Plan Review Details - Permit 08120584
Plan Review Stops For Permit 08120584
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-08-26 Cont ID  
Sent By jgomez Date 2009-08-26 Time 10:08 Rev Time 0.00
Received By jgomez Date 2009-08-25 Time 10:48 Sent To PC
Notes
2009-08-26 10:08:47TRUSS PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-08-17 Cont ID  
Sent By jgomez Date 2009-08-17 Time 14:13 Rev Time 0.00
Received By jgomez Date 2009-08-17 Time 14:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-07-22 Cont ID  
Sent By jgomez Date 2009-07-22 Time 11:20 Rev Time 0.00
Received By jgomez Date 2009-07-22 Time 11:20 Sent To  
Notes
2009-07-22 11:20:19TALKED TO LEO PRICE. PLANS SUBMITTED ARE NOT THE ONES
 THAT WERE REVIEWED. MISSING COMPLETE PRODUCT APPROVALS
 PACKAGE, SURVEYS, IMPACT FEES, ETC. ALSO, ONE SET IS A
 COPY WITHOUT ORIGINAL SEAL AND SIGNATURES..

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2009-07-22 Cont ID  
Sent By jgomez Date 2009-02-13 Time 09:57 Rev Time 0.00
Received By jgomez Date 2009-02-13 Time 09:57 Sent To  
Notes
2009-02-13 10:18:10BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE 3 COPIES OF COMPLETE PROJECT MANUAL. MISSING
 FROM PERMIT PACKAGE.
  
 2- DOORS AND WINDOWS GLAZING U-FACTOR AND SHGC FACTOR
 SHOWN ON ENERGY CALCULATIONS ITEM #7A AND #7B TO BE
 AVAILABLE ON INSTALLED WINDOWS/DOORS FOR BUILDING
 INSPECTOR VERIFICATION.
  
 3- PROVIDE COMPLETE TRUSS PACKAGE (3 COPIES) PRIOR TO
 INSTALLATION.
  
 4- RESUBMIT PRODUCT APPROVALS FOR:
 A) PRECAST LINTELS.
 B) EXTERIOR SWING DOORS.
 C) SHINGLES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-22 Cont ID  
Sent By jgomez Date 2009-01-22 Time 09:50 Rev Time 0.00
Received By jgomez Date 2009-01-22 Time 09:40 Sent To  
Notes
2009-01-22 10:01:28NEW RESIDENTIAL (R2) BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FBC WITH 2007 REVISIONS.
  
 1- EXHIBIT "A" SUBMITTED:
 A) MISSING PRODUCT APPROVAL FOR SINGLE HUNG WINDOWS TO
 VERIFY COMPLIANCE WITH THE U FACTOR AND SHGC FACTOR
 SHOWN ON EXHIBIT A.
  
 B) CLARIFY SPECIFICATIONS SHOWN ON SEC. 2.01 (A)
 REGARDING "ADDITIONAL AUTOMATIC ENGAGING SECONDARY LOCK
 WHICH LIMITS SINGLE HUNG WINDOWS TO AN INITAL OPENING
 HEIGHT OF 4". NEED TO CLARIFY THIS TO VERIFY COMPLIANCE
 WITH EGRESS REQUIREMENTS OF SEC. 1025 FBC 2004.
  
 C) PROVIDE THREE COPIES OF EVERY PAPER SUBMITTED.
  
 2- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 B) REVISE OWNER INFORMATION (REPEAT COMMENT).
  
 C) REVISE PERMIT NUMBER (REPEAT COMMENT).
  
 3- PROVIDE THREE COPIES OF EXHIBIT "B".
  
 4- PROVIDE THREE COPIES OF SOIL TEST REPORT. SEC.
 1802.1 FBC 2004 (REPEAT COMMENT).
  
 5- EXHIBIT "D":
 A) SHINGLES FLORIDA PRODUCT APPROVAL FL728-R1 AND NOA
 08-0305.04 SUBMITTED DON'T CORRESPOND TO EACH OTHER.
 SUBMIT EITHER COMPLETE FLORIDA PRODUCT APPROVAL
 FL728-R1 INCLUDING THE SHINGLES DRAWINGS SUBMITTED FOR
 APPROVAL OR SUBMIT THE NOA ALONE.
 NOTE: MAKE SURE EITHER OPTION HAS DESIGNER OF RECORD
 APPROVAL IN WRITING (REVIEW STAMP) AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- EXHIBIT "C":
 A) PROVIDE SKETCH SHOWING LOCATION OF WINDOWS, DOORS
 AND WALLS CONSIDERED FOR THE CALCULATIONS. SEE SHEET
 A100 FOR ACTUAL BUILDING ORIENTATION. NEED SURVEY TO
 VERIFY DIMENSIONS. ALSO, SEE SHEET A405 FOR ACTUAL TYPE
 OF WINDOWS AND DOORS TO BE CONSIDERED. THERE ARE NOT
 "C" TYPE WINDOWS ON THIS ELEVATION. CALCULATIONS DON'T
 SHOW DOOR OPENINGS. (NOTE: CALCULATIONS TO BE BASED ON
 WINDOWS/DOORS ROUGH OPENINGS).
  
 B) ARCHITECT'S WALL OPENINGS CALCULATIONS NEED TO HAVE
 ARCHITECT'S SEAL, SIGNATURE AND DATE AS REQUIRED BY
 SEC. 61G-16.003 FLORIDA ADMINISTRATIVE CODE AND CHAPTER
 481 FLORIDA STATUTE (REPEAT COMMENT).
  
 C) PROVIDE THREE COPIES.
  
 D) REVISE PERMIT NUMBER TO MATCH NEW PERMIT NUMBER
 08120584.
  
 E) CLARIFY WHY PROVIDING WALL OPENING CALCULATIONS. ARE
 THERE TWO BUILDINGS ON THE SAME LOT CONSIDERED AS ONE
 BUILDING PER EXCEPTION ON SEC. 704.3 FBC 2004 OR THE
 TWO BUILDINGS ARE LOCATED ON TWO DIFFERENT PARCELS.
  
 7- NEED TO PROVIDE SURVEY TO VERIFY BUILDING LOCATION
 AND SETBACKS. SURVEY NOT SUBMITTED AT THIS TIME.
 NOTE: PROVIDE THREE COPIES.
  
 8- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 9- PROVIDE COMPLETE TRUSS PACKAGE. NONE SUBMITTED AT
 THIS TIME.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE PACKAGE
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 10- NEED TO PAY BALANCE OF PERMIT FEES: $28,787.43.
  
 11- SUBMITTAL IS MISSING THE REST OF THE PRODUCT
 APPROVALS:
 A) DOUBLE FRENCH DOORS AS SHOWN ON PLANS.
  
 B) SINGLE HUNG WINDOWS.
  
 C) PRECAST LINTELS AS SHOWN ON PLANS.
  
 D) FIXED WINDOWS AS SHOWN ON PLANS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. FLORIDA PRODUCT APPROVALS NUMBERS
 SPECIFIED ON SHEET S-4 EXPIRED ON 10-01-08.
  
 F) ROOF RIDGE VENTS AS SHOWN ON PLANS.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-02-17 Cont ID  
Sent By dpalmer Date 2009-02-17 Time 15:17 Rev Time 0.00
Received By dpalmer Date 2009-02-17 Time 15:17 Sent To  
Notes
2009-02-17 15:18:08PLANS SIGNED BACK IN BY ZONING ON 2/17.
 ELEC REVIEW DONE AND STAMPED ELECTRICAL SHEETS SAME
 DAY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-01-14 Cont ID  
Sent By dpalmer Date 2009-01-14 Time 08:20 Rev Time 0.00
Received By dpalmer Date 2009-01-13 Time 16:59 Sent To  
Notes
2009-01-14 08:20:26** DENIED **
  
  
 ** PLEASE SEE THE NOTES BELOW WHICH ARE THE SAME NOTES
 FROM TWO PREVIOUS REVIEWS UNDER EXPIRED PERMIT
 APPLICATIONS.
 THESE ITEMS COULD HAVE BEEN SET UP AS A PROVISO HOWEVER
 THE PLANS ARE COMING BACK FOR COMMENTS FROM OTHER
 TRADES. PLEASE MAKE CORRECTIONS AT THIS TIME. THIS
 AFFECTS ALL UNITS.
  
 ** PLEASE BE SURE TO REMOVE ALL OLD/VOIDED SHEETS AND
 REPLACE WITH THE NEW CORRECTED SHEETS.
  
  
  
 1) NOTE: PLEASE SEE 422.30, 31. THE PREVIOUS REVIEW
 GAVE THESE SECTIONS OF THE CODE FOR DISCONNECTS WHICH
 ARE REQUIRED FOR DISHWASHER, DISPOSAL AND HOOD. THE
 RESPONSE FROM THE ENGINEER STATES THESE DEVICES MEET
 422.33A AND DO NOT NEED DISCONNECTS. AS SHOWN ON THE
 PLANS THESE APPLIANCES ARE BEING CONNECTED VIA HARD
 WIRED CONNECTIONS TO A JUNCTION BOXES. IN ORDER TO MEET
 422.33A THESE WOULD BE REQUIRED TO BE CORD AND PLUG
 CONNECTED EQUIPMENT WITH THE CORDS BEING *PLUGGED IN*
 TO RECEPTACLES. AS THERE ARE ONLY JUNCTION BOXES WITH
 THE HARD WIRED CONNECTIONS THESE WOULD NEED TO BE
 REVISED ON THE PLANS FOR ALL UNITS TO CORD AND PLUG
 APPLIANCES WITH RECEPTACLES.
 I HAVE PLACED A CALL TO MR. NESTOR MARTINEZ AND SPOKE
 AT LENGTH ABOUT THE CODE SECTIONS. MR. MARTINEZ WILL
 MAKE THESE ADJUSTMENTS TO PLANS FOR ALL APPLIANCES IN
 ALL UNITS.
  
 2) NOTE: PLANS STILL INDICATE THE 2002 NFPA-70 (NEC)>
 PLEASE SEE FS 553.73 WHICH ADOPTS THE FLORIDA BUILDING
 CODE. AS OF DECEMBER 8TH, 2006 THE STATE OF FLORIDA IS
 UNDER THE 2005 NFPA-70 (NEC>
 PLEASE ADJUST CODES ON PLANS.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-01-15 Cont ID  
Sent By efabian Date 2009-01-15 Time 12:45 Rev Time 0.00
Received By efabian Date 2009-01-15 Time 12:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-02-18 Cont ID  
Sent By mawillia Date 2009-02-18 Time 12:55 Rev Time 0.00
Received By mawillia Date 2009-02-18 Time 12:21 Sent To  
Notes
2009-02-18 12:54:59*****APPROVED*****
  
 PLAN SHEETS A203, A204, A405, A603, A700.1, A702.1,
 E203, AND E204 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-01-28 Cont ID  
Sent By mawillia Date 2009-01-28 Time 10:06 Rev Time 0.00
Received By mawillia Date 2009-01-28 Time 07:14 Sent To  
Notes
2009-01-27 23:10:43*****DENIED*****
  
 1. AMEND CODE INFORMATION ON PAGE A004 TO REFLECT
 REFERENCES TO NFPA 101, LIFE SAFETY CODE, 2006 EDITION
 AND THE FLORIDA FIRE PREVENTION CODE - 2007 EDITION.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
 (THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 OTHER REVIEWERS COMMENTS AS WELL AS THE ABOVE HAVE BEEN
 SATISFIED.)
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-20 Cont ID  
Sent By lmartine Date 2009-08-20 Time 17:41 Rev Time 0.00
Received By lmartine Date 2009-08-20 Time 17:41 Sent To  
Notes
2009-08-20 17:41:54GAVE TO JULIO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-05 Cont ID  
Sent By adarroug Date 2009-02-05 Time 10:27 Rev Time 0.00
Received By adarroug Date 2009-02-05 Time 10:27 Sent To  
Notes
2009-02-05 10:30:20---------EXPEDITED-----------
  
 TO "COMM" BD#46,--PLANS ON RACK/4 ROLLS AND PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-28 Cont ID  
Sent By mawillia Date 2009-01-28 Time 10:06 Rev Time 0.00
Received By mawillia Date 2008-12-31 Time 08:58 Sent To  
Notes
2008-12-31 09:01:39TO "COMM" BD#38--EXPEDITED--

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-01-20 Cont ID  
Sent By rregueir Date 2009-01-20 Time 08:47 Rev Time 0.00
Received By rregueir Date 2009-01-20 Time 08:47 Sent To  
Notes
2009-01-20 08:47:39PREVIOUSLY REVIEWED, PASSED AND STAMPED BY TOM GORDON
 ON 5/5/08 UNDER EXPIRED PERMIT #07080679

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-02-12 Cont ID  
Sent By kstevens Date 2009-02-12 Time 16:45 Rev Time 0.00
Received By kstevens Date 2009-02-12 Time 16:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-12 Cont ID  
Sent By kstevens Date 2009-01-12 Time 13:49 Rev Time 0.00
Received By kstevens Date 2009-01-12 Time 13:49 Sent To  
Notes
2009-01-12 14:02:22DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT A004 CODE INFORMATION SHALL ALSO INCLUDE THE
 2007 AMENDMENTS. SECTION 106.1.1.
  
 2. SHTS P305 BUILDING TYPE V "L" LOWER FLOOR PLAN AND
 402 BUILDING "L" SANITARY ISOMETRIC RISER DIAGRAM SHOWS
 A BACKWATER VALVE IN THE SEWER. SECTION 715.1 STATES,
 WHERE THE FLOOD LEVEL RIMS OF PLUMBING FIXTURES ARE
 BELOW THE ELEVATION OF THE MANHOLE COVER OF THE NEXT
 UPSTREAM MANHOLE IN THE PUBLIC SEWER, SUGH FIXTURES
 SHALL BE PROTECTED BY A BACKWATER VALVE INSTALLED IN
 THE BUILDING DRAIN, BRANCH OF THE BUILDING DRAIN OR
 HORIZONTAL BRANCH SERVING SUCH FIXTURES. PLUMBING
 FIXTURES HAVING FLOOD LEVEL RIMS ABOVE THE ELEVATION OF
 THE MANHOLE COVER OF THE NEXT UPSTREAM MANHOLE IN THE
 PUBLIC SEWER SHALL NOT DISCHARGE THROUGH A BACKWATER
 VALVE. ALL FIXTURES, INCLUDING THE SECOND FLOOR
 FIXTURES ARE DISCHARGING THROUGH THE BACKWATER VALVE AS
 INDICATED ON THE PLANS. THIS IS PROHIBITED. SUBMIT THE
 ELEVATION OF THE MANHOLE COVER OF THE NEXT UPSTREAM
 MANHOLE IN THE PUBLIC SEWER AS WELL AS THE ELEVATION OF
 THE SLAB SO IT CAN BE DETERMINED WHAT FIXTURES SHALL
 DISCHARGE THROUGH THE BACKWATER VALVE. SUBMIT MANUF.
 SPECIFICATIONS FOR THE BATHTUBS AND THE WATER CLOSETS
 SHOWING THE HEIGHTS OF EACH FIXTURES TO DETERMINE THE
 HEIGHT OF THE FLOOD RIM LEVELS FOR THESE FIXTURES.
 SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-02-12 Cont ID  
Sent By ajones Date 2009-02-12 Time 14:15 Rev Time 0.00
Received By ajones Date 2009-02-12 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-01-07 Cont ID  
Sent By ajones Date 2009-01-07 Time 14:10 Rev Time 0.30
Received By ajones Date 2009-01-07 Time 14:09 Sent To  
Notes
2009-01-07 14:12:35LANDSCAPING PLANS MUST BE APPROVED BEFORE A CO IS
 ISSUED.