN ON SHEET M-1
 IS LISTED AS 104 AMPS. PER TABLE 430.250 THE CORRECT
 AMPERAGE WOULD BE 114 AMPS.
  
 2} THE #1 THHN CONDUCTORS FEEDING THE DISCONNECT ?A?,
 AND THE 40 HP MOTOR, ARE NONCOMPLIANT WITH 430.250,
 430.22(E), 310.16.
  
 3} SHEET 4/4 OF THE ENGINEERED PLANS LIST THE MATERIAL
 HANDLING FAN AS 20 HP. CORRELATE WITH M-1, PROVIDE
 MANUFACTURERS SPECIFICATIONS FOR THE MOTOR STARTER AND
 THE EXHAUST/MATERIAL HANDLING FAN.
  
 4} THE AIR LOCK FAN ON SHEET M-1 IS LISTED AS 1 HP
 THREE PHASE 208 VOLTS @201 AMPS.PER 430.250 THE
 AMPERAGE SHOULD BE 4.6. SEE 430.22(E)
  
 5} SAME COMMENT FOR THE REGENERATION FAN LISTED AT 6.3
 AMPS, 7.5 AMPS PER 430.250.
  
 6} ALL ENGINEERED SHEETS REFERENCE THE 2006
 SUPPLEMENTS, SHOULD REFERENCE 2007
  
 7} THE DUST COLLECTOR EXHAUST FAN IS LISTED AT 230
 VOLTS. THE SERVICE IS 208 VOLTS. 408.4 NEC.
  
 8} INICATE WHAT THE COLLECTOR IS BEING USED FOR.
 DECLARE LOCATION PER ARTICLE 500, SHOW COMPLIANCE WITH
 THE WIRING METHODS DECLARED.
  
 9} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATION NUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-01-22 Cont ID  
Sent By mwennerg Date 2009-01-22 Time 10:52 Rev Time 0.00
Received By mwennerg Date 2009-01-22 Time 10:52 Sent To  
Notes
2009-01-22 11:05:42***DENIED***
  
 1) PLEASE PROVIDE ADDITIONAL INFORMATION ILLUSTRATING
 THE EQUIPMENT LOCATION AS IT RELATES TO REQUIRED MEANS
 OF EGRESS.
  
 2) WORK SHALL COMPLY WITH APPLICABLE BUILDING CODES AND
 FLORIDA FIRE PREVENTION CODE, 2007 EDITION.
  
 3) PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING ANY
 EXISTING BUILDING FIRE PROTECTION SYSTEMS IF
 APPLICABLE. FIRE SPRINKLER, FIRE ALARM ETC)
  
 4) WORK TO COMPLY WITH NFPA 664, STANDARD FOR THE
 PREVENTION OF FIRE AND EXPLOSIONS IN WOOD PROCESSING
 FACILITIES, 2007 EDITION.
  
 5) PLEASE MAKE NOTE OF OTHER REVIEW COMMENTS REGARDING
 FAC REQUIREMENTS FOR TITLE BLOCK.
  
 6) PLEASE PROVIDE INFORMATION DESCRIBING DAILY
 MAINTENANCE /HOUSEKEEPING IMPLEMENTATION TO LIMIT DUST
 BUILD-UP AND REDUCE THE HIGH COMBUSTIBILITY HAZARD.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-01 Cont ID  
Sent By rregueir Date 2009-02-01 Time 15:54 Rev Time 0.00
Received By rregueir Date 2009-01-06 Time 16:08 Sent To PC
Notes
2009-01-12 08:26:471/12/09--TO "COMM" BD#12
2009-01-06 16:09:16TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-02-01 Cont ID  
Sent By rregueir Date 2009-02-01 Time 15:53 Rev Time 0.00
Received By rregueir Date 2009-02-01 Time 15:52 Sent To PC
Notes
2009-02-01 15:53:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE ADDITION OF A DUST COLLECTOR TO THIS PROPERTY
 WOULD CONSTITUTE A CHANGE OF OCCUPANCY. DECLARE THE
 PREVIOUS AND NEW OCCUPANCY CLASSIFICATIONS BASED ON
 FBCB CHAPTER 3 ON PLANS. DEMONSTRATE COMPLIANCE WITH
 FBC, EXISTING BUILDING CHAPTER 8 FOR CHANGE OF
 OCCUPANCY. INDICATE CHANGE OF OCCUPANCY ON PERMIT
 APPLICATION AT THE DESCRIPTION OF WORK SECTION.
  
 2. DEMONSTRATE COMPLIANCE WITH NFPA 664-02 FOR
 WOODWORKING FACILITIES. DUST COLLECTORS SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 8.2.2.5.
 DEMONSTRATE COMPLIANCE WITH THESE AND OTHER RELATED
 REQUIREMENTS ON PLANS.
  
 3. DETAIL IS PROVIDED REGARDING WIND RESISTANCE FOR THE
 DUCT COLLECTOR STAND. PLEASE PROVIDE SUPPORTING
 DOCUMENTATION SHOWING THE DUST COLLECTOR EQUIPMENT
 ITSELF AND RELATED DUCTWORK ARE DESIGNED AND INSTALLED
 FOR WIND RESISTANCE IN ACCORDANCE WITH FBCM 301.13.
  
 MUCH INFORMATION IS MISSING FORM PLANS. ADDITIONAL
 COMMENTS ARE LIKELY IN SUBSEQUENT REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2009-01-21 Cont ID  
Sent By eschneid Date 2009-01-21 Time 17:00 Rev Time 2.00
Received By eschneid Date 2009-01-21 Time 17:00 Sent To  
Notes
2009-01-21 17:01:41FAILED
  
 1) A SURVEY, LESS THAN ONE YEAR OLD, IS REQUIRED.
  
 2) SITE PLAN IS ILLEGIBLE. ACCURATE DIMENSIONS ARE
 REQUIRED ON THE SITE PLAN.
  
 3) THE PROPOSED DUST COLLECTOR SYSTEM IS SHOWN IN AN
 AREA THAT THE APPROVED SITE PLAN LABELS AS PARKING. NO
 PARKING MAY BE REMOVED UNLESS IT IS REPLACED ELSEWHERE.
  
 4) THE INSTALLATION OF THIS LARGE DUST COLLECTOR SYSTEM
 UPGRADES THE BUSINESS USE FROM "CABINET WORK ON A
 CUSTOM BASIS TO INDIVIDUAL ORDER - RETAIL" TO "WOOD
 KITCHEN CABINET MANUFACTURING". THIS CHANGE IN USE ON
 THE CITY'S PERMITTED USE TABLE REQUIRES THAT ALL
 ACTIVITIES, TO INCLUDE THE DUST COLLECTION, OCCUR IN AN
 ENCLOSED BUILDING.
  
 5) PROVIDE DETAILS ON HOW THE DUST COLLECTOR SYSTEM
 WILL COMPLY WITH THE PARTICULATE MATTER AND VIBRATION
 REQUIREMENTS OF THE SECTION 94-310 OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS.
  
 6) SHOULD ANY LANDSCAPE, INCLUDING SOD, BE REMOVED,
 THEN IS SHALL BE VERIFIED THAT THE SITE CONFORMS TO THE
 MINIMUM LANDSCAPE PERCENTAGE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
  
  