Plan Review Details - Permit 09010047
Plan Review Stops For Permit 09010047
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-10-21 Cont ID  
Sent By dpalmer Date 2009-10-21 Time 08:19 Rev Time 0.00
Received By dpalmer Date 2009-10-21 Time 08:19 Sent To PC
Notes
2009-10-21 08:20:47GEC SHOWN AS #6 WHICH IS TOO SMALL PER 250.66
 CONTRACTOR STATES SIZE IS ACTUALLY #2 AWG.
 VIF IN FIELD. PLANS FOR FINAL.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-10-06 Cont ID  
Sent By dpalmer Date 2009-10-06 Time 14:48 Rev Time 0.00
Received By dpalmer Date 2009-10-05 Time 16:56 Sent To  
Notes
2009-10-06 14:48:52MET WITH MR. ROBERT DILLINGER. SIGNED OUT ONE SET OF
 REDLINED PLSN. OTHER SET WITH COVER SHEET AND SIGN OUT
 SHEET IN LUIS'S OFFICE.
2009-10-05 16:56:39ON HOLD, MEETING WITH ROBERT DILLINGER ON 10/6
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-06-12 Cont ID  
Sent By btrobaug Date 2009-06-12 Time 11:47 Rev Time 0.00
Received By btrobaug Date 2009-06-12 Time 10:15 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-05-07 Cont ID  
Sent By btrobaug Date 2009-05-07 Time 14:02 Rev Time 0.00
Received By btrobaug Date 2009-05-07 Time 12:47 Sent To PC
Notes
2009-05-07 12:56:50 
  
 THIS REVIEW WAS DONE UNDER THESE CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E-1 INCORRECTLY REFERENCES THE 2008 NEC IN THE
 ELECTRICAL NOTES
  
 2} R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.***ONE DETECTOR NEEDS TO BE
 ADDED OUTSIDE THE BACK BEDROOMS TO SATISFY THIS
 REQUIREMENT. SEE 210.12 FOR AFCI CIRCUITING.
  
 2} SEE 210.12 FOR AFCI CIRCUITING.THERE IS NO NOTES
 INDICATING THIS REQUIREMENT FOR THE BEDROOM OUTLETS.
  
 3} THE RISER DIAGRAM ON SHEET E-2 LISTS 4/0 COPPER
 CONDUCTORS IN THE 2 1/2" RISER CONDUIT. THE #4
 GROUNDING ELECTRODE CONDUCTOR IS NOT LARGE ENOUGH FOR
 THOSE CONDUCTORS, SEE 250.66. THERE ALSO A NOTE
 MENTIONING ALUMINUM CONDUCTORS PANEL FEEDERS, CORRELATE
 ALL THE FEEDERS AND REMOVE THE NOTES THAT AREN'T
 RELEVANT TO SHOW THE INTENT OF THE DESIGNER.
  
 4} FROM THE METER THERE ARE 1/0 CONDUCTORS RUNNING TO
 THE 225 AMP DISCONNECTING VIOLATION OF 310.15(B)(6)
  
 5} THE RECEPTACLES ON CIRCUIT A-23 IN THE GREAT AND
 MASTER BEDROOMS ARE LABELED WATER PROOF EXTERIOR
 RECEPTACLES ON THE PANEL SCHEDULE. 408.4 NEC.
  
 6} THE DINING ROOM RECEPTACLES ARE REQUIRED TO BE ON A
 SMALL APPLIANCE CIRCUIT PER 210.52 (B) (1) RECEPTACLE
 OUTLETS SERVED IN THE KITCHEN, PANTRY, BREAKFAST ROOM,
 DINING ROOM, OR SIMILAR AREA OF A DWELLING UNIT, THE
 TWO OR MORE 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS
 REQUIRED BY 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR
 RECEPTACLE OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP
 OUTLETS COVERED BY 210.52(C), AND RECEPTACLE OUTLETS
 FOR REFRIGERATION EQUIPMENT.
  
 7} PER 210.52(C)(1) WALL COUNTER SPACES A RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH WALL COUNTER SPACE
 THAT IS 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM
 A RECEPTACLE OUTLET IN THAT SPACE***THE COUNTERTOP
 RECEPTACLES ON THE REFRIGERATOR SIDE OF THE KITCHEN DO
 NOT COMPLY WITH THAT ARTICLE AS NO RECEPTACLES ARE
 SHOWN.
  
 8} THE RECEPTACLE SPACING IN THE SUN ROOM MUST COMPLY
 WITH 210.52(A)(1) & (2).
  
 9} A RECEPTACLE MUST BE ADDED OUTSIDE AT THE FRONT OF
 THE HOUSE PER 210.52(E).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
 8} RECEPTACLES IN THE SUN ROOM MUST COMPLY WITH.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-01-12 Cont ID  
Sent By btrobaug Date 2009-01-12 Time 09:45 Rev Time 0.00
Received By btrobaug Date 2009-01-12 Time 08:49 Sent To I
Notes
2009-01-12 09:04:48 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 2} PROVIDE A PANEL SCHEDULE WITH OCP AND WIRE SIZES PER
 408.4, 310.16 NEC.
  
 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE.
  
 4} THE KITCHEN LAYOUT IS INCOMPLETE AND THEREFORE
 COMPLIANCE WITH 210.52(B) FOR SPACING CANNOT BE
 PROPERLY REVIEWED
  
 5} PER 210.8(A)(6), KITCHEN COUNTERTOP RECEPTACLE MUST
 BE GFI PROTECTED.INDICATE SAME ON THE PLAN.
  
 6} PER 210.8(A)(1)ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN BATHROOMS SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL. NOT SHOWN ON THE PLAN.
  
 7} 210.52 (E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING. THESE ARE REQUIRED TO BE GFI PROTECTED PER
 210.8(A)(3).
  
 8} PROVIDE A LEGEND FOR THE DEVICES AND FIXTURES ON THE
 PLAN.IT IS HARD TO DETERMINE LIGHTS , SPEAKERS AND
 PHONE SYMBOLS.106.1.3 FBC
  
 9} 106.1.3 RESERVED. QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.***THE SCALE
 GIVEN IS INCORRECT AS THE COPIED PLANS SEEM TO HAVE
 BEEN REDUCED.
  
 PER 713 FLORIDA STATUTES A NOTICE OF COMMENCEMENT MUST
 BE FILED PRIOR TO THE FIRST INSPECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-30 Cont ID  
Sent By dpalmer Date 2009-09-30 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2009-09-30 Time 08:40 Sent To E
Notes
2009-09-30 08:40:45PLANS ON BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 12:40 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 12:40 Sent To E
Notes
2009-04-29 12:40:33TO BT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-12 Cont ID  
Sent By btrobaug Date 2009-01-12 Time 09:46 Rev Time 0.00
Received By btrobaug Date 2009-01-06 Time 15:37 Sent To PC
Notes
2009-01-06 15:37:38TO "E" BOX