Plan Review Details - Permit 09010041
Plan Review Stops For Permit 09010041
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-23 Cont ID  
Sent By rmcdouga Date 2009-01-23 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2009-01-23 Time 15:50 Sent To Z
Notes
2009-01-23 15:50:552004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) THE PLANS INDICATE TWO DWELLING UNITS WITHIN THE
 STRUCTURE. IF THESE ARE TWO SEPARATE DWELLING UNITS
 THEY MAY BE REQUIRED TO HAVE THEIR OWN SEPARATE STREET
 ADDRESSES. PLEASE CONTACT JOHN NGUYEN AT 561-822-1239.
  
 2) THE DWELLING UNIT SEPARATION IS REQUIRED TO BE
 MAINTAINED. SHOW COMPLIANCE WITH R317.1 TWO-FAMILY
 DWELLINGS. DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL
 BE SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR
 ASSEMBLIES HAVING NOT LESS THAN 1-HOUR FIRE-RESISTANCE
 RATING WHEN TESTED IN ACCORDANCE WITH ASTM E 119.
 FIRE-RESISTANCE-RATED FLOOR-CEILING AND WALL ASSEMBLIES
 SHALL EXTEND TO AND BE TIGHT AGAINST THE EXTERIOR WALL,
 AND WALL ASSEMBLIES SHALL EXTEND TO THE UNDERSIDE OF
 THE ROOF SHEATHING.
  
 3) PRODUCT APPROVALS WERE SUBMITTED FOR A PELLA
 EXTERIOR OUTSWING DOOR AND THE PLANS INDICATE THE NEW
 DOOR AS AN INSWING. PLEASE CORRECT. DCA RULE 9B-72
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-01-09 Cont ID  
Sent By btrobaug Date 2009-01-09 Time 10:44 Rev Time 0.00
Received By btrobaug Date 2009-01-09 Time 08:33 Sent To Z
Notes
2009-01-09 10:14:41 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION
 ON THE APPLICATION, PROVIDE AN AIC RATING PER 110.9 &
 10.
  
 2} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE
 CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED
 LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS
 USED, THE CALCULATED LOAD AFTER APPLYING DEMAND
 FACTORS, ARTICLE 215.5 NEC 2005.*** FOR THE ENTIRE
 SERVICE.
  
 3} THERE IS NO "GROUND" PROVIDED BY FPL (SEE RISER
 OVERHEAD) REMOVE THE #6.
  
 4} 250.24(C) GROUNDED CONDUCTOR BROUGHT TO SERVICE
 EQUIPMENT WHERE AN AC SYSTEM OPERATING AT LESS THAN
 1000 VOLTS IS GROUNDED AT ANY POINT, THE GROUNDED
 CONDUCTOR(S) SHALL BE RUN TO EACH SERVICE DISCONNECTING
 MEANS AND SHALL BE BONDED TO EACH DISCONNECTING MEANS
 ENCLOSURE. THE GROUNDED CONDUCTOR(S) SHALL BE INSTALLED
 IN ACCORDANCE WITH 250.24(C)(1) THROUGH (C)(3).
 EXCEPTION: WHERE MORE THAN ONE SERVICE DISCONNECTING
 MEANS ARE LOCATED IN AN ASSEMBLY LISTED FOR USE AS
 SERVICE EQUIPMENT, IT SHALL BE PERMITTED TO RUN THE
 GROUNDED CONDUCTOR(S) TO THE ASSEMBLY, AND THE
 CONDUCTOR(S) SHALL BE BONDED TO THE ASSEMBLY
 ENCLOSURE.*** THE RISER HAS MULTIPLE GROUND RODS. THE
 NEUTRAL SHOULD BE GROUNDED IN THE GUTTER, A MAIN
 BONDING JUMPER INSTALLED IN THE DISCONNECTS, AND
 ADDITIONAL ELECTRODES ONLY AT SEPARATE STRUCTURES PER
 250.32
  
 5 } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE
 FEEDERS TO THE CABANA PANELS ON THE RISER DIAGRAM.215.5
 NEC.
  
 6} INDICATE CONDUCTOR SIZES ON THE PANEL SCHEDULE SO
 THAT COMPLIANCE WITH 310.16 CAN BE REVIEWED.
  
 7} 210.25 COMMON AREA BRANCH CIRCUITS
 BRANCH CIRCUITS IN DWELLING UNITS SHALL SUPPLY ONLY
 LOADS WITHIN THAT DWELLING UNIT OR LOADS ASSOCIATED
 ONLY WITH THAT DWELLING UNIT. BRANCH CIRCUITS REQUIRED
 FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM, SIGNAL,
 COMMUNICATIONS, OR OTHER NEEDS FOR PUBLIC OR COMMON
 AREAS OF A TWO-FAMILY OR MULTIFAMILY DWELLING SHALL NOT
 BE SUPPLIED FROM EQUIPMENT THAT SUPPLIES AN INDIVIDUAL
 DWELLING UNIT.THERE ARE TWO PANELS AND THREE UNITS. THE
 2ND FLOOR UNIT APPEARS HAS NO ACCESS TO THE PANEL FOR
 THAT UNIT. PLEASE CLARIFY.
  
 8} LABEL THE WATER HEATERS ON THE PLAN. 106.1 FBC
  
 9} R313.1.1 RESIDENTIAL BUILDING CODE, SMOKE ALARMS
 SHALL BE LOCATED AS REQUIRED IN NEW DWELLINGS WHEN
 REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR. SEE
 ARTICLE FOR COMPLETE TEXT.***LOCATE THE ALARMS ON THE
 PLANS.
  
 FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE
 FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE
 THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.(2005 NEC) ON THE ELECTRICAL OR COVER SHEET.
 ALSO NOTE THE 2007 REVISIONS TO THE 2004 FBC ARE IN
 EFFECT.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-01-06 Cont ID  
Sent By mmiller Date 2009-01-06 Time 10:09 Rev Time 0.00
Received By mmiller Date 2009-01-06 Time 10:09 Sent To  
Notes
2009-01-06 10:10:32OK PER FREDERICK MITTNER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 11:19 Sent To  
Notes
2009-01-06 11:21:51TO "SFR" "E"

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-13 Cont ID  
Sent By btrobaug Date 2009-01-13 Time 10:45 Rev Time 0.00
Received By kstevens Date 2009-01-13 Time 09:01 Sent To B
Notes
2009-01-13 09:08:54DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 EXISTING BUILDING
  
 1. SHT C1 PRESENT CODE CYCLE IS THE FBC-2004 WITH 2007
 AMENDMENTS. SECTION 106.1.1. PLANS INDICATE 2006
 AMENDMENTS. PLEASE UPDATE CODE CRITERIA.
  
 2. INDICATE LEVEL OF ALTERATION PER CHAPTER 3 OF THE
 FBC-2004 EXISTING BUILDING CODE.
  
 2. SHTS D2 & A3. MORE INFORMATION IS REQUIRED. SECTION
 106.1.2. THE DEMO SHEET DOES NOT SHOW A KITCHEN SINK
 NOR DOES IT SHOW A WASHING MACHINE WHICH ARE BOTH
 INDICATED ON THE PROPOSED SHEET. ARE THESE FIXTURES
 EXISTING OR NEW? PLEASE CLARIFY.
  
 3. WITH NEW INFORMATION, THERE MAY BE MORE COMMENTS. IF
 NEW FIXTURES, A SANITARY RISER DIAGRAM WILL BE REQUIRED
 FOR THE NEW FIXTURES SHOWING ALL PIPE SIZES, TRAPS,
 VENTS ETC. SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***