Plan Review Details - Permit 08120552
Plan Review Stops For Permit 08120552
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-01-02 Cont ID  
Sent By jnguyen Date 2009-01-02 Time 14:25 Rev Time 0.00
Received By jnguyen Date 2009-01-02 Time 09:01 Sent To  
Notes
2009-01-02 10:03:07I TOOK A LOOK AT THE ASSOCIATED DOCUMENTS IN THIS
 PERMIT APPLICATION FOLDER & NOTICED THERE WERE PAPA
 PRINT OUTS FOR THREE PARCEL BOUNDARIES. I ANALYZED
 THEIR LOCATIONS IN GIS & REALIZED THAT THESE THREE
 PARCELS WERE ADJACENT TO ONE ANOTHER. I ALSO TOOK A
 LOOK AT THE SITE PLANS UPSTAIRS & CAME TO THE
 REALIZATION THAT THE AREA OF ALTERATION INDEED TOOK
 PLACE ON THREE PARCELS. THEREFORE, THIS PERMIT ACTUALLY
 DOES NOT REFERENCE JUST ONE PARCEL, BUT THREE DIFFERENT
 PARCELS THAT ARE ADJACENT TO ONE ANOTHER: PCN#
 74434321080550060 - 481 HIBISCUS ST (WEST PARCEL), PCN#
 74434321080550040 - 455 HIBISCUS ST (MIDDLE PARCEL) &
 PCN# 74434321080550012 - 421 HIBISCUS ST (EAST PARCEL).
 I TALKED TO JOE SULLIVAN ON THE PHONE & HE CONFIRMED TO
 ME THAT THE WORK BEING REFERENCED ON THIS PERMIT TOOK
 PLACE ON THREE PARCELS. HE ALSO ACKNOWLEDGED TO ME THAT
 THEY WERE TRYING TO IMPLEMENT A UNITY OF TITLE DEED AT
 THE COUNTY TO MERGE THESE THREE PARCELS (PCN#
 74434321080550060, PCN# 74434321080550040 & PCN#
 74434321080550012) INTO A SINGLE ONE. HOWEVER, SINCE
 OUR DATABASE & THE COUNTY'S RECORDS "CURRENTLY"
 RECOGNIZED THESE THREE PARCELS AS THERE OWN DISTINCT
 UNIQUE ENTITIES, I HAVE ADDED THE PREVIOUSLY OMITTED
 PCN# 74434321080550060 & PCN# 74434321080550040 (ALONG
 WITH THEIR ASSOCIATED PRIMARY ADDRESSES 481 & 455
 HIBISCUS ST) TO THE ORIGINAL PERMIT APPLICATION WITH
 PCN# 74434321080550012 - 421 HIBISCUS ST. DOWN THE
 LINE, WE WILL EVENTUALLY HAVE TO FIND OUT WHICH PCN#
 THIS PARCEL WILL RETAIN OR IF IT WILL BE ISSUED A
 COMPLETELY NEW ONE, WHEN THE UNITY OF TITLE DEED
 BECOMES OFFICIAL (SOME TIME IN MID-FEBRUARY). THIS
 PROPOSED MARRIOTT HOTEL WILL LIKELY RETAIN THE ADDRESS
 OF 455 HIBISCUS ST AFTER THE MERGER TAKES PLACE. 455
 HIBISCUS ST WAS THE FIRST ADDRESS ISSUED BY LILI BACK
 IN APRIL 2008 & IT MOST CLOSELY RESIDES WITH WHERE THE
 BUILDING WILL BE SITUATED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-30 Cont ID  
Sent By jwitmer Date 2008-12-30 Time 20:01 Rev Time 2.50
Received By jwitmer Date 2008-12-30 Time 20:01 Sent To  
Notes
2008-12-30 20:02:35BUILDING PLAN REVIEW
 PERMIT: 08120552
 ADD: 455 HIBISCUS STREET
 CONT: "PLAN REVIEW"
 TEL: (561)239-6986 JOE SULLIVAN
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: DONALD T. YOSHINO, AIA
 STRUCTURAL ENGINEER: JOEL MIDDLEBROOKS, P.E.
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 1E) INFORMATIONAL: PLANS ARE CURRENTLY BROUGHT IN AS A
 PLAN REVIEW OR MAJOR WORKING DRAWING REVIEW, AND ARE
 REVIEWED UNDER THE 2004 FBC BASE CODE WITH 2007
 SUPPLEMENTS. EFFECTIVE MARCH 1ST, 2009 THE 2007FBC BASE
 CODE WILL BE ENACTED. IF THIS PROJECT HAS NOT BEEN
 CONVERTED OVER TO A PERMIT APPLICATION, BEFORE MARCH
 1ST, 2009 THE
 PLANS ON THE NEXT REVIEW WILL BE REVIEWED UNDER THE
 2007 FBC AS THE BASE CODE.
  
 1F) PLEASE PROVIDE A UNITY OF TITLE FOR THREE LOTS THE
 HIGH RISE WILL BE BUILT ON. TABLE 602. WILL REQUIRE 3
 HR RATED WALLS THROUGH BUILDING WHERE RATED LOT LINES
 OCCURWITH NO UNITY OF TITLE.
  
 2) SOILS REPORT WAS NOT SUBMITTED, NO COPIES. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G15-23.002 ENGINEERS
  
 SHEET S0.02 AUGER-CAST PILES INDICATES THERE WERE TEST
 COMPLETED BY ARDAMAN & ASSOC. REPORT# 08-2021DATED
 02-23-08.
  
 3) THRESHOLD BUILDING REQUIREMENTS:
  
 3A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 3B)THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 3C) INFORMATIONAL:
 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 4) INFORMATIONAL; 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) INFORMATIONAL: 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 6) FBC 13-103.0 ENERGY CODE COMPLIANCE SHALL BE
 DEMONSTRATED BY SUBMITTAL OF APPROPRIATE CODE
 COMPLIANCE FORMS, NO ENERGY FORMS NOR INPUT DATA
 REPORTS WERE SUBMITTED.
  
 7) SHEET LS1 PLANS FAIL TO INDICATE THE FOLLOWING
 INFORMATION.110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503,
 CHAPTER 6 & TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004. PLANS INDICATE ROUNDING
 DOWN NOT ROUNDING UP TO THE
 NEXT WHOLE NUMBER OR PERSON.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) NUMBER OF UNITS
 I ) NUMBER OF FLOORS
 J ) NUMBER OF BEDROOMS
 J) SQ. FT.( FOOTPRINT)
 K) SQ. FT. A/C SPACE PER FLOOR
  
 8) SHEET LS1 EXIT DOOR# 1, THE PLANS INDICATE THAT THE
 FULL 91? IS TAKEN FOR MEANS OF EGRESS, WHERE AS SHEET
 A11.01 INDICATES THAT THERE ARE (2) SIDE LIGHTS THAT
 ARE EACH 2?-1? PLEASE REVIEW SECTION 1008.1.1 MINIMUM
 CLEAR WIDTH FOR A DOORWAY IS 32? TO BE CONSIDERED IN A
 MEANS OF EGRESS.
  
 9) SHEET LS1 EXIT DOOR2 & 3, THE PLANS HAVE TAKEN THE
 FULL WIDTH OF THE DOOR OPENING, NOT SUBTRACTING THE
 DOOR WIDTH OF 2? OR A CLEAR OPENING OF 34? AND OCCUPANT
 LOAD OF 170 NOT 180. SECTION 1008.1.1.
  
 10) SHEET A2.01 DOOR# 101C IS WITHIN A 2 HR WALL BUT
 THE DOOR SCHEDULE ON SHEET A11.01 INDICATES A 45 MINUTE
 DOOR. SEE TABLE 715.3 OPENING PROTECTIVES. THE DOOR
 SCHEDULE ALSO INDICATES THE DOOR FRAME AND DOOR
 MATERIALS ARE CONSTRUCTED OF ALUMINUM. SHOW COMPLIANCE
 WITH SECTION 715.3.
  
 11) SHEET A2.1 ROOM 108 IT ROOM REQUIRES 1 HR RATED
 WALLS AND 20 MINUTE OPENING PROTECTION, SEE NFPA 645.2
 AND TABLE 715.3.
  
 12) SHEET A2.1 DOOR # 1123 C&D BOTH ARE LOCATED WITHIN
 A 2 HR FIRE RATED WALL THE DOOR SCHEDULE INDICATES 20
 MINUTE PLEASE REVIEW TABLE 715.3.
  
 13) SHEET A2.1 FOUR WINDOWS INDICATED AS (HH) ON SHEET
 A 12.01 AS 45MINUTE SHOULD READ 1 ? HR OPENING
 PROTECTION SEE TABLE 715.3, 2HR RATED WALL.
  
 14) SHEET A2.1 STAIR TOWER# 2THE INTERIOR WALL THAT
 BACKS UP AGAINST THE COMPUTER ALCOVE IS INDICATED AS A
 WALL TYPE ?1C? OR ONE HOUR WALL, PLEASE REVIEW SECTION
 1019.1.
  
 15) SHEET A2.1 STAIR TOWER # 2 EXTERIOR WALL IS MISSING
 THE WALL IDENTIFICATION TAG ALL TOGETHER, TABLE 602.
  
 16) SHEET A2.1 THERE ARE AREAS OF CONCERN WHERE THE
 FLOOR RATING WILL BE OF CONCERN:
 16A) THE FPL VAULT THE FLOOR RATING OF THE 2ND FLOOR
 OVER THE VAULT IS TO BE THE SAME RATING AS THE WALLS.
  
 17) SHEET A2.1 ROOM # 135 LINEN ROOM ALSO INDICATES A
 LAUNDRY CHUTE, THE LAUNDRY CHUTE DOES NOT PROVIDE A 2HR
 SHAFT ENCLOSURE PLANS INDICATE A WALL TYPE ELEVEN ON
 TWO SIDES OF THE ENCLOSURE SEE SECTION 707.13.1.
  
 18) SHEET A2.1 ROOM # 135 IS ALSO NOT ONLY A LINEN ROOM
 BUT A LAUNDRY CHUTE TERMINATION ROOM WITH THE DOOR
 REQUIRING A 45 MINUTE DOOR SEE 707.13.4.
  
 19) SHEET A2.1 DOOR # 103 AND WINDOW (W):
 19A) THE DOOR SCHEDULE INDICATES DOOR# 103 TO BE A 90
 MINUTE RATED OPENING DOOR TYPE ?B? A ALUMINUM AND
 GLAZED OPENING PLEASE PROVIDE DOCUMENTATION ON THE FIRE
 RATING OF THE ALUMINUM DOOR FRAME AND DOOR ASSEMBLY AS
 WELL AS GLAZING. OPENING PROTECTIVE?S 715.3. THE
 ALLOWABLE OPENINGS IN THIS WALL AREA FOR PROTECTED
 OPENINGS IS 75%. NOTE 704.8.1 DOES ALLOW THESE OPENINGS
 TO BE NOT RATED UP TO 75% OF THE WALL AREA BECAUSE OF
 THE FIRE SPRINKLED BUILDING!
  
 20) SHEET A2.1 DOOR# 103 (SHEET E-9) THIS DOORWAY HAS A
 EXIT SIGN INDICATING THIS IS A EXIST TO A PUBLIC WAY.
 IN A PREVIOUS MEETING DOOR # 21 HAD OPENED ONTO THE
 EASTERN EXPOSURE AND HAD THE SAME TYPE OF PROBLEM THAT
 CONFRONTS THE OCCUPANTS THAT NOW WILL BE EXITING THIS
 DOORWAY TO END UP AT THE PUBLIC WAY. THEY ARE TRAVELING
 WITHIN 5.72 FEET OF THE PROPERTY LINE AND NO PROTECTION
 OF FIRE DANGER FROM ADJOINING PROPERTIES, PLEASE REVIEW
 SECTION 1023.5.2 EGRESS COURTS, CONSTRUCTION AND
 OPENINGS & 1023.6 ACCESS TO THE PUBLIC WAY.
  
  
 21) SHEET A2.1 DOOR# 136B ROLL UP DOOR FOR THE TRASH
 ROOM, LOCATED FROM THE CENTERLINE OF THE ALLEY LESS
 THAN 20?-0? TABLE 602 NON-BEARING EXTERIOR WALLS
 REQUIRES 2HR WALLS AND 90 MINUTE OPENING PROTECTIVE?S
 PLEASE UP DATE THE DOOR SCHEDULE TABLE 715.3. PROVIDE
 MANUFACTURER?S SPECIFICATIONS ON FIRE RATING AND HOW
 THIS DOOR WILL AUTOMATICALLY CLOSE 715.3.7.
  
 22) SHEET A2.2 ASSEMBLY ROOM OR MEETING ROOM 201, LS
 SHEET LS 2 INDICATES 121 OCCUPANTS REQUIRING 2 EXITS AS
 PER TABLE 1014.1 THIS AMOUNT OF OCCUPANTS EXCEED THE
 ALLOWABLE OCCUPANT LOAD FOR ONE EXIT TABLE 1014.1. LS 2
 ONLY INDICATES ONE EXIT AND A NOTE FOR THE MONUMENTAL
 STAIR INDICATING SHAFT NOT REQUIRED AS PER SECTION
 707.2.2. THIS CODE SECTION IS INCORRECT. EITHER YOU ARE
 LOOKING AT:
 707. 2 EXCEPTION 2 WHERE A SHAFT ENCLOSURE IS NOT
 REQUIRED FOR AN ESCALATOR OR STAIR THAT IS NOT PART OF
 MEANS OF EGRESS.
  
 707.2 EXCEPTION 2.2 WHERE THE OPENINGS ARE PROTECTED BY
 A FIRE SHUTTER AT EVERY FLOOR, NOTE IF THE FIRE SHUTTER
 IS CLOSED HOW CAN IT BE PART OF A REQUIRED EGRESS.
  
 707.2 EXCEPTION # 7, (7.2) CAN?T BE USED AGAIN BECAUSE
 IT IS PART OF A REQUIRED MEANS OF EGRESS.
  
 23) SHEET A2.2 DOOR# 201A IS WITHIN A 2HR RATED WALL
 BUT THE DOOR SCHEDULE INDICATES THE DOOR TO BE A 20
 MINUTE DOOR. PLEASES REVIEW TABLE 715.3 OPENING
 PROTECTIVE?S 2HR WALL REQUIRES A 1 ? OPENING
 PROTECTIVE.
  
 24) SHEET A2.2/ LS2, DOOR# 201A WHICH LEADS FORM
 MEETING ROOM 201 OUT INTO THE PARKING GARAGE BEHIND
 PARKED CARS TO REACH THE VERTICAL EXIT ENCLOSURE.
 1013.2 DOES NOT ALLOW TRAVEL EXIT ACCESS THROUGH A
 HIGHER HAZARD OCCUPANCY WITHOUT A RATED CORRIDOR TO
 TRAVEL IN TO REACH THE VERTICAL EXIT. PLEASE SEE
 ATTACHED BOAF INFORMAL INTERPRETATIONS.
  
 25) SHEET A2.2 PLEASE REVIEW THIS LEVEL OF GARAGE AND
 ALL ABOVE FOR CLASSIFICATION AS TO OPEN OR ENCLOSED
 GARAGE. 406.3.3.1. IF CONSIDERED OPEN THE DOOR SCHEDULE
 IS MISSING THE WIND DESIGN PRESSURES, ALL ARE
 +00.0/-00.0. 1609.6.2.2 COMPONENTS AND CLADDING THIS
 COMMENT WILL STAND FOR ALL OPENINGS WITHIN THE OPEN
 PARKING GARAGE FOR ALL FLOORS.
  
 26) SHEET A2.2 THE ELEVATOR MACHINE ROOM DOOR # 205
 DOES NOT INDICATE ANY FIRE RATING IN THE DOOR SCHEDULE
 SHEET A11.01 REVIEW 3006.4 REQUIRING A 2HR RATING.
  
 27) SHEET A2.02 NOTE FOR STRUCTURAL DRAWINGS TO PROVIDE
 DETAIL FOR ALL BLOCK WALLS TO WITHSTAND IMPACT LOADS,
 CRASH WALL STRUCTURAL PLANS HAVE SECTIONS THROUGH FOR 3
 RD AND FOURTH LEVEL BUT NONE FOUND FOR THE SECOND
 LEVEL. 1607.7.3.
  
 28) SHEET A2.02 STAIR# 2 THE EXTERIOR WALL IS MISSING
 THE WALL IDENTIFICATION TYPE AT THE EXTENSION OF
 STAIRWELL. 1019.1.
  
 29) SHEET A2.02 THE EAST SIDE OF THE OPEN PARKING
 GARAGE, THE PLANS DO NOT PROVIDE ANY DIMENSIONS AS TO
 THE DISTANCE THE FACE OF THE BUILDING IS LOCATED TO THE
 PROPERTY LINE. TABLE 704.8.
  
 30) SHEET A2.02 STAIRWELL# 3 WINDOW AA DOES NOT
 INDICATE ANY OPENING PROTECTIVE?S ON SHEET A12.01
 WINDOW SCHEDULE. PLEASE REVIEW 1019.1.4. VERTICAL
 ENCLOSURE EXTERIOR WALLS.
 EXTERIOR WALLS OF A VERTICAL EXIT ENCLOSURE SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 704 FOR
 EXTERIOR WALLS. WHERE NONRATED WALLS OR UNPROTECTED
 OPENINGS ENCLOSE THE EXTERIOR OF THE STAIRWAY AND THE
 WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF THE
 BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES (3.14
 RAD), THE BUILDING EXTERIOR WALLS WITHIN 10 FEET (3048
 MM) HORIZONTALLY OF A NONRATED WALL OR UNPROTECTED
 OPENING SHALL BE CONSTRUCTED AS REQUIRED FOR A MINIMUM
 1-HOUR FIRE-RESISTANCE RATING WITH ?-HOUR OPENING
 PROTECTIVE?S. THIS CONSTRUCTION SHALL EXTEND VERTICALLY
 FROM THE GROUND TO A POINT 10 FEET (3048 MM) ABOVE THE
 TOPMOST LANDING OF THE STAIRWAY OR TO THE ROOF LINE,
 WHICHEVER IS LOWER. THIS NOTE WILL SERVE FOR ALL
 FLOORS.
  
 31) SHEET A2.03 DOOR # 23 & 33 BOTH ARE INDICATED AS
 INTERIOR DOORS ON THE DOOR SCHEDULE BUT THIS LEVEL OF
 THE PARKING GARAGE IS CONSIDERED OPEN? 1609.6.2.2
 PLEASE INDICATE POSITIVE AND NEGATIVE WIND PRESSURES.
 THIS STATEMENT WILL BE COMMON TO ALL FLOORS.
  
 32) SHEET A2.03 ELEVATOR MACHINE ROOM 304 THIS DOOR ON
 THE DOOR SCHEDULE IS INDICATED AS A 20 MINUTE DOOR,
 PLEASE REVIEW 3006.4. NOT LESS THAN THE RATING OF THE
 HOIST WAY ENCLOSURE. 2 HR HOIST WAY ENCLOSURE REQUIRES
 1 ? HOUR OPENING PROTECTIVE.
  
 33) SHEET A2.04 ROOF TOP GARDEN AREA DOES NOT INDICATE
 ANY PITCH AS IN A ROOF TOP OR IN PLANTERS, ROOF DRAINS,
 SCUPPERS AND OR SECONDARY OR OVERFLOW ROOF DRAINS. NOTE
 THE SAME LEVEL AS THE GARAGE FLOOR. PLEASE INDICATE THE
 TYPE OF ROOF COVERING TO BE SUPPLIED.1503.1, 1503.4,
 1503.4.2 & 1503.4.3.
  
 34) SHEET A2.04 DOOR# 400A IS MISSING THE 18? ON THE
 LATCH SIDE OF THE DOOR 11-4.13.6
 MANEUVERING CLEARANCES AT DOORS.
  
 35) A2.05 DOOR# 524 THE ELECTRIC CLOSET THE DOORS SWING
 ACROSS ONE HALF OF THE REQUIRED EGRESS CORRIDOR WIDTH.
 1008.1.8.8 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF
 THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY,
 OR LANDING, NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY OR LANDING, WHEN FULLY OPEN. DOORS SHALL NOT
 OPEN IMMEDIATELY ONTO A STAIR WITHOUT A LANDING. THE
 LANDING SHALL HAVE A WIDTH AT LEAST EQUAL TO THE WIDTH
 OF THE DOOR.
  
 36) A2.05 STAIR TOWER# 2 THE PLANS INDICATE WOVEN WIRE
 SECURITY PARTITION AND DOOR BENEATH SLAB. PLEASE
 EXPLAIN DOES THIS DOOR BLOCK THE VERTICAL EXIT?
 1019.1.1.
 1019.1.1 OPENINGS AND PENETRATIONS.
 EXIT ENCLOSURE OPENING PROTECTIVE?S SHALL BE IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 715.
 EXCEPT AS PERMITTED IN SECTION 402.4.6, OPENINGS IN
 EXIT ENCLOSURES OTHER THAN UNEXPOSED EXTERIOR OPENINGS
 SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO
 THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES AND FOR
 EGRESS FROM THE ENCLOSURE.
  
 37) 37) A2.05 UNIT M ROOM 525 HAS A VERTICAL CHASE
 BUILT INTO ONE CORNER WITH WALL IDENTIFICATION TAG WALL
 TYPE 6. THIS WALL DOES NOT HAVE A STC RATING. 1207.2.
  
 38) A2.05 THIS FLOOR IS THE FIRST FLOOR ASSEMBLY WHERE
 STRUCTURE BORNE SOUND WILL NEED TO BE ADDRESSED. THIS
 COMMENT WILL ALSO STAND FOR ALL FLOORS ABOVE. 1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 39) A2.05 ELEVATOR LOBBY DOOR 514A IS INDICATED AS A 20
 MINUTE DOOR IN THE DOOR SCHEDULE BUT ALSO A TYPE ?K? OR
 ALUMINUM DOOR PLEASE PROVIDE MANUFACTURERS SPEC FOR 20
 MINUTE FIRE RATING USING THIS MATERIAL. TABLE 715.3.
  
 40) A2.05 ELEVATOR LOBBY DOORS ARE TO BE FIRE RATED
 DOORS 707.14.1 ELEVATOR LOBBY .HOW ARE THESE DOORS TO
 CLOSE UPON ACTIVATION OF ALARM SYSTEM 715.3.7.
  
 41) A2.05 THIS COMMENT WILL STAND FOR ALL FLOORS. DOOR
 513 THAT LEADS TO THE MAIDS ROOM IS LISTED WITHIN THE
 DOOR SCHEDULE AS A 20 MINUTE DOOR. THIS WOULD NORMALLY
 BE CORRECT BUT IN THIS CASE THE DOOR ALSO ACTS AS THE
 LAUNDRY CHUTE ACCESS DOOR THAT SEPARATES THE LAUNDRY
 CHUTE ROOM FROM THE CORRIDOR. 707.13.3 REFUSE AND
 LAUNDRY CHUTE ACCESS ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS COMPLETELY ENCLOSED BY
 CONSTRUCTION THAT HAS A FIRE-RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR AND OPENINGS INTO THE ACCESS ROOMS
 SHALL BE PROTECTED BY OPENING PROTECTIVE?S HAVING A
 FIRE PROTECTION RATING OF NOT LESS THAN ? HOUR AND
 SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE
 DETECTION OF SMOKE.
  
 42) SHEET A2.05 UNIT 501 THERE IS A WINDOW THAT IS NOT
 IDENTIFIED AND EXERCISE ROOM WINDOW DOES NOT HAVE A
 WINDOW IDENTIFICATION TAG. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 43) SHEET A2.05 EXERCISE ROOM WINDOW SINCE THE WINDOW
 SCHEDULE DOES NOT INDICATE ROOM WITH WINDOW TYPE THE
 DESCRIPTION OF THIS WINDOW IS BLOCKED ON THE
 ELEVATIONS, MAY BE A HAZARDOUS LOCATION PROVIDE
 ADDITIONAL INFORMATION. 106.1.2, 2406.3 HAZARDOUS
 LOCATION.
  
  
 44) PLEASE PROVIDE ELEVATIONS FOR THE POOL DECK WITH
 SLOPES, VARIOUS AREAS INDICATE SLOPED DECKS BUT THE
 TRUE ELEVATION ARE NOT PROVIDED SLOPES OF THE WET DECKS
 (424.1.3.1.2) . ALSO NOTE WHAT IS GOING TO BE THE
 COATING ON THE DECK MAKING IT WATERTIGHT. PLANS WILL
 NEED TO INDICATE DECK DRAINS AS WELL AS DRAINS FOR
 PLANTERS, NOTE ? OF THE VERTICAL CONTRIBUTION (WALL
 AREA) WILL NEED TO BE FIGURED INTO THE POOL DECK
 DRAINAGE CALCULATIONS.
  
 45) SHEET A2.05 ALSO INDICATES A SLEEVE FOR A ADA
 COMPLIANT LIFT. IF THE LIFT IS PROVIDED THEN PROVIDE
 MANUFACTURERS SPEC ON LIFT AND SLEEVE. 424.1.2.5.6- NOT
 A REQUIREMENT.
  
 46) SHEET A2.05 GLASS WALL WILL NEED TO BE FIGURED AS A
 GUARD RAIL SYSTEM MEETING THE REQUIREMENTS OF 2407
 .1-3.
  
 47) THIS COMMENT WILL STAND FOR ALL FLOORS. BETWEEN
 UNITS 509 & 510 THERE ARE DOUBLE DOORS PLEASE PROVIDE
 THE STC RATING FOR THESE DOORS .1207.2.
  
 48) SHEET A2.08 THE ROOF TOP DOOR IS MISSING TAG FOR
 IDENTIFICATION, 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 49) SHEET A2.08 GRID LINE C AND 11 THERE APPEARS TO BE
 A ROOF TOP HATCH, THE PENTHOUSE FLOOR PLAN DOES NOT
 INDICATE ANY SUCH HATCH?
  
 50) SHEET A2.08 ROOF TOP NOTES INDICATE THE USE OF NOA
 07-0517.02 SYSTEM TYPE ?F?
 FULLY ADHERED MEMBRANE. THIS SUB-SYSTEM AT THE HEADING
 OF THE PAGE INDICATES THIS IS FOR A NON-INSULATED
 LIGHTWEIGHT ROOFING APPLICATION, NOT THE ROOF SYSTEM
 R-VALUE PROVIDED ON THE PLAN OF R-11.37. NOTE THIS R
 VALUE WILL NEED TO MATCH ON THE INPUT DATA SHEET OF THE
 ENERGY CALCULATIONS. CHAPTER 13-404 ROOFS/ CEILINGS.
 PLEASE ALSO PROVIDE A INSULATION LAYOUT SHEET SHOWING
 THE MINIMUM OF R-11.37 AT THE ROOF DRAINS.
 13-404.1ABCD.1, SEE BOAF INFORMAL INTERPRETATIONS.
 SHEET A6.01 DETAIL A14.
  
 51) SHEET A2.08/ M11 BOTH INDICATE THE USE OF A/C
 STANDS, PLEASE SEE TABLE 15.22.3 FOR MINIMUM LEG HEIGHT
 OF STANDS. NOTE TAKE INTO ACCOUNT THE DEPTH OF
 INSULATION REQUIRED IT WILL TAKE TO CREATE THE ROOF
 SLOPE REQUIRED.
  
 52) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
  
 FL BLD CODE 1609.6.2.2/ RULE 9B-72 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 52A) FIXED
 52B) STOREFRONT
 52C) CURTAIN-WALL
 52D) MULLIONS VERTICAL/ HORIZONTAL
 52E) GLAZED EXTERIOR DOORS
 52F) INSULATED EXTERIOR DOORS SWING, SINGLE & PAIRS
 52G) OVERHEAD OR COIL DOORS
 52H) EXTERIOR LOUVER DOORS
 52I WALL LOUVERS
 52J) EFIS SYSTEMS
 52K) ROOFING PRODUCTS, INCLUDING WATERPROOFING
 52L) PRE-ENGINEERED A/C STANDS
  
 53) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 54) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 55) WIND PRESSURES FOUND ON SHEET S8.00 FOR WALL DESIGN
 ARE DESIGNED TO ASCE 7-02 FOR
 BUILDINGS LESS THAN OR EQUAL TO SIXTY FEET, THE TEXT
 SHOULD READ GREATER THAN OR EQUAL TO SIXTY FEET.
 MISPRINT.
  
 56) SHEET A4.01 INDICATES THE FLOOR BETWEEN GARAGE AND
 RESIDENCE TO BE SPRAY ON INSULATION TYPE PLEASE PROVIDE
 MANUFACTURERS SPEC FOR THIS INSULATION OPEN TO THE
 ELEMENT OF WIND. 13-405.1.A.B.1.
  
 57) SHEET A4.07 POOL COLLECTOR TANK PENETRATES THE
 FLOOR SLAB LETTING THE 5TH FLOOR AND FOURTH FLOOR
 COMMUNICATE TOGETHER. HOW IS A FIRE RATING TO BE
 MAINTAINED AT THE 5TH FLOOR ASSEMBLY, THE DOOR LEADING
 TO THE POOL EQUIPMENT (402) ALSO DOES NOT SHOW AS A
 RATED DOOR ON THE DOOR SCHEDULE. PLEASE PROVIDE MORE
 INFORMATION AS WHAT TYPE OF CHEMICALS WILL BE STORED IN
 THE POOL EQUIPMENT ROOM AND QUANTITIES. SECTION 707.2
 EXCEPTIONS,
 715.3 OPENING PROTECTIVE?S & TABLE 307.7(2).
  
 58) SHEET A8.01 INDICATES VARIOUS MASONRY WALLS WITH A
 2 HR FIRE RATING, PLEASE PROVIDE THE MINIMUM EQUIVALENT
 THICKNESS OF THE BLOCK FOR BEARING AND NON BEARING
 WALLS TABLE 721.3.2.THIS REPORT SHOULD BE PREPARED BY
 THE BLOCK MANUFACTURER.
  
 59) PLEASE PROVIDE DETAILS FOR PENETRATIONS OF FIRE
 RATED WALLS (712.3.1) AND PENETRATIONS THROUGH
 HORIZONTAL ASSEMBLIES (712.4.1).
  
 60) SHEET A9.01 PLEASE PROVIDE WHICH OF THE ELEVATORS
 MEETS THE SIZE REQUIREMENTS TO ACCOMMODATE A AMBULANCE
 STRETCHER, SECTION 3002.4. 24?X76? PLEASE PROVIDE A
 DEPICTION WITHIN THE CAB.
  
 61) SECTION 3002.8 EACH ENCLOSED ELEVATOR LOBBY AND
 EACH ELEVATOR MACHINE ROOM SHALL BE PROVIDED WITH AN
 APPROVED SMOKE DETECTOR OR OTHER AUTOMATIC FIRE ALARM
 INITIATING DEVICE WHERE ALLOWED BY NFPA 72 LOCATED IN
 THE LOBBY CEILING IN ACCORDANCE WITH
 NFPA 72. SMOKE DETECTORS SHALL BE INSTALLED IN HOIST
 WAYS WHICH ARE SPRINKLED, AND SHALL NOT BE INSTALLED IN
 UNSPRINKLED ELEVATOR HOIST WAYS UNLESS THEY ARE
 INSTALLED TO ACTIVATE THE HOIST WAY SMOKE RELIEF
 EQUIPMENT. WHEN THE SMOKE DETECTOR IS ACTIVATED, ALL
 AFFECTED ELEVATORS SHALL OPERATE IN CONFORMANCE WITH
 NFPA 72, SECTION 6.15.3. FIRE ALARM INITIATING DEVICES
 ARE NOT REQUIRED FOR ELEVATOR RECALL AT UNENCLOSED
 LOBBIES. E- 10 MISSING SMOKE DETECTOR IN ELEVATOR
 MACHINE ROOM, E-11 MISSING SMOKE DETECTOR IN ELEVATOR
 MACHINE ROOM AND E 13-E15 DO NOT SHOW SMOKE DETECTORS
 IN THE ELEVATOR LOBBY?S.
  
 62) SHEET E13-E15 ALSO DO NOT INDICATE HOW THE ELEVATOR
 LOBBY DOORS WILL AUTOMATICALLY CLOSE UPON THE
 ACTIVATION OF ALARM SYSTEM, NOR DID THE DOOR SCHEDULE
 A11.01. REQUIRED OPENING PROTECTION 707.14.1/ 715.3.
  
 63) A9.02 NOR FP1-FP8 LAUNDRY CHUTE DETAILS DOES NOT
 PROVIDE INFORMATION AS TO THE REQUIRED FIRE SPRINKLER
 REQUIRED WITHIN THE LAUNDRY SHAFT, 707.13.6.
  
 64) PROVISO: PROVIDE SHOP DRAWINGS FOR LAUNDRY CHUTE TO
 BE REVIEWED BY DESIGN TEAM BEFORE SUBMITTAL TO BUILDING
 DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC...
  
 65) SHEET A10.01 DETAIL A14 AND A10.02 DETAIL A10,
 INDICATES THE SECURITY GATE WITHIN THE CONFINES OF THE
 VERTICAL STAIR ENCLOSURE, EXIT ENCLOSURES SHALL NOT BE
 USED FOR ANY PURPOSE OTHER THAN MEANS OF EGRESS 1019.1.
 BOTH THE BUILDING AND FIRE REVIEWER WILL NEED TO REVIEW
 IF THIS WILL BE ALLOWED. THE CITIES INTERPRETATION HAS
 BEEN NOT TO ALLOW EVEN SECURITY CAMERAS WITHIN A
 VERTICAL EXIT. SUPPLY INFORMATION ON THE LOCKING
 MECHANISM, AUTOMATIC CLOSING DEVICE AND HOW BOTH WOULD
 BE FAIL SAFE UPON THE ACTIVATION OF THE ALARM SYSTEM.
 WHAT WOULD TRIGGER THE ACTIVATION OF THIS SYSTEM,
 SPRINKLERS, SMOKE ALARM ?
  
 66) BOTH A10.01 AND A10.02 FAIL TO INDICATE COMPLIANCE
 WITH 403.13 STAIRWELL PRESSURIZATION REQUIREMENTS FOR
 HIGH-RISE BUILDINGS EITHER THROUGH PASSIVE OR
 MECHANICAL SYSTEMS, THE MECHANICAL PLANS DO INDICATE
 THE CHASE AND FAN MOTORS FOR MECHANICAL PRESSURIZATION.
 PLEASE MAKE NOTATION WHERE COMPLIANCE CAN BE FOUND.
  
 67) PLEASE PROVIDE ADDITIONAL INFORMATION TO THE DOOR
 SCHEDULE OR DOORS INTO THE ENCLOSURE COMPLYING WITH
 403.12STAIRWAY DOOR OPERATION. SINCE COMMENT 65 ABOUT
 THE SECURITY GATE WITHIN THE STAIRWELL WILL MOST LIKELY
 NOT BE APPROVED. IF THE STAIRWELL DOORS WILL BE LOCKED
 FROM THE STAIRWELL SIDE THEY SHALL BE CAPABLE OF BEING
 UNLOCKED SIMULTANEOUSLY WITHOUT UNLATCHING UPON SIGNAL
 FROM THE FIRE COMMAND CENTER.
  
 68) SHOW COMPLIANCE WITH 403.12.1 STAIRWAY
 COMMUNICATION SYSTEMS 403.12.1FOR BOTH STAIR TOWERS.
  
 69) PLEASE PROVIDE COMPLIANCE WITH 403.15SMOKE CONTROL
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 909 SMOKE
 CONTROL SYSTEMS REQUIREMENTS FOR HIGH RISE BUILDINGS.
 THE MECHANICAL PLANS DO NOT INDICATE HOW THIS WILL BE
 ACCOMPLISHED.
  
 70) SHEET A10.03 GLASS HANDRAILS AND GUARDS, PLEASE
 SHOW COMPLIANCE WITH :
 2407.1 MATERIALS.
 GLASS USED AS STRUCTURAL BALUSTRADE PANELS IN RAILINGS
 SHALL BE CONSTRUCTED OF EITHER SINGLE FULLY TEMPERED
 GLASS, LAMINATED FULLY TEMPERED GLASS OR LAMINATED
 HEAT-STRENGTHENED GLASS. GLAZING IN RAILING IN-FILL
 PANELS SHALL BE OF AN APPROVED SAFETY GLAZING MATERIAL
 THAT CONFORMS TO THE PROVISIONS OF SECTION 2406.1.1.
 FOR ALL GLAZING TYPES, THE MINIMUM NOMINAL THICKNESS
 SHALL BE ? INCH (6.4 MM). FULLY TEMPERED GLASS AND
 LAMINATED GLASS SHALL COMPLY WITH CATEGORY II OF CPSC
 16 CFR 1201, LISTED IN CHAPTER 35.
 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED
 TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.7. A
 SAFETY FACTOR OF FOUR SHALL BE USED.
 607.7.1 HANDRAILS AND GUARDS.
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE DESIGNED TO
 RESIST A LOAD OF 50 PLF (0.73 KN/M) APPLIED IN ANY
 DIRECTION AT THE TOP AND TO TRANSFER THIS LOAD THROUGH
 THE SUPPORTS TO THE STRUCTURE.
 EXCEPTIONS:
 1. FOR ONE- AND TWO-FAMILY DWELLINGS, ONLY THE SINGLE,
 CONCENTRATED LOAD REQUIRED BY SECTION 1607.7.1.1 SHALL
 BE APPLIED.
 2. IN GROUP I-3, F, H AND S OCCUPANCIES, FOR AREAS THAT
 ARE NOT ACCESSIBLE TO THE GENERAL PUBLIC AND THAT HAVE
 AN OCCUPANT LOAD NO GREATER THAN 50, THE MINIMUM LOAD
 SHALL BE 20 POUNDS PER FOOT (0.29 KN/M).
 1607.7.1.1 CONCENTRATED LOAD.
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE ABLE TO RESIST
 A SINGLE CONCENTRATED LOAD OF 200 POUNDS (0.89 KN),
 APPLIED IN ANY DIRECTION AT ANY POINT ALONG THE TOP,
 AND HAVE ATTACHMENT DEVICES AND SUPPORTING STRUCTURE TO
 TRANSFER THIS LOADING TO APPROPRIATE STRUCTURAL
 ELEMENTS OF THE BUILDING. THIS LOAD NEED NOT BE ASSUMED
 TO ACT CONCURRENTLY WITH THE LOADS SPECIFIED IN THE
 PRECEDING PARAGRAPH.
 1607.7.1.2 COMPONENTS.
 INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL),
 BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO
 WITHSTAND A HORIZONTALLY APPLIED NORMAL LOAD OF 50
 POUNDS (0.22 KN) ON AN AREA EQUAL TO 1 SQUARE FOOT
 (0.093M2), INCLUDING OPENINGS AND SPACE BETWEEN RAILS.
 REACTIONS DUE TO THIS LOADING ARE NOT REQUIRED TO BE
 SUPERIMPOSED WITH THOSE OF SECTION 1607.7.1 OR
 1607.7.1.1.
 1607.7.1.3 STRESS INCREASE.
 WHERE HANDRAILS AND GUARDS ARE DESIGNED IN ACCORDANCE
 WITH THE PROVISIONS FOR ALLOWABLE STRESS DESIGN
 (WORKING STRESS DESIGN) EXCLUSIVELY FOR THE LOADS
 SPECIFIED IN SECTION 1607.7.1, THE ALLOWABLE STRESS FOR
 THE MEMBERS AND THEIR ATTACHMENTS ARE PERMITTED TO BE
 INCREASED BY ONE-THIRD.
  
 2407.1.2 SUPPORT.
 EACH HANDRAIL OR GUARD SECTION SHALL BE SUPPORTED BY A
 MINIMUM OF THREE GLASS BALUSTERS OR SHALL BE OTHERWISE
 SUPPORTED TO REMAIN IN PLACE SHOULD ONE BALUSTER PANEL
 FAIL. GLASS BALUSTERS SHALL NOT BE INSTALLED WITHOUT AN
 ATTACHED HANDRAIL OR GUARD.
  
 71)SHEET A11.01 DOOR SCHEDULE IS NOT COMPLETE, REMARKS
 ARE FOR THE MOST PART OPEN, NO MENTION OF DOOR
 HARDWARE, LOCKS LEVERS, PANIC HARDWARE, HINGES,
 ELECTRONIC LOCKS AND CLOSERS. SECTION 1008.
  
 72) SHEET A12.01 WINDOW SCHEDULE IS NOT COMPLETE. THE
 WINDOW SCHEDULE NOR PLANS HAVE INDICATED FOR THIS
 PROJECT IF FROM GRADE TO 30?-0? IF LARGE MISSILE WILL
 BE INSTALLED FROM 30?-60? SMALL MISSILE AND ABOVE 60?
 RATED ONLY FOR WIND. IF THE PROJECT DOES ELECT TO
 INSTALL WINDOWS AS SUCH PLEASE PROVIDE A DIAGRAM AND
 ALSO INCLUDE THE INTERIOR ZONE AND END ZONES. THE
 THRESHOLD INSPECTOR WILL NEED SUCH A DOCUMENT TO KEEP
 THE WINDOW PLACEMENT CORRECT, PLEASE ALSO PROVIDE THE
 WINDOW, REPORT NUMBER (FL OR NOA) AND ASSOCIATED
 PRESSURES ON THE SAME DOCUMENT. 1609.6.2.2.
  
  
 73) THIS COMMENT WILL STAND FOR ALL 14.00 SERIES PLANS.
 IN MOST CASES THE SUITE ENTRY DOORS ARE RECESSED IN THE
 CORRIDORS. SINCE THESE DOORS ARE 20 MINUTE RATED THEY
 DO ALSO REQUIRE CLOSERS AND LATCHES. 11-4.13.6 DOES
 REQUIRE A 12 INCH CLEARANCE ON THE CORRIDOR LATCH SIDE
 OF THE DOOR, IN MANY CASES THE PLANS ARE SHORT OF THE
 ONE FOOT REQUIREMENT.
  
 74) A12.01 WINDOW (N) IS A CURTAIN WALL SYSTEM PLEASE
 PROVIDE A LISTED FLOOR ASSEMBLY FOR THIS SYSTEM.
 04.13.1 VOIDS.
 THE VOID CREATED AT THE INTERSECTION OF A FLOOR/CEILING
 ASSEMBLY AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713.4.
  
 713.4 EXTERIOR CURTAIN WALL/FLOOR INTERSECTION.
 WHERE FIRE- RESISTANCE-RATED FLOOR OR FLOOR/CEILING
 ASSEMBLIES ARE REQUIRED, VOIDS CREATED AT THE
 INTERSECTION OF THE EXTERIOR CURTAIN WALL ASSEMBLIES
 AND SUCH FLOOR ASSEMBLIES SHALL BE SEALED WITH AN
 APPROVED MATERIAL OR SYSTEM TO PREVENT THE INTERIOR
 VERTICAL SPREAD OF FIRE. SUCH MATERIAL OR SYSTEMS SHALL
 BE SECURELY INSTALLED AND CAPABLE OF PREVENTING THE
 PASSAGE OF FLAME AND HOT GASES SUFFICIENT TO IGNITE
 COTTON WASTE WHERE SUBJECTED TO ASTM E 119
 TIME-TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF WATER
 (2.49 PA) FOR THE TIME PERIOD AT LEAST EQUAL TO THE
 FIRE-RESISTANCE RATING OF THE FLOOR ASSEMBLY. HEIGHT
 AND FIRE-RESISTANCE REQUIREMENTS FOR CURTAIN WALL
 SPANDRELS SHALL COMPLY WITH SECTION 704.9.
  
 75) LOUVERS NEW TO THE 2004 FBC- 2007
 SUPPLEMENTS1609.1.4(5) LOUVERS PROTECTING INTAKE AND
 EXHAUST VENTILATION DUCTS NOT ASSUMED TO BE OPEN THAT
 ARE LOCATED WITHIN 30 FEET (9144 MM) OF GRADE SHALL
 MEET REQUIREMENTS OF THE LARGE MISSILE TEST.
 IMPACT-RESISTANT COVERINGS SHALL BE TESTED AT 1.5 TIMES
 THE DESIGN PRESSURE (POSITIVE OR NEGATIVE) EXPRESSED IN
 POUNDS PER SQUARE FEET AS DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING SECTION 1609 FOR WHICH THE
 SPECIMEN IS TO BE TESTED.
  
 76) A12.01 THERE ARE MANY VARIOUS WINDOW WITHIN THE
 WINDOW SCHEDULE THAT QUALIFY AS A
 HAZARDOUS LOCATION 2406.3(7). PLEASE INDICATE AS SUCH
 IN WINDOW SCHEDULE REMARKS.
  
 77) SHEET A14.6 ACCESSIBLE UNIT THE PLAN INDICATES AT
 THE KITCHENETTE ? ON WALL BEYOND-NO BASE CABINET AT
 SINK?, YET THE PLAN CLEARLY INDICATES SWING DOORS ON
 THE SINK BASE UNIT. PLEASE CLARIFY.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK. THIS NOTE WILL STAND FOR ALL ACCESSIBLE UNITS.
  
 78) SHEET A14.01 ENTRY DOOR# 1. ALTHOUGH THIS UNIT IS
 NOT AN ACCESSIBLE UNIT THE CODE DOES NOT DISCERN OR
 MAKE ACCEPTATIONS TO 11-4.13.6 MANEUVERING CLEARANCES
 AT DOORS .
 THIS DOOR REQUIRES A DOOR CLOSURE AND LATCH THUS
 REQUIRING THE 1?-0? CLEAR ON THE CORRIDOR SIDE OF THE
 DOOR. TWO ISSUES, AGAIN THE DOOR SCHEDULE DOES NOT
 INDICATE THE HARDWARE REQUIRED FOR THIS DOOR.
  
 THE SECOND ISSUE IS ONE THAT CAN BE ARGUED, WE HAVE
 ACCESSIBLE ROOM MAKING AN EXEMPTION TO THE OTHER GUEST
 ROOMS. NO WHERE IN 11-4.13.6 DOES IT INDICATE
 EXCEPTIONS. IF A DISABLED PERSON RENTS TWO ROOM NOT
 ADJOINING AND WANTS TO CHECK ON THEIR CHILDREN IN
 ANOTHER ROOM THAT IS NOT ACCESSIBLE THEY WOULD BE
 UNABLE TO DO SUCH BECAUSE OF THE LIMITATION. NEIL
 MELICK OUR FORMER BUILDING OFFICIAL HAS SAT ON THE
 GOVERNORS? TAC BOARD FOR THE DISABLED AND NOW SITS ON
 THE FED BOARD, HE WILL BE CHECKING IN ON THIS SITUATION
 AND PROVIDE FURTHER INSIGHT. THIS COMMENT WILL STAND
 FOR ALL FLOORS.
  
 79) SHEET A2.01. ANOTHER ACCESSIBLE ISSUE WILL BE THE
 SERVING AND DINING AREA FIRST FLOOR THE BUFFET AND
 BREAKFAST AREAS, PLEASE SHOW COMPLIANCE WITH: SECTIONS
 11-5.1. 5% OF DINING AREAS, INCLUDING THE OUTSIDE
 DINING AREA AND 11-5.2 COUNTERS AND BARS (BUFFET AREA).
  
 80) SHEET A2.01. THE PASSENGER LOADING ZONE, PLEASE
 PROVIDE THE VERTICAL CLEARANCE IN THIS AREA AS WELL AS
 THE HEIGHT ALONG THE VEHICLE ROUTE. 11-4.6.5 VERTICAL
 CLEARANCE. PROVIDE MINIMUM VERTICAL CLEARANCE OF 114
 INCHES (2895 MM) AT ACCESSIBLE PASSENGER LOADING ZONES
 AND ALONG AT LEAST ONE VEHICLE ACCESS ROUTE TO SUCH
 AREAS FROM SITE ENTRANCE(S) AND EXIT(S). AT PARKING
 SPACES COMPLYING WITH SECTION 11-4.1.2(5)(B), PROVIDE
 MINIMUM VERTICAL CLEARANCE OF 98 INCHES (2490 MM) AT
 THE PARKING SPACE AND ALONG AT LEAST ONE VEHICLE ACCESS
 ROUTE TO SUCH SPACES FROM SITE ENTRANCE(S) AND EXIT(S).
  
 81) SHEET A15.01 THE REFLECTED CEILING PLAN INDICATES
 DROP CEILINGS IN THE COMPUTER ALCOVE AND LOBBY AREA BUT
 THE SECTION ON A4.03 DOES NOT PROVIDE DETAIL AS TO HOW
 THE GYPSUM WALL BOARD IS TO BE INSTALLED AT THE VARIOUS
 HEIGHTS, 106.1.2 ADDITIONAL INFORMATION REQUIRED, AND
 SECTION 2508.1 & TABLE 2508.1/ GYPSUM WALLBOARD.
  
 82) A15.01 LIGHTING NICHE THAT LEADS TO THE ELEVATORS
 SHEET A4.02 INDICATES VARIOUS CEILING HEIGHTS, SOFFITS,
 ETC BUT AGAIN THERE IS NO SECTION OR DETAIL MARKERS
 PROVIDING HOW THE FINISH GYPSUM WALL BOARD CEILINGS ARE
 TO BE INSTALLED THERE ARE NO DETAILS FOR THIS TYPE OF
 APPLICATIONS, SECTION 2508.1 & TABLE 2508.1 / GYPSUM
 WALLBOARD. THIS COMMENT WILL STAND FOR ALL FLOORS.
  
 83) A15.01 NOTE# 8 INDICATES FOR FINISH INFORMATION WE
 ARE TO REFER TO THE I. D. SET, NO FINISHES HAVE BEEN
 PROVIDED FOR THIS PLAN REVIEW.
  
 83A) PLEASE PROVIDE COMPLIANCE WITH 803.1AND TABLE
 803.5.
  
 83B) SINCE THERE ARE NO DETAILS OF SOFFITS NOR WALL
 FINISH DETAILS PLEASE REVIEW THE NEW DETAILS FOR
 803.4.2 SET OUT CONSTRUCTION.
  
 83C) IF THERE IS TO BE TEXTILE WALL COVERINGS COMPLY
 WITH 803.6.1.
  
 84) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-01-01 Cont ID  
Sent By dpalmer Date 2009-01-01 Time 16:42 Rev Time 8.75
Received By dpalmer Date 2009-01-01 Time 07:39 Sent To  
Notes
2009-01-01 16:42:52MARRIOTT RESIDENCE INN
  
 455 HIBISCUS ST
  
  
 *** DENIED REVIEW **
  
  
 ** IMPORTANT:
 IT IS VERY IMPORTANT TO UNDERSTAND THE REVIEW IS BASED
 ON THE PLANS SUBMITTED AT THIS TIME. AS THERE IS MANY
 ITEMS NOT YET COMPLETED OR SUBMITTED FOR REVIEW A
 COMPLETE REVIEW OF CODE COMPLIANCE DETERMINATION CAN
 NOT BE DONE AT THIS TIME. THERE MAY CERTAINLY BE NEW
 COMMENTS ON THE FOLLOWING REVIEW DUE TO CHANGES IN
 PLANS, SUBMITTED DOCUMENTS ETC WHICH IS NOT POSSIBLE TO
 BE MADE AT THIS TIME.
  
  
 1) NOTE: PLANS HAVE BEEN SUBMITTED FOR * PLAN REVIEW*
 ONLY AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE
 KNOW ONCE PERMIT APPLICATION IS MADE ITEMS SUCH AS
 LICENSING OF CONTRACTOR, AND OTHER DESIGN PROFESSIONALS
 WILL ALL BE VERIFIED AT THAT TIME. PLAN REVIEW DOES NOT
 *LOCK* A PROJECT IN UNDER THE CODE IN EFFECT AT THE
 TIME OF THE REVIEW. ONLY PLANS SUBMITTED FOR PERMIT
 APPLICATION WITH LICENSED CONTRACTOR. THIS IS GIVEN FOR
 INFORMATION ONLY AS THE FLORIDA BUILDING CODE IS SET TO
 CHANGE ON MARCH 1ST, 2009.
 EVEN ONCE ALL ITEMS NOTED FOR CODE COMPLIANCE ARE
 ADDRESSED AND PERMIT APPLICATION HAS NOT BEEN MADE THE
 REVIEW STATUS WILL STILL REMAIN FAILED.
  
 2) NOTE: THE INFORMATION OF THE PROJECT HAS BEEN ROUTED
 TO THE ADDRESSING REVIEWER. THE PROJECT WAS SUBMITTED
 UNDER AN ADDRESS OF 421 HIBISCUS ON THE PAPERWORK
 HOWEVER THE ADDRESS ON PLANS AND NOW IN OUR SYSTEM IS
 455 HIBISCUS. PLEASE BE SURE TO CONFIRM THIS ADDRESS IS
 THE FINAL LOCATION. ALL PLANS AND OTHER SUPPORTING
 DOCUMENTATION ONCE SUBMITTED WILL NEED TO COORDINATE.
 THIS COMMENT IS FOR COORDINATION OF PLANS AND
 DOCUMENTS.
  
 3) NOTE: THE CODES FOR THIS REVIEWER NEED TO BE STATED
 ON PLANS AS FOLLOWS. SOME OF THE CODES BELOW ARE LISTED
 AND ACCURATE HOWEVER SOME OTHERS LISTED ON PLANS ARE
 NOT CURRENTLY IN EFFECT. PLEASE BE SURE THE FOLLOWING
 IS NOTED ON THE ARCHITECTURAL SHEET GN2 AS WELL AS ON
 THE ELECTRICAL PLANS.
  
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70 (NATIONAL ELECTRICAL CODE)
 2003 NFPA-101 (LIFE SAFETY CODE)
 2002 NFPA-72 (NATIONAL FIRE ALARM CODE)
 2003 NFPA-20 ( STANDARD FOR STATIONARY FIRE PUMP)
 PLEASE ALSO BE SURE THE FP SHEETS CONTAIN THE REFERENCE
 TO NFPA-20 2003.
  
 ** THESE ARE NOTED FOR THIS REVIEWER. THERE MAY BE
 OTHERS NOTED BY OTHER TRADES.
 PLEASE SEE SOME NOTES BELOW AS THERE ARE SOME CODE
 REFERENCES TO CODES WHICH ARE NO LONGER ADOPTED IN THE
 STATE OF FLORIDA.
  
 4) NOTE: THE PROJECT AS SUBMITTED IS NOTED AND SHOWN AS
 A HOTEL FOR TRANSIENT LODGING. THIS IS NOTED FOR
 INFORMATION ONLY. PLEASE BE AWARE OF HOUSE BILL 7121
 WHICH AFFECTED NUMEROUS FLORIDA STATUTES WITH RESPECT
 TO RESIDENTIAL HIGH-RISE BUILDINGS. IF THERE IS ANY
 INTENT TO CHANGE THE OCCUPANCY OF THE BUILDING TO A
 CONDO AT A LATER DATE PLEASE BE AWARE OF SEVERAL
 ASPECTS OF THE STATUTES AND STATE LEGISLATION WHICH
 WOULD AFFECT DESIGN AS WELL AS CODE REQUIREMENTS. AS
 SUBMITTED THIS WOULD NOT AFFECT THE BUILDING AND IS
 NOTED FOR INFORMATION ONLY AS SOME OTHER HOTELS HAVE
 DONE THIS.
  
 5) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUTES 481.219. THE TITLE
 BLOCKS ON THE LANDSCAPE PLANS ARE MISSING INFORMATION
 AS REQUIRED.
 THE TITLE BLOCKS ARE MISSING PRINTED NAME AND LICENSE
 NUMBER OF THE LANDSCAPE DESIGNER. THE TITLE BLOCKS ARE
 ALSO MISSING THE REQUIRED CERTIFICATE OF AUTHORIZATION
 NUMBER. THIS REQUIRED ON ALL LANDSCAPE PLANS WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADE REVIEWS.
  
 6) NOTE: PLEASE BE SURE ALL RAISED SEALS ARE CLEAR AND
 VISIBLE. THE INFORMATION ON RAISED SEAL OF THE
 LANDSCAPE ARCHITECT IS NOT CLEAR AND VISIBLE AND COULD
 NOT BE READ. ON THE SET REVIEWED THE INFORMATION ON
 SEAL SUCH AS LICENSE NUMBER AND NAME COULD NOT BE READ
 EVEN USING LEAD RUB. THE VERIFICATION OF LICENSING OF
 SAID DESIGNER COULD NOT BE DONE. PLEASE SEE NOTE ABOVE
 WITH RESPECT TO PRINTED NAME AND LICENSE NUMBER OF
 DESIGNER AS REQUIRED.
  
 7) NOTE: ALL EXTERIOR LIGHTING OUTSIDE THE PROPERTY
 LINE OR IN THE RIGHT OF WAY AREAS BEING INSTALLED OR
 REPLACED SHALL BE UNDER SEPARATE PERMITS. THESE ALSO
 MAY NOT BE FED FROM THE ELECTRICAL SERVICE IN THIS
 BUILDING. PLEASE CONTACT JONATHAN BRAMLEY OF ENGINEER
 SERVICES FOR INFORMATION ON RIGHT OF WAY LIGHTING
 SPECIFICS. HIS CONTACT INFORMATION IS [email protected]
 OR 561-494-1089.
 ALL EXTERIOR LIGHTING WITHIN THE PROPERTY BOUNDARIES
 MAY BE FED FROM THIS BUILDING.
  
 8) NOTE: THE ELECTRICAL PLANS INDICATE LIGHTING INSIDE
 THE FPL VAULT. THIS IS NOT PERMITTED AS THIS IS AN
 EASEMENT ARE BELONGING TO FPL AND ALSO TO FPL VAULT
 STANDARDS. PLEASE BE SURE TO CONTACT THE FPL
 REPRESENTATIVE TO OBTAIN AN SPECIFICS REQUIRED BY FPL.
 THE ELECTRICAL LIGHTING ETC AS SHOWN ON PLANS WILL NOT
 BE PART OF THIS PERMITTED SCOPE OF WORK. ANY LIGHTING
 INSTALLED IN THE FPL VAULT EASEMENT AREA IS UNDER
 UTILITY JURISDICTION.
 PLANS ALSO IDENTIFY A SUMP PIT. IF THIS PIT CONTAINS
 ANY ELECTRICAL SUMP PUMP IT SHALL NOT BE FED FROM THE
 ELECTRICAL SERVICE OF THE BUILDING. THIS WOULD ALSO BE
 UNDER FPL UTILITY VAULT EASEMENT AREA.
 PLEASE BE SURE TO OBTAIN FPL VAULT CONSTRUCTION
 STANDARDS OF THE VAULT. IN ANY CASE THE NEC PROVIDES
 MINIMUM RATINGS WHICH MUST BE MET FOR WALLS, FLOORS,
 DOORS ETC. THESE SHALL BE 3HR MINIMUM AND CONSTRUCTED
 OF CONCRETE. IT IS NOT PERMITTED TO HAVE ANY OF THE
 CONSTRUCTION MATERIALS OF WALL BOARD AND THE LIKE. AS
 THE FPL VAULT WILL NOT CONTAIN SPRINKLERS IT IS NOT
 PERMITTED TO GO TO LESSER RATING.
  
 9) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS. SOME WERE SUBMITTED AND SHOWN FOR GARAGE
 AREAS HOWEVER THESE ARE NOT ALL EGRESS PATHS. PLEASE BE
 SURE TO SEE NFPA-101 7.8.1.3, 7.9.1.2, 7.9.2.2, FBC
 1006.2.1, .2.3. ALL EGRESS STAIRS SHALL CONTAIN A
 MINIMUM OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED
 TO GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS.
 THIS IS BASED ON AN AVERAGE PER FORMULA STATED IN THE
 LIFE SAFETY CODE.
 ** IMPORTANT**
 IF THIS BUILDING IS GOING TO REMAIN OCCUPIED UNDER
 EMERGENCY POWER DURING OR AFTER AN EVEN SUCH AS A
 HURRICANE OR OTHER TIME WHEN NORMAL POWER IS LOST THE
 BUILDING SHALL CONTAIN BATTERY BACK UP LIGHTING IN ALL
 EGRESS PATHS TO MEET THE 1FT CANDLE AVERAGE. THE LIFE
 SAFETY CODE AS WELL AS CHAPTER 10 OF THE FLORIDA
 BUILDING CODE ADDRESSES THE REQUIRED EGRESS LIGHTING TO
 EXIT *ALL* OCCUPANTS OUT OF THE BUILDING IN EMERGENCY
 EVENT OR LOSS OF NORMAL POWER.
 WHEN A BUILDING IS OCCUPIED UNDER EMERGENCY POWER THE
 BACK UP SYSTEM OF THE PREVIOUS NORMAL POWER HAS NOW
 BECOME THE NORMAL POWER. A LOSS OF ONE BREAKER SUCH AS
 THE GENERATOR MAIN OR THE GENERATOR ITSELF GOING DOWN
 WOULD REMOVE ALL LIFE SAFETY BACK UP FOR LIGHTING AND
 EGRESS PATHS.
 PLEASE CALL TO GO OVER OTHER OPTIONS WHICH WOULD
 REQUIRE A LETTER THE OWNER WHICH WOULD BE REQUIRED TO
 EVACUATE ALL OCCUPANTS WHEN THE BUILDING GOES INTO
 EMERGENCY POWER BACK UP. THE WORDING TO THAT AFFECT
 WOULD BE GONE OVER AT A LATER DATE IF THAT IS THE
 OPTION.
 BASED ON THE PLANS SUBMITTED OTHER LOCATIONS WHICH WILL
 REQUIRE BATTERY BACK UP LIGHTING FIXTURES OF SOME TYPE
 WHETHER OR NOT BUILDING REMAINS OCCUPIED WILL BE THE
 STAIRS, EMERGENCY GENERATOR ROOM, FIRE PUMP ROOM, MAIN
 ELECTRICAL ROOM, ELEVATOR EQUIPMENT ROOMS AND FIRE
 COMMAND ROOM. THERE ARE AREAS OF THE PLANS WHICH DO NOT
 MEET THE WIRING REQUIREMENTS AND ARE ALSO REQUIRED TO
 CONTAIN BATTERY BACK UP FIXTURE FOR EGRESS LIGHTING.
 PLEASE SEE SECTIONS ABOVE AS WELL AS 700.12F, 700.16
 ETC.
 ALL STAIRS BASED ON WIRING AS SHOWN ARE REQUIRED TO BE
 BATTERY BACK UP. BASED ON CIRCUITING AND SYMBOL LEGEND
 WHICH DOE NOT INDICATE THE FIXTURES AS BATTER Y BACK UP
 THE GENERATOR MAY NOT BE USED AS THE SOLE BACK UP FOR
 EGRESS LIGHTING.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE LIFE SAFETY CODE. 7.9.2.2
  
 THE EMERGENCY LIGHTING SYSTEM SHALL BE ARRANGED TO
 PROVIDE THE REQUIRED ILLUMINATION AUTOMATICALLY IN THE
 EVENT OF ANY INTERRUPTION OF NORMAL LIGHTING DUE TO ANY
 OF THE FOLLOWING:
 (1) FAILURE OF A PUBLIC UTILITY OR OTHER OUTSIDE
 ELECTRICAL POWER SUPPLY
 (2) OPENING OF A CIRCUIT BREAKER OR FUSE
 (3) MANUAL ACT(S), INCLUDING ACCIDENTAL OPENING OF A
 SWITCH CONTROLLING NORMAL LIGHTING FACILITIES
  
 THERE ARE NUMEROUS LOCATIONS ON PLANS IN WHICH THE
 OPENING OR TRIPPING OF SINGLE CIRCUIT BREAKER WILL
 LEAVE EGRESS AREAS IN TOTAL DARKNESS. THIS IS WHETHER
 OR NOT BUILDING IS OCCUPIED UNDER GENERATOR POWER.
  
 *** PLEASE SEE NOTES #24 AND #40 ON SHEET E-24 WHICH
 CONFLICTS WITH FIXTURES ON SYMBOL LEGEND AND ON PLANS.
  
 10) NOTE: THE FIRST FLOOR POWER PLANS CONTAINS A NOTE
 FOR THE MAIN ELECTRICAL ROOM AND FIRE PUMP ROOM FOR
 SIGNAGE HOWEVER THESE ARE NOT THE ONLY TWO LOCATIONS.
 OTHER LOCATIONS SUCH AS THE FIRE COMMAND ROOM AND THE
 EMERGENCY GENERATOR ROOM WOULD ALSO REQUIRE SUCH
 SIGNAGE. ALL OF THESE ROOMS ARE ALSO REQUIRED TO
 CONTAIN PERMANENT MAPPING CONTAINING A LAYOUT OF THE
 BUILDING SHOWING THE LOCATIONS OF EACH OF THESE ROOMS
 CLEARLY IDENTIFIED. THIS WOULD BE REQUIRED IN ALL ROOMS
 NOTING EACH OF THE OTHERS. THIS COMMENT MAY BE ADDRESS
 BY NOTES ON PLANS. THIS WILL ONE OF THE REQUIRED ITEMS
 BY THE CONTRACTOR TO HAVE ALL SIGNAGE UP FOR ALL MAINS,
 ELECTRICAL SERVICES, FIRE PUMPS, FIRE COMMAND ROOM ETC
 BEFORE ANY RELEASE OF POWER. THIS IS NOT THE ONLY
 REQUIREMENT OTHERS WILL BE DIRECTED AT A LATER DATE BY
 THE INSPECTION STAFF.
 230.2E, 700.8,701.9, ETC
  
 11) NOTE: PLEASE BE SURE TO LIST ALL OF THE FOLLOWING
 ITEMS REQUIRED TO BE LOCATED IN THE FIRE COMMAND ROOM.
 NFPA-101 11.8.5 THESE ARE SYSTEMS AT A MINIMUM. PLEASE
 SEE NOTES FORM OTHER TRADES SUCH AS THE FIRE MARSHAL
 WHICH MAY ALSO NOTE OTHER ITEMS.
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER
 SECTION OF THIS CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) SPRINKLER VALVE AND WATER-FLOW ANNUNCIATORS
 (6) EMERGENCY GENERATOR STATUS INDICATORS
 (7) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (8) FIRE PUMP STATUS INDICATORS
 (9) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
  
 12) NOTE: PLEASE BE SURE THE ELEVATION OF ALL EMERGENCY
 ELECTRICAL SYSTEMS SUCH AS THE GENERATOR, EQUIPMENT,
 FIRE PUMP ETC IS LISTED ON PLANS. THE ELEVATIONS ARE
 REQUIRED TO MEET ONE OF THE FOLLOWING; EITHER THE 100
 YEAR STORM ELEVATION OR THE ELEVATION SET FORTH BY THE
 SLOSH (SEA, LAKE, OVERLAND SURGES BY HURRICANES) CHARTS
 BASED ON A CATEGORY 4 HURRICANE.
 AS THE PLANS ALREADY CONTAIN INFORMATION FOR SUMP PIT
 IN SOME LOCATIONS OTHER THAN THE ELEVATOR PITS THERE IS
 A CONCERN OF THE ELEVATIONS OF EQUIPMENT.
 PLEASE PROVIDE THIS INFORMATION.
  
 13) NOTE: AS NOTED ABOVE FOR COMPLETE PHOTO-METRICS FOR
 EGRESS. PLEASE ALSO INCLUDE THE LIGHTING LEVELS IN THE
 EMERGENCY GENERATOR ROOM. PLEASE SEE NFPA-110 7.3.3.
 THE LIGHTING LEVELS IN THIS ROOM SHALL BE AT A MINIMUM
 OF 30FT CANDLES.
  
 14) NOTE: PLEASE ALSO INCLUDE THE LIGHTING LEVELS FOR
 ELEVATOR PITS TO MEET THE MINIMUM OF 5 FT CANDLES.
 PLEASE SEE NEC 620.23 WHICH CONTAINS REFERENCE TO
 MINIMUM REQUIREMENTS. SEE HANDBOOK COMMENTARY; ASME
 A17.1-2004, SAFETY CODE FOR ELEVATORS AND ESCALATORS,
 REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX) AT THE PIT
 FLOOR AND REQUIRES LUMINAIRES TO BE EXTERNALLY GUARDED
 TO PREVENT ACCIDENTAL BREAKAGE.
 THE POWER PLANS AS WELL AS THE LIGHTING PLANS CONTAIN A
 *J* WHICH IS NOTED AS A JUNCTION BOX ON THE SYMBOL
 LEGEND. AT THIS TIME NO REQUIRED LIGHTING IS SHOWN.
  
 15) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS IN
 COMPLIANCE WITH ALL SECTIONS OF FLORIDA BUILDING CODE
 CHAPTER 13.
 PLEASE BE SURE TO SEE AREAS SUCH AS
 13-415.2,13-415.2.ABC.1.1, .1.2 AND .1.3 FOR LIGHTING
 PERFORMANCE LEVELS. PLEASE BE SURE TO SEE SECTION NOTES
 FOR ITEMS SUCH AS TRACK LIGHTING, HID LIGHTING ETC
 WHICH ARE NOT ALWAYS BASED ON BULB WATTAGE.
 THE COORDINATION OF ALL ITEMS ON THE INPUT DATA REPORT
 FOR *ALL* BUILDING COMPONENTS IS MOST IMPORTANT. THE
 LACK OF COORDINATION OF THE IDR WITH THE PLANS IS ONE
 OF THE KEY ITEMS IN THE DELAY OF ISSUANCE OF MANY
 BUILDING PERMITS. AS THIS PROJECT WAS ONLY SUBMITTED
 UNDER PLAN REVIEW THE NEW REQUIREMENTS OF THE FLORIDA
 BUILDING CODE BEING ADOPTED IN MARCH OF 2009 WILL
 GREATLY INCREASE THE STRINGENCY OF THIS CHAPTER OF THE
 FBC.
 AS NO ENERGY CALCULATIONS WERE SUBMITTED FOR REVIEW IT
 IS NOT POSSIBLE TO COMMENT ON CALCULATIONS AT THIS
 TIME.
 ** ONCE AGAIN WHEN SUBMITTING THE CALCULATIONS ALONG
 WITH THE IDR, PLEASE BE SURE ALL ITEMS ON PLANS
 COORDINATE WITH THE SUBMITTED CALCULATIONS.
  
 16) NOTE: PLEASE SUBMIT LIGHTING PLANS IN COMPLIANCE
 WITH THE MINIMUM REQUIREMENTS OF FBC CHAPTER 13 FOR
 LIGHTING CONTROLS. PLEASE SEE 13-415.1.ABC.1 WHICH
 REQUIRES *ALL* LIGHTING IN ANY BUILDING GREATER THAN 5K
 SQ FT TO BE AUTOMATICALLY SHUT OFF WHEN ANY AREA OR
 BUILDING IS NOT OCCUPIED. THERE ARE SOME EXCEPTIONS TO
 THIS REQUIREMENT HOWEVER MANY AREAS OF THIS BUILDING IS
 NOT CONSIDERED 24HR OPERATION OR MEET THE DEFINITIONS
 OF PATIENT CARE. THERE WOULD BE SOME AREAS/ROOMS IN
 WHICH MAY BE CONSIDERED A HAZARD TO THE OCCUPANTS IF
 THE LIGHTING WAS AUTOMATICALLY SHUT OFF SUCH AS THE
 ELECTRICAL ROOMS. (SEE NEC 110.26 SECTION FOR
 ILLUMINATION)
 THERE ARE MANY LOCATIONS ON PLANS WHICH ONLY INDICATE A
 STANDARD SINGLE POLE SWITCH FOR THE LIGHTING CONTROLS
 WHICH IS NOT PERMITTED. SOME OF THE FOLLOWING LOCATIONS
 ARE NOTED FOR EXAMPLE LOCATIONS OF THIS AND IS NOT ALL
 LOCATIONS ON PLANS WHICH ARE NOT CODE COMPLIANT.
 SEE ROOMS:
 120,121,124,125,123,135,134,133,130,131,107,106,105 ETC
 THESE ARE ONLY SOME ROOMS WHICH ARE NOTED FOR EXAMPLE.
 THERE ARE MANY OTHERS.
  
 A) PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 FOR
 ALL AREAS WHICH REQUIRE LIGHTING CONTROLS. THE PLANS
 CONTAIN A NOTE WHICH MENTIONS THE ENTIRE BUILDING IS
 UNDER ENERGY MANAGEMENT HOWEVER BASED ON THE ITEMS
 LISTED ABOVE, **ALL ** SEPARATE SPACES WHICH CONTAIN
 FLOOR TO CEILING HEIGHT PARTITIONS SUCH AS ROOMS AND
 AREAS REQUIRES AN OVER RIDE OF SUCH A SYSTEM OR MEET
 THE REQUIREMENTS FOR INDIVIDUAL SPACES.
 PLEASE ALSO SEE THE CONTROLS IN THE 13-415.1.ABC.1 (1)
 FOR ANY MORE THAN ONE LEVEL WHICH REQUIRES SEPARATE
 CONTROLS.
 PLEASE SEE FBC 1006.1.2 AND NFPA-10 17.8.1.2.2 FOR ANY
 DEVICES CONTROLLING EGRESS LIGHTING AS THESE SHALL BE
 *FAIL-SAFE ON* DEVICES.
 PLEASE SEE AREAS SUCH AS MULTI-GANG BATHROOMS WHICH
 WILL REQUIRE DUAL TECHNOLOGY DEVICES. IN THESE AREAS
 AND OTHER POSSIBLE AREAS IT WILL NOT BE PERMISSIBLE TO
 USE ONLY MOTION SENSOR TYPE DEVICES.
  
 B) PLEASE BE SURE TO SEE 13-415.1.ABC.1.4 FOR EXTERIOR
 LIGHTING CONTROLS REQUIRED. THERE ARE ONE OF TWO
 METHODS PERMITTED FOR CONTROLS. (BOTH MAY BE USED).
 IF USING AN ASTRONOMICAL TIME CLOCK PLEASE BE SURE TO
 LIST THE MINIMUM REQUIRED PROGRAMMING BATTERY BACK UP
 TIME. THE CODE REQUIRES 10HRS MINIMUM.
  
 C) PLEASE BE SURE TO SEE SECTION 13-415.1.ABC.1.3 AS
 NOTED ABOVE TO HOTEL AND MOTEL GUEST ROOMS. THESE SHALL
 CONTAIN CONTROLS TO TURN OFF ALL LIGHTING IN THE
 GUESTROOMS/SUITES WHEN THEY ARE NOT OCCUPIED. THIS
 INCLUDES ALL OUTLETS INCLUDING SWITCHED RECEPTACLES
 WHICH MAY CONTAIN LIGHTING FIXTURES WHICH MAY BE OF THE
 PLUG-IN TYPE. THE USE OF STANDARD SINGLE POLE OR 3-POLE
 SWITCHES IS NOT PERMITTED. THESE DO NOT MEET ANY
 AUTOMATED CONTROLS.
  
 D) PLEASE SEE THERE IS LIGHTING ON PLANS WHICH DO NOT
 SHOW ANY LIGHTING CONTROLS AT ALL INCLUDING NO
 CIRCUITING ETC.
  
 E) PLEASE BE SURE TO SEE SOME ROOMS SUCH AS CONFERENCE
 ROOMS, EMPLOYEE BREAK ROOMS ETC AS LISTED IN
 13-415.1.ABC.1.2 REQUIRE OCCUPANCY SENSORS WHETHER OR
 NOT PART OF ANY BUILDING AUTOMATION SYSTEM.
  
 F) PLEASE SEE NOTE #31 ON SHEET E24 WHICH CONFLICTS
 WITH THE LIGHTING CONTROLS ON PLANS AND INFORMATION
 SHOWN/SUBMITTED.
  
 THE INTENT OF THE ENERGY CODE AND THE MINIMUM FEDERALLY
 ADOPTED REQUIREMENTS IS THAT LIGHTING IS TURNED OFF TO
 CONSERVE ENERGY WHEN THE ROOM(S) AND AREAS ARE NOT
 OCCUPIED. IN JULY OF 2004 THE FEDERAL MANDATES ADOPTED
 1999 ASHRAE 90.1. ALL STATES IN THE US WERE REQUIRED TO
 ADOPTED THIS MINIMUM STANDARD OR EQUIVALENT BY THEIR
 NEXT CODE CYCLE. THE FEDERAL MANDATES HAVE HAD
 ADJUSTMENTS SINCE THAT DATE. THE STATE OF FLORIDA
 ADOPTED THE FLORIDA ENERGY EFFICIENCY CODE (CHAPTER 13)
 IN THE 2001 FBC CODE CYCLE AND WAS SUBSTANTIALLY
 CHANGED IN THE ADOPTION OF THE 2004 FBC OCT 1ST, 2005.
 THERE HAVE BEEN SEVERAL REVISIONS TO THE 2004 FBC WHICH
 HAVE AFFECT CHAPTER 13 AND MORE SPECIFICALLY LIGHTING
 CONTROLS.
 ** THIS NOTE GIVES SECTIONS FOR LIGHTING CONTROLS WHICH
 ARE REQUIRED TO MEET A *MINIMUM*. THERE ARE MANY
 SYSTEMS ON THE MARKET WHICH MEET THE MINIMUM AND MANY
 WHICH MEET THE MINIMUM AND ABOVE. THIS OFFICE/REVIEWER
 ONLY REQUIRES THE MINIMUM MEETING THE FLORIDA BUILDING
 CODE. ANY SYSTEMS CHOSEN BY THE DESIGN TEAM WHICH GO
 ABOVE THE MINIMUM REQUIREMENTS OF THE CODE WILL NOT BE
 REJECTED AS THEY MOST CERTAINLY MEET THE MINIMUM.
  
 IF ANY OF THESE ITEMS NEED TO BE GONE OVER IT IS BEING
 NOTED TO CALL AND GO OVER ANY QUESTIONS OR COMMENTS.
 AS THERE ARE MANY ASPECTS OF THE PLANS WHICH DO NOT
 SHOW THE MINIMUM AT THIS TIME THERE MAY BE NEW COMMENTS
 ON THE FOLLOWING REVIEW ONCE INFORMATION IS SUBMITTED
 OR SHOWN.
 PLEASE BE SURE CHECK LISTING PER 110.3 OF ANY PROPOSED
 SYSTEMS AND PLEASE SUBMIT COMPLETE SYSTEMS PROPOSAL FOR
 ANY BUILDING MANAGEMENT SYSTEM.
  
 17) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FOLLOWING ITEMS.
 THE GENERATOR.
 FIRE PUMP.
 FIRE PUMP CONTROLLER.
 ATS (AUTOMATIC TRANSFER SWITCH).
 FUEL TANK. THE FUEL TANK WILL BE REVIEWED BY OTHERS)
  
 MINIMUM EQUIPMENT MEETING THE CODE AT THIS TIME MUST BE
 VERIFIED. EVEN IF THE EQUIPMENT IS NOT FINALIZED
 EQUIPMENT WILL NEED TO BE CHOSEN AT THIS TIME. THE
 MANUFACTURE OR BRAND OF EQUIPMENT MAY ALWAYS BE CHANGED
 AT A LATE DATE.
 90.7,110.3, NFPA_20, NFPA-101, NFPA-70, NFPA-110.
 FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 18) NOTE: PLEASE PROVIDE ALL SHUT DOWN OF ALL EQUIPMENT
 IN IT ROOM INCLUDING A/C UNIT. THE PLANS DO NOT SHOW
 ANY EPO (EMERGENCY POWER OFF) BUTTON AS REQUIRED PER
 645.10. THE PANEL SCHEDULE FEEDING THE IT PANEL AND THE
 IT PANEL SCHEDULE ALSO DOES NOT LIST ANY SHUNT TRIP
 BREAKERS. PLEASE SEE 645.10 FOR DISCONNECTING
 REQUIREMENTS.
 PLEASE SEE NEC 645.4 REQUIREMENTS OF AN IT ROOM. WHEN
 ANY PROPOSED ROOM DOES MEETS ALL ITEMS LISTED PER 645.4
 THE WIRING METHODS WHICH ARE LESS STRINGENT IN THIS
 CODE SECTION MAY NOT BE USED.
 PLEASE MEET ALL OF 645.4 OR PLEASE CHANGE DESIGNATION
 AND PROVIDE NOTE FOR WIRING METHODS OF CHAPTERS 1-4
 MUST BE USED. IT MAY BE HELPFUL TO CONTACT IT PERSONNEL
 FOR MARRIOTT TO CONFIRM WIRING METHODS TO BE USED.
 THE FOLLOWING IS EXTRACTED FROM THE NEC FOR EASE OF
 CODE SECTIONS:
  
  
 THIS ARTICLE SHALL APPLY, PROVIDED ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) DISCONNECTING MEANS COMPLYING WITH 645.10 ARE
 PROVIDED.
 (2) A SEPARATE HEATING/VENTILATING/AIR-CONDITIONING
 (HVAC) SYSTEM IS PROVIDED THAT IS DEDICATED FOR
 INFORMATION TECHNOLOGY EQUIPMENT USE AND IS SEPARATED
 FROM OTHER AREAS OF OCCUPANCY. ANY HVAC SYSTEM THAT
 SERVES OTHER OCCUPANCIES SHALL BE PERMITTED TO ALSO
 SERVE THE INFORMATION TECHNOLOGY EQUIPMENT ROOM IF
 FIRE/SMOKE DAMPERS ARE PROVIDED AT THE POINT OF
 PENETRATION OF THE ROOM BOUNDARY. SUCH DAMPERS SHALL
 OPERATE ON ACTIVATION OF SMOKE DETECTORS AND ALSO BY
 OPERATION OF THE DISCONNECTING MEANS REQUIRED BY
 645.10.
 FPN: FOR FURTHER INFORMATION, SEE NFPA 75-2003,
 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT, CHAPTER 10, 10.1, 10.1.1, 10.1.2, AND
 10.1.3.
 (3) LISTED INFORMATION TECHNOLOGY EQUIPMENT IS
 INSTALLED.
 (4) THE ROOM IS OCCUPIED ONLY BY THOSE PERSONNEL NEEDED
 FOR THE MAINTENANCE AND FUNCTIONAL OPERATION OF THE
 INSTALLED INFORMATION TECHNOLOGY EQUIPMENT.
 (5) THE ROOM IS SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTANT-RATED WALLS, FLOORS, AND CEILINGS WITH
 PROTECTED OPENINGS.
 FPN: FOR FURTHER INFORMATION ON ROOM CONSTRUCTION
 REQUIREMENTS, SEE NFPA 75-2003, STANDARD FOR THE
 PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT, CHAPTER
 5.
  
 ALL ITEMS ABOVE WITH THE EXCEPTION OF # 1 ABOVE ARE
 SHOWN ON PLANS.
  
 19) NOTE: PLEASE SEE 110.26 AS THE MAIN ELECTRICAL ROOM
 WHICH REQUIRES THE DOORS TO SWING OUTWARD. THE DOORS
 SHALL ALSO BE EQUIPMENT WITH PANIC HARDWARE, PRESSURE
 PLATES OR OTHER TYPES OF LOCKING MECHANISMS WHICH DOES
 NOT IMPEDED THE EGRESS OF ANY PERSONNEL IN THE ROOM IN
 THE EVENT OF AN EMERGENCY. AN OCCUPANT WHICH HAS HAD A
 FLASH, BURN OR OTHER INJURY NEEDS TO EXIT THE ROOM
 WITHOUT HAVING USE HANDS, EYES ETC TO EXIT. THERE ARE
 MANY DOCUMENTED CASES IN WHICH THIS IS SUCH A HAZARD.
  
 20) NOTE: PLEASE PLACE NOTES ON PLANS FOR SIGNAGE
 REQUIRED FOR ARC FLASH OF ALL EQUIPMENT MEETING 110.16
  
 21) NOTE: PLEASE SEE 210.8B2 AS ALL 15 AND 20 AMP 120V
 RECEPTACLES IN KITCHEN AND BUFFET AREA WILL BE REQUIRED
 TO BE GFI OR GFI PROTECTED. THIS DOE NOT MATTER IF
 THESE RECEPTACLES ARE SERVING COUNTER SPACES.
  
 22) NOTE: PLEASE SEE 210.63, 210.8B3,4,AND 5. THERE ARE
 LOCATIONS ON PLANS IN WHICH REMOTE AIR CONDITIONING OR
 REFRIGERATION EQUIPMENT IS NOTED HOWEVER NO RECEPTACLE
 FOR SERVICING COULD BE LOCATED ON PLANS.
 PLEASE BE SURE ALL LOCATIONS OF OUTSIDE OR ROOF TOP
 EQUIPMENT CONTAIN THESE DEVICES FOR SERVICING AS WELL
 AS PROTECTION.
  
 23) NOTE: PLEASE SEE FBC 3006.2 FOR REQUIRED
 CONDITIONING/VENTILATION OF ELEVATOR EQUIPMENT ROOMS.
 THE ELECTRICAL PLANS DO SHOW ELECTRICAL FOR ELEVATOR
 EQUIPMENT HOWEVER ANY EQUIPMENT ON MECHANICAL PLANS
 WHICH ARE BEING INSTALLED TO MEET THIS CODE SECTION
 NEEDS OT BE SHOWN ON ELECTRICAL PLANS.
  
 24) NOTE: PLEASE SEE 620.23 AS NOTED ABOVE FOR ELEVATOR
 PIT AREAS FOR LIGHTING LEVELS. THIS SAME SECTION
 REQUIRES THE LIGHTING AS WELL AS RECEPTACLES IN THESE
 EQUIPMENT ROOMS TO BE ON DEDICATED CIRCUITS. BASED ON
 SHEET E11 WHICH SHOWS THE LIGHTING IN THE ELEVATOR
 EQUIPMENT ROOM CIRCUITED TO LIGHTING OF OTHER AREAS
 THIS DOES NOT MEET THE CODE SECTION GIVEN.
  
 25) NOTE: THE POWER PLANS ARE INCOMPLETE AS THERE NO
 ELECTRICAL EQUIPMENT OR POWER SHOWN FOR THE POOL
 EQUIPMENT ROOM.
 680,310,240 ETC
 FBC106.1.1, 106.1.2 FOR CLARITY, COORDINATION, AND
 ADDITIONAL INFORMATION NEEDED ON RECORD PLANS.
  
 26) NOTE: PLEASE OBTAIN PHOTO-METRIC LEVELS FOR
 SWIMMING POOL AREA FOR ANY NIGHT TIME SWIMMING PER PALM
 BEACH COUNTY HEALTH DEPARTMENT. ALL PHOTO-METRICS FOR
 ANY SWIMMING AFTER DUSK OR BEFORE DAWN SHALL BE STAMPED
 BY THE HEALTH DEPARTMENT.
 THIS IS NOT A CITY OF WEST PALM BEACH ADOPTED LEVEL OF
 LIGHTING HOWEVER UNLESS PLANS ARE STAMPED PERMIT MAY
 NOT BE ISSUED. PLEASE ALSO KEEP IN MIND IF THERE IS NOT
 GOING TO BE ANY SWIMMING OUTSIDE OF THE DAYLIGHTS HOURS
 PER THE HEALTH DEPARTMENT PLEASE PLACE NOTES ON PLANS
 ACCORDINGLY.
  
 27) NOTE: ANY PROPOSED LIGHTNING PROTECTION SYSTEM IS
 GOING TO BE REQUIRED TO BE UNDER SEPARATE PERMIT.
 HOWEVER PLEASE PLACE NOTES ON PLANS THAT ANY PROPOSED
 LIGHTNING PROTECTION SYSTEM SHALL MEET NFPA-780. (OR
 WORDS TO THAT AFFECT).
 THERE ARE MANY SYSTEMS ON THE MARKET WHICH DO NOT MEET
 ANY ACCEPTABLE STANDARD AND ARE NOT LISTED TO MEET
 NFPA-780.
  
 28) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS
 PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE
 SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE
 LIFE SAFETY PLANS.
 * TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633, FLORIDA STATUTES*
  
 29) NOTE: PLEASE SEE FA PLANS. THERE ARE CODE REFERENCE
 TO ADA REQUIREMENTS WHICH ARE NOT PART OF THE CURRENT
 ADOPTED CHAPTER 11 OF THE FBC. PLEASE SEE FBC
 11-4.28.1, .2 AND .3 FOR REFERENCES AND PLEASE BE SURE
 TO REFLECT THESE CODES.
 PLEASE ALSO SEE THERE ARE SEVERAL REFERENCES TO THE
 2002 NATIONAL ELECTRICAL CODE ON FA SHEETS. PROJECT IS
 CURRENTLY SUBMITTED FOR REVIEW UNDER THE 2005 NFPA-70/
 NEC.
 PLEASE ADJUST NOTES AND REFERENCES ON PLANS.
 PLEASE BE SURE ALL HEIGHTS, LOCATIONS AND LEVELS ARE
 PER SECTIONS NOTED ABOVE.
  
 30) NOTE: PLEASE COORDINATE THE FLOOR PLANS FOR THE
 FIRE PUMP ROOM. PLEASE SEE SHEET FP -10 WHICH CONTAINS
 A DIFFERENT ROOM LAYOUT INCLUDING DOORS WHICH ARE NOT
 THE SAME AS THE REST OF THE PLANS SUBMITTED.
 THERE ARE MANY ASPECTS OF NFPA-20 FOR FIRE PUMP ROOMS
 WHICH ARE REVIEWED INCLUDING FLOOR DRAINAGE REQUIRED.
 COORDINATION OF ALL OF THESE ITEMS IS IMPERATIVE.
 NEC 695, NFPA-20
  
 31) NOTE: PLEASE PROVIDE INFORMATION ON FUEL
 CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP
 AND ALL EMERGENCY SYSTEMS PER 700 AND 701.
 PLEASE BE SURE TO INCLUDE 5% FOR SUMP AND 5% FOR
 EXPANSION.
 PLEASE SEE NFPA-110, NFPA-20 9.6.2.2
  
 32) NOTE: THE FIRE PUMP SERVICE ENTRANCE CONDUCTORS ARE
 ALONG WITH OTHER ELECTRICAL SERVICE ENTRANCE CONDUCTORS
 ARE NOT PERMITTED TO HAVE MORE THAN 8FT OF UNPROTECTED
 CONDUCTORS INSIDE THE BUILDING. 230.70,230.71 PLEASE
 SEE NEC FOR CONDUCTORS TO BE CONSIDERED OUTSIDE THE
 BUILDING BY DEFINITION (SEE SAME SECTION 695.6
 INCLUDING 230.6) FOR THESE REQUIREMENTS.
 THE RISER SHOWS SE CONDUCTORS TO GUTTERS AND THEN TO
 THE MAIN SERVICE EQUIPMENT. MOST CERTAINLY THIS WOULD
 BE MORE THAN 8 FT OF TOTAL LENGTH OF UNPROTECTED
 CONDUCTORS. AS THE NEC DOES NOT PROVIDE THE 8 FT LENGTH
 MANY JURISDICTIONS USED TO CONTAIN LOCAL TECHNICAL
 AMENDMENTS ALLOWING UP TO 8 FT AND SOME NOT ALLOWING
 ANY INSIDE WITHOUT PROTECTION. AS THE TECHNICAL
 AMENDMENTS WENT AWAY IN THE 2001 CODE CYCLE THIS AHJ
 DOES STILL ALLOW UP TO 8 FT HOWEVER NOT ANY GREATER.
 THE NEC IS NO SPECIFIC AND A AHJ COULD PERMIT LESS.
 PLEASE ADJUST RISER WITH THE CONDUCTORS AS SHOWN.
  
 33) NOTE: THE RISER IS SHOWING *EQUIPMENT GROUNDING
 CONDUCTORS* BEFORE THE FIRST MEANS OF SERVICE
 DISCONNECT FOR ALL PROPOSED SERVICES INCLUDING THE FIRE
 PUMP WHICH IS NOT PERMITTED. AS THE CODE REQUIRES THE
 NEUTRAL (GROUNDED) CONDUCTOR TO BE BONDED AT THE FIRST
 MEANS OF DISCONNECT IF AN EQUIPMENT GROUND IS INSTALLED
 THIS WOULD PARALLEL THE NEUTRAL. THIS WOULD CREATE
 OBJECTIONABLE CURRENTS PER 250.6 AND IS NOT PERMITTED.
 PLEASE REMOVE AND ADJUST RISER.
 250.6,250.24 ETC.
  
 34) NOTE: EMERGENCY EQUIPMENT MAINS AND FIRE PUMP MAINS
 NEED TO BE LABELED AS SUCH. FOR EXAMPLE: THE FIRE PUMP
 AS SHOWN IS A SEPARATE SERVICE FROM FPL AS REQUIRED.
 THE RISER NOTES THIS IS MAIN FOUR OF FIVE HOWEVER THIS
 IS THE FIRE PUMP MAIN.
 A SECOND EXAMPLE IS THE EMERGENCY MAIN AS SHOWN ON
 RISER. THIS IS NOTED AS MAIN 3 OF 3 YET THIS IS
 ACTUALLY THE EMERGENCY MAIN ONE OF ONE.
 EACH MAIN IN EACH PERMITTED SERVICE NEEDS TO BE
 LABELED.
 230.2, 701.9,700.8 AS NOTED ABOVE.
 PLEASE ADJUST LABELING.
  
 35) NOTE: RISER NOTES THE FIRE PUMP CONTROLLER AS
 SERVICE ENTRANCE RATE HOWEVER NO INDICATE OF THIS UNIT
 CONTAINING THE BUILT IN TRANSFER SWITCH IS NOTED.
 PLEASE SEE NOTES ABOVE AND EXPANDED ON THE FIRE PUMP
 CONTROLLER INFORMATION.
 695.4
 PLEASE BE SURE TO SEE NOTES ON TRANSFER SWITCHES.
  
 36) NOTE: PLEASE SEE 230.95,240.13 ETC. THE CODE
 REQUIRES GROUND FAULT PROTECTION FOR ANY SYSTEMS 150V
 OR MORE TO GROUND AND 100AMPS OR OVER. THE RISER
 INDICATES GFI PROTECTION WHICH IS CLASS A PROTECTION
 FOR PERSONNEL. THIS IS NOT THE SAME KING OF PROTECTION
 WHICH IS GFP WHICH IS WHAT IS REQUIRED IN THE SECTIONS
 GIVEN. PLEASE PROVIDE INFORMATION ON THE TRANSFER
 SWITCHES AND PLEASE SEE THE FOLLOWING COMMENT WHICH MAY
 AFFECT THE USE OF 3-POLE OR 4-POLE TRANSFER SWITCHES.
  
 37) NOTE: PLEASE SEE NEC
 ,250.20,250.30,250.66,240.13.230.95, 700.7D AND 700.26.
 GFP PROTECTION IS REQUIRED ON THE NORMAL SIDE OF THE
 SERVICE HOWEVER ONLY GROUND FAULT SENSING IS REQUIRED
 TO BE ON THE SECONDARY SIDE. THE CODE ACTUALLY DOES NOT
 REQUIRE NOR DOES IT RECOMMEND GFP ON THE EMERGENCY
 EQUIPMENT.
 PLEASE SEVERAL WHITE PAPERS WHICH HAVE NOTES ON THE
 ABOVE SITUATION WHEN GROUND FAULT PROTECTION IS
 TRIGGERED BY THE CODE. MANY OF THESE IN FACT NOTE A
 COORDINATION LOSS OF EQUIPMENT WHEN THE USE OF 3-POLE
 ATS SWITCHES IS USED.
 PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL
 CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING
 CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND
 THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY
 GROUNDED TO ACHIEVE GROUND-FAULT SENSING.
 PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM *ASCO*
 WHITE PAPERS:
  
 WHERE GROUND FAULT PROTECTION IS TRIGGERED BY THE CODE
 AND AN ALTERNATE POWER SUPPLY IS INCLUDED, SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT SHOWN ABOVE
 ILLUSTRATES SUCH A CIRCUMSTANCE. THE SERVICE IS LARGER
 THAN 1,000 AMPS. CONSEQUENTLY, GROUND FAULT PROTECTION
 IS REQUIRED AT THE MAIN SERVICE DISCONNECT AT A
 MINIMUM. IF IT IS INSTALLED THERE AND THE GENERATOR
 NEUTRAL GROUNDING WAS THROUGH A SOLID CONNECTION TO THE
 MAIN SERVICE NEUTRAL, A GROUND FAULT WHEN THE GENERATOR
 IS FEEDING THE LOAD WILL CAUSE THE MAIN SERVICE
 DISCONNECT TO OPEN. THIS WILL NOT DISCONNECT THE ARCING
 FAULT FROM THE GENERATOR. COORDINATION IS THUS LOST."
  
 THIS HAS BEEN READ AND NOTED BY OTHER MANUFACTURES.
 PLEASE OBTAIN AND VERIFY COORDINATION FROM THE PROPOSED
 MANUFACTURE AND ADJUST PLANS.
 AS THE PLANS DO NOT INDICATE THE USE OF 3 OR 4 POLE
 DEVICES AT THIS TIME FINAL COMMENT CAN NOT BE MADE.
 PLEASE ALSO SEE GENERATOR GROUNDING DETAIL MAYBE BE
 REQUIRED TO BE REVISED.
  
 38) NOTE: PLEASE SEE 700.9 OF THE NEC ALONG WITH
 EXHIBITS IN 700.1 ETC.
 THE RISER INDICATES EMERGENCY/LIFE SAFETY SYSTEMS BEING
 WIRED IN WITH LEGALLY REQUIRED SYSTEMS WHICH ARE NOT
 PERMITTED. PLEASE ADJUST RISER. PLEASE ALSO KNOW THERE
 MAY BE NEW COMMENTS AS SEVERAL ITEMS WILL NEED TO BE
 PROVIDED.
 *** IMPORTANT**
 PLEASE SEE NEC 700 AND 701 DEFINITIONS AND OTHER
 ADOPTED CODES AS NOT ALL SYSTEMS, FEEDERS, BRANCH
 CIRCUITS ETC AS SHOWN ON RISER AND PANEL SCHEDULES ARE
 LIFE SAFETY/EMERGENCY SYSTEMS AS SOME ARE CONSIDERED
 LEGALLY REQUIRED. THIS WOULD REQUIRE SEPARATION.
 THIS CAN BE GONE OVER.
 AN EXAMPLE IS THE ELEVATOR IS THIS OCCUPANCY IS
 CONSIDERED LEGALLY REQUIRE AND NOT LIFE SAFETY. THIS IS
 A BACK UP REQUIRED TO COME ON IN 60SECONDS INSTEAD OF
 THE REQUIRED 10 SECONDS LISTED IN 700 SYSTEMS.
 AN ELEVATOR IN A HOSPITAL WOULD BE DIFFERENT AND WOULD
 BE CONSIDERED LIFE SAFETY.
 THIS COMMENT WILL ALL TIE INTO THE COMMENTS ABOVE WITH
 RESPECT TO THE LIGHTING AND BACK UP OF THE EGRESS
 LIGHTS. IF ALL MEET THE BATTERY BACK UP THEN THIS WOULD
 ONLY BE ONE LEGALLY REQUIRED (701) SYSTEM. THIS WOULD
 CHANGE MANY ASPECTS OF THE DESIGN INCLUDING NEXT
 COMMENT.
 PLEASE BE AWARE OF ANY PHONE SYSTEMS BEING PROPOSED
 WHICH WOULD BE REQUIRED TO CONTAIN UPS FOR BACK AS
 EMERGENCY COMMUNICATIONS IS REQUIRED TO CONTAIN BACK UP
 WHICH MAY THEN BE PART OF THE GENERATOR WHICH IS 10, 60
 SECOND BACK UP. NO DELAY IN PHONE SYSTEM IS PERMITTED.
  
 39) NOTE: PLEASE SUBMIT A COMPLETE COORDINATION STUDY
 FOR ALL LIFE SAFETY/EMERGENCY SERVICE EQUIPMENT AND
 BREAKERS. PLEASE SEE 240.12, 700.27 AND 701.18. THIS
 REQUIRES ALL BREAKERS AND EQUIPMENT TO BE COORDINATE.
  
 40) NOTE: PLEASE PROVIDE NOTE FOR SUPPORT OF VERTICAL
 CONDUCTORS PER 300.19.
  
 41) NOTE: PLEASE INDICATE AIC RATING FOR ALL SERVICE
 EQUIPMENT INCLUDING RATINGS OF ALL PANELS. 110.9. COULD
 NOT LOCATE ALL REQUIRED.
  
 42) NOTE: EVEN AS THE SWIMMING POOL IS UNDER A SEPARATE
 PERMIT PLEASE SEE 2005 NEC WHICH REQUIRES AN EQUAL
 POTENTIAL BOND.
 PLEASE PROVIDE DETAIL ON PLANS AS THIS MAY BE PART OF
 THE STRUCTURAL ELEMENTS OF THE PROPOSED STRUCTURE AND
 POOL AREA.
  
 43) NOTE: PLEASE PROVIDE THROUGH WALL AND FLOORS
 PENETRATION DETAILS PER 300.21. THE SPREAD OF FIRE IS
 REQUIRED TO BE CONTAINED PER SEVERAL ADOPTED REFERENCES
 AND STANDARDS.
 PLEASE SEE THE HANDBOOK COMMENTARY WHICH PROVIDES THE
 REFERENCES SUCH AS NFPA-221,251, ASTM AND ANSI
 REQUIREMENTS.
  
 44) NOTE: PLEASE COORDINATE ALL ITEMS ON RISER AND
 PANEL SCHEDULES. PLEASE SUBMIT COMPLETE PLANS FOR FULL
 REVIEW. THERE ARE SEVERAL ASPECTS OF RISER AND PANELS
 WHICH ARE NOT COMPLETED. AN EXAMPLE LIST WILL BE GIVEN
 OF SOME OF THESE ITEMS. THIS IS NOT A COMPLETE LIST. AS
 THERE ARE MANY ITEMS NOT YET COMPLETE OR SUBMITTED
 THESE CAN SIMPLY NOT BE REVIEWED.
  
 A) EXAMPLE:
  
 B) EXAMPLE: RISER INDICATES MDPLEM AS A MCB( MAIN
 CIRCUIT BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS
 THIS AS MLO (MAIN LUG ONLY).
  
 C) EXAMPLE: RISER INDICATES MDPHEM AS A MCB( MAIN
 CIRCUIT BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS
 THIS AS MLO (MAIN LUG ONLY).
  
 D) EXAMPLE: RISER INDICATES MDPL AS A MCB ( MAIN
 CIRCUIT BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS
 THIS AS MLO (MAIN LUG ONLY).
  
 E) EXAMPLE: RISER INDICATES MDPH AS A MCB( MAIN CIRCUIT
 BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS THIS AS MLO
 (MAIN LUG ONLY).
  
 45) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE KEEP IN MIND THIS NEEDS TO SHOW THE ENTIRE FEED
 THRU FROM THE SOURCE TO THE END USE. THE CODE REQUIRES
 A MAXIMUM ON THE ENTIRE RUN NOT FROM A PANEL TO THE END
 DEVICE ON A CIRCUIT. THIS MAY GREATLY AFFECT FEEDERS OR
 BRANCH CIRCUIT CONDUCTORS.
 PLEASE SEE 13-413.1ABC.1.
  
 46) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER
 13-413.ABC.2, .2.1 AND .2.2. THE WORDING AS STATED IN
 THE FBC IS ACCEPTABLE. THIS WAS CONFIRMED WITH FLORIDA
 BUILDING COMMISSION/DCA.
  
 47) NOTE: PLEASE INCLUDE EFFICIENCY RATINGS OF MOTORS
 WHICH SHALL MEET 13-414.1.ABC.1.1.
  
 48) NOTE: PLEASE INCLUDE LOAD CALCULATIONS FOR ALL
 PANELS AND SERVICES. SOME INFORMATION IS SHOWN ON PLANS
 HOWEVER MOST IS NOT COMPLETE AT THIS TIME.
 PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125%.
 230.42,215.5.
 220.
 P
 PLEASE SEE SECTIONS SUCH AS 220.12,220.14,220.42,
 220.44 AND OTHERS SUCH AS 220.43 FOR TRACK LIGHTING.
 THERE ARE SEVERAL ASPECTS OF THE LOAD CALCULATIONS AND
 HOW LOADS WERE DERIVED WHICH NEED TO BE SHOWN
 FBC 106.1.1, 106.1.2, 106.3.5.1.2 FOR ADDITIONAL
 INFORMATION, CLARITY AND COORDINATION.
  
 49) NOTE: PLEASE COMPLETE ALL PANELS WITH THE CONDUCTOR
 SIZES PER 310.16, 240.4 ETC
 MANY ARE NOTED AND SHOWN HOWEVER DUE TO SOME PANELS NOT
 BEING COMPLETE AT THIS TIME THIS NOTE REMAINS.
  
 50) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND
 PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR
 EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN FROM
 COMMENTARY IN THE CODE WHICH STATES THE USE OF *GEN LT*
 ETC IS NOT ACCEPTABLE. THIS INCLUDES ALL SUITES/ROOMS.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 51) NOTE: THE RISER LENDS TO EACH PANEL FOR UNITS AS
 FEED THROUGH HOWEVER THE PANEL SCHEDULES DO NOT
 INDICATE ANY FEED THRU NOTES, LUGS ETC.
 240, 215 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 52) NOTE: PLEASE SEE 210.12 FOR REQUIRED ARC FAULT
 PROTECTION FOR UNIT OUTLETS. THIS INCLUDES PROTECTIONS
 OF ALL OUTLETS INCLUDING LIGHTS, FANS AND RECEPTACLES.
 ** PLEASE BE AWARE OF ANY LIGHTING CONTROL SYSTEMS FOR
 DESIGN WHICH MAY BE AFFECTED BY THE REQUIREMENT OF AFCI
 PROTECTION.
  
 53) NOTE: PLEASE SEE 210.60 OF THE NEC. WHEN A GUEST
 ROOM/SUITE FALLS UNDER THE DEFINITION WITH PERMANENT
 MEANS OF COOKING ALL THE REQUIREMENTS OF 210.52 MUST BE
 MET.
 THIS INCLUDES MANY OF FOLLOWING WHICH WILL GREATLY
 AFFECT THE PLANS, WIRING, THE LOADS, THE PANEL
 SCHEDULES ETC AS SUBMITTED. THE PLANS AT THIS DO NOT
 MEET THE CODE WITH RESPECT TO MANY ITEMS. PLEASE SEE
 THE FOLLOWING EXAMPLES:
  
 A) PLEASE SEE 210.52C1-5 FOR RECEPTACLES ALONG KITCHEN
 COUNTER SPACES WHICH SHALL MEET SPACING.
 THIS INCLUDES PENINSULAR AREAS.
 THIS ALSO INCLUDES OTHER SPACING AS THERE ARE UNITS
 SUCH AS UNIT *B* WHICH SHOWS MORE THAN FOUR FT BETWEEN
 COUNTER TOP RECEPTACLES WHICH IS NOT PERMITTED.
 THERE ARE OTHER UNITS ALSO NOT JUST UNIT *B*. SEE UNIT
 *S* AS AN EXAMPLE WHICH SHOWS COUNTER SPACE OF 12
 INCHES OR MORE YET NO RECEPTACLE IS SHOWN.
 GFCI PROTECTION PER 210.8A6
  
 B) PLEASE SEE 210.52B1 FOR THE REQUIRED CIRCUITING
 WHICH REQUIRES MINIMUM OF TWO SMALL APPLIANCE CIRCUITS.
 EACH CIRCUIT IS REQUIRED TO BE FIGURED PER 220.53 WHICH
 REQUIRES 1500VA PER EACH.
 SEE ANY AREAS SUCH AS DINING, BREAKFAST AREAS OF THE
 LIKE WHICH WILL BE AFFECTED. THE PLANS DO NOT INDICATE
 THE DINING, BREAKFAST OR EATING AREA OF THE LIKE. THE
 PLANS DO SHOW THE RECEPTACLES IN THE AREAS WHICH WOULD
 BE CONSIDERED ONE OF THESE AS ON THE GENERAL LIGHTING
 AND RECEPTACLES CIRCUIT WHICH IS NOT PERMITTED. AN AREA
 NEEDS TO BE DESIGNATED AND RECEPTACLE WIRING NEEDS TO
 BE ADJUSTED.
  
 C) PLANS DO NOT SHOW ANY RECEPTACLE FOR DISHWASHER.
 PLEASE BE SURE TO SEE 210.4 FOR ANY DEVICES SUCH A
 SINGLE YOKE BEING FED FROM A TWO BREAKERS WHICH SHALL
 MEET DISCONNECTING REQUIREMENTS.
  
 D) NOTE: PLEASE SEE 210.52D, 210.11C3 AS THE BATHROOM
 WIRING SHALL NOT FEED ANY OTHER ROOMS, DEVICES, OUTLETS
 ETC. THIS NEEDS TO BE SPECIFIED AS THE DEDICATED
 BATHROOM CIRCUIT AS NOTED ABOVE PER 408.4.
  
 54) NOTE: PLEASE SEE FBC 1019.1.25 AS NO OTHER SYSTEMS
 ARE PERMITTED IN THE VERTICAL EGRESS STAIRS WITH THE
 EXCEPTION OF THOSE SYSTEMS REQUIRED TO BE PART OF THE
 STAIRS. SHEET E-16 INDICATES A SWITCH FOR A LIGHT
 FIXTURE ON THE ROOF TOP. THE SWITCH IN THIS LOCATION IS
 NOT PERMITTED.
 PLEASE ALSO PROVIDE LIGHTING PER EGRESS OF ROOF AREAS
 INCLUDING MEETING LIGHTING CONTROLS PER FBC
 13-415.1.ABC.1.4.
  
 55) NOTE: PLEASE BE SURE TO SHOW/IDENTIFY THE REQUIRED
 SMOKE ALARMS, DETECTORS, AND CARBON MONOXIDE DETECTORS
 ON UNIT ROOM LAYOUT FOR ELECTRICAL PLANS AS THE FIRE
 ALARM WILL BE UNDER SEPARATE PERMIT.
  
 56) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCE FOR
 ELECTRICAL PANELS. SOME SHOW FURNITURE IN FRONT OF
 PANELS. LOCATION NEEDS TO MEET 110.26.
 PLEASE ALSO PROVIDE A LAYOUT OF ALL ELECTRICAL, FIRE
 PUMP ROOMS ETC SO COMPLIANCE FOR MINIMUM CLEARANCES
 AREA REVIEWED.
 PLEASE SEE NOTES ABOVE WITH RESPECT TO PERMITTED
 SYSTEMS SUCH AS 700 AND 701 IN THE SAME LOCATIONS.
 NFPA-110 SECTION 7.2.2 AS EPSS EQUIPMENT SHALL NOT BE
 INSTALLED IN THE SAME ROOM WHERE THE NORMAL ELECTRICAL
 SERVICE EQUIPMENT IS INSTALLED. THE CODE; SECTION
 7.2.2.1 DOES PERMIT TRANSFER SWITCHES TO BE INSTALLED
 IN THE NORMAL ELECTRICAL SERVICE ROOM ONLY WHERE TWICE
 THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF NFPA 70,
 NATIONAL ELECTRICAL CODE, EXISTS BETWEEN EQUIPMENT
 ENCLOSURES.
 EMERGENCY EQUIPMENT ROOMS WITH THE 2HR RATING AS
 REQUIRED PER 7.2.1.1 PROVIDES THE SAFE LOCATION SO ANY
 FIRE IN THE MAIN SWITCH GEAR BY AN EXPLOSION ETC WOULD
 NOT DAMAGE THE LIFE SAFETY OR LEGALLY REQUIRED SYSTEMS.
 PLEASE SEE LOCATION WHERE THE GENERATOR IS RUNNING AT
 FULL SPEED CAN ALSO BE DISTRACTING FOR ANY EMERGENCY
 PERSONNEL WHEN ATTEMPTING TO SHUT DOWN ANY SPECIFIC
 SYSTEMS. MEETING THE SECTION ABOVE FOR SEPARATION AND
 CLEARANCE REQUIREMENTS NEEDS TO BE ADDRESSED.
 LOCATIONS OF ALL ELECTRICAL EQUIPMENT NEED TO BE
 VERIFIED.
  
 PLEASE COMPLETE PLANS WITH ALL FURNITURE AS PROPOSED.
  
 57) NOTE: PLEASE SEE 210.8B3,4 AND 5 OF THE 2005 NEC
 WHICH REQUIRES ALL RECEPTACLES OUTSIDE EVEN IF FOR
 DEDICATE EQUIPMENT SUCH AS DRINKING FOUNTAINS TO BE
 GFI/ GFI PROTECTED. PLEASE SEE FOUNTAIN ON ROOF TOP
 PLANS WHICH NEEDS TO MEET THIS.
 CIR 567L-13
  
 58) NOTE: PLEASE SUBMIT A COMPLETE FIXTURE LEGEND FOR
 ALL SPECIFIC FIXTURES. THERE ARE SEVERAL ITEMS FOR FBC
 CHAPTER 13 AS NOTED ABOVE ALONG WITH OTHER ITEMS SUCH
 AS POOL AREA LIGHTS WHICH NEED TO BE REVIEWED.
 PLEASE SEE 411.4B, 680.22 AND 680.23 WHICH WILL GREATLY
 AFFECT THE REVIEW FOR TYPES OF FIXTURES PERMITTED.
 PLEASE PLACE NOTE ON LIGHTING PLANS FOR POOL AREA WHICH
 DOES NOT PERMIT ANY LOW VOLTAGE LIGHTING SYSTEMS WITHIN
 10FT OF THE WATERS EDGE.
 FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION, CLARITY
 AND COORDINATION.
  
 59) NOTE: PLEASE KEEP IN MIND TO INDICATE THE REQUIRED
 WIND LOAD RATINGS FOR ANY ROOF-TOP OR OUTSIDE POLE
 LIGHT PER SECTION 1609 OF THE FBC. THE CALCULATIONS
 WHICH NEED TO BE SUBMITTED WILL NEED TO SHOW THE EPA
 (EFFECTIVE PROJECTED AREA) OF ANY PROPOSED LIGHT
 FIXTURE. THE CALCULATIONS WILL BE PART OF THE
 STRUCTURAL REVIEW ONCE SHOWN AND SUBMITTED.
 ELECTRICAL PLANS MUST SHOW MINIMUM WIND LOAD DESIGNS.
  
 60) NOTE: IF A GUTTER IS STILL GOING TO BE PART OF THE
 FUTURE SERVICE PROPOSED DESIGN; PLEASE INCLUDE
 DIMENSIONS. NEC 366
 THIS INCLUDES ANY OTHER PROPOSED GUTTERS IF THEY ARE
 STILL PART OF THE DESIGN.
 PLEASE KEEP IN MIND PREVIOUS COMMENTS ABOVE WITH
 RESPECT TO NO MORE THAN 8FT OF TOTAL LENGTH OF
 UNPROTECTED CONDUCTORS.
  
 61) NOTE: THE RISER CONTAINS NOTES AND DETAIL FOR THE
 GROUNDING ELECTRODE SYSTEM HOWEVER THIS SEEMS TO BE
 MISSING THE REQUIRED FOUNDATION/FOOTER STEEL PER
 250.50. THE NOTE ON RISER MENTIONS *BUILDING STEEL*
 HOWEVER THIS BY DEFINITION THIS WOULD BE PART OF THE
 STRUCTURAL STEEL FOR THE BUILDING. THE
 FOUNDATION/FOOTER STEEL WOULD BE AT THE LOWEST POINT OF
 THE BOTTOM OF SUCH FOUNDATION.
 THIS MAY HAVE BEEN WHAT WAS MEANT BY NOTE HOWEVER THERE
 MAY BE SOME BUILDING STEEL EVEN IF POST TENSION CABLES
 SEEMS TO BE THE CONSTRUCTION SYSTEM.
 PLEASE ADJUST NOTE TO ALLEVIATE ANY CONFUSION.
  
 62) NOTE: PLEASE SEE SHEET E1 WHICH INDICATES A PANEL
 FP, YET THIS IS NOT ON RISER AND NO PANEL SCHEDULE
 COULD BE LOCATED.
 IF THIS IS PART OF THE FIRE PUMP, OR CONTROLLER PLEASE
 SEE NOTES ABOVE WITH RESPECT TO MORE INFORMATION
 NEEDED.
 695,408,215.5 ETC
  
 63) NOTE: PLEASE PLACE NOTE ON PLANS FOR COLOR CODING
 FOR 277/480V SYSTEMS AS FOLLOWS:
 BROWN, PURPLED, AND YELLOW.
 PLEASE KNOW AS THE NEC DOES NOT PROVIDE COLOR CODING OF
 ALL SYSTEMS AND ORANGE IS FOR OPEN DELTA HIGH LEG
 SYSTEMS THE CITY OF WEST PALM BEACH USED TO HAVE
 TECHNICAL AMENDMENTS FOR THIS ITEM. THE LOCAL TECHNICAL
 AMENDMENTS ARE NO LONGER IN EFFECT HOWEVER IN KEEPING
 WITH THE UNIFORMITY WITH ALL OTHER BUILDING SYSTEMS
 WITHIN THIS JURISDICTION AND IN THE INTEREST OF LIFE
 SAFETY AND FIRE HAZARD THE ABOVE COLOR CODING IS
 REQUIRED PER 90.4.
  
 64) NOTE: PLEASE INDICATE THE REQUIRED SIGN CIRCUIT PER
 600.5.
  
 65) NOTE: PLEASE CHECK WITH THE LOCAL FAA AUTHORITY FOR
 REQUIREMENTS OF ANY AIRCRAFT WARNING LIGHTS WHICH MAY
 BE REQUIRED. PLEASE CHECK WITH THE FAA WEBSITE OR
 CONTACT THE LOCAL AIRPORT AUTHORITY.
 THIS WILL AFFECT ELECTRICAL ON PLANS IF SO REQUIRED.
 ( OTHER HIGH-RISE BUILDINGS IN AREA DO CONTAIN
 LIGHTING).
  
  
  
 ** PLEASE BE SURE TO SUBMIT THE ABOVE INFORMATION AS
 WELL AS INFORMATION NOT YET SUBMITTED.
 PLEASE CALL TO GO OVER ANY COMMENTS WHICH MAY NOT BE
 CLEAR IN ANY MANNER. CONTACT INFORMATION IS BELOW. IF
 VOICE MAIL IS CONTACTED PLEASE BE SURE TO LISTEN TO
 MESSAGE AS I MAY NOT BE IN THE OFFICE.
 PLEASE LEAVE A MESSAGE WHEN CALLING AND THE CALL WILL
 BE RETURNED AS SOON AS POSSIBLE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2009-01-12 Cont ID  
Sent By   Date 2009-01-12 Time   Rev Time 1.00
Received By efabian Date 2009-01-12 Time 11:41 Sent To  
Notes
2009-01-12 11:16:30PLEASE UPDATE TRASH COLLECTION NOTE ON SHEET C-5 TO
 REFLECT COLLECTION BY THE CITY'S SANITATION DEPARTMENT
 USING (2) 8 CU./YDS. DUMPSTERS WHICH SHALL BE ROLLED
 OUT FOR SERVICE BY WAY OF A STAGING AREA IN THE ALLEY.
  
 EROSION CONTROL & LAND STABILIZATION BOND SHALL BE
 REQUIRED AND POSTED TO THE ENGINEERING SERVICES
 DIVISION PRIOR TO COMMENCEMENT OF WORK ON SITE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-01-11 Cont ID  
Sent By mawillia Date 2009-01-11 Time 14:30 Rev Time 0.00
Received By mawillia Date 2009-01-10 Time 16:15 Sent To  
Notes
2009-01-10 17:16:12*****DENIED*****
  
 01. THE STRUCTURE WILL BE CONSIDERED A HIGH-RISE AND
 SHALL COMPLY WITH THE FLORIDA BUILDING CODE AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 02. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 03. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04. THE PROJECT SITE ADDRESS SHALL BE IN THE TILTLE
 BLOCK OF EACH SUBMITTED PLAN SHEET, NONE SHOWN ON THE
 CIVIL AND LANDSCAPE SHEETS.
  
 05. IN ALL BUILDINGS OVER ONE STORY IN HEIGHT, AT LEAST
 ONE STAIRWAY SHALL BE PROVIDED IN AN USABLE CONDITION
 AT ALL TIMES.
  
 06. A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT. THE STANDPIPES SHALL BE PROVIDED WITH
 CONSPICUOUSLY MARKED AND READILY ACCESSIBLE FIRE
 DEPARTMENT CONNECTIONS ON THE OUTSIDE OF THE BUILDING
 AT THE STREET LEVEL AND HAVE AT LEAST ONE STANDARD HOSE
 OUTLET AT EACH FLOOR.
  
 07. WHERE/IF UNDERGROUND WATER MAINS AND FIRE HYDRANTS
 ARE TO BE PROVIDED, THEY SHALL BE INSTALLED,
 COMPLETEED, AND IN SERVICE PRIOR TO CONSTRUCTION WORK.
  
 08. THERE SHALL BE NO DELAY IN THE INSTALLATION OF FIRE
 PROTECTION EQUI;MENT.
  
 09. THE INSTALLATION OF THE SPRINKLER SYSTEM SHALL BE
 PLACED IN SERVICE AS SOON AS PRACTICABLE.
  
 10. THE PROJECT SITE ADDRESS SHALL BE TEMPORILY POSTED
 PRIOR TO, AND DURING CONSTRUCTION, OR UNTIL SUCH TIME
 THAT THE PERMANENT NUMERICAL ADDRESS IS DIPLAYED ON THE
 EXTERIOR ELEVATION WHICH FRONTS THE BUILDING.
  
 11. LANDSCAPE SHALL NOT INTERFERE OR HINDER
 ACCESSIBILITY TO FIRE HYDRANTS, FIRE DEPARTMENT
 CONNECTIONS, AND (OR) ANY OTHER LIFE/FIRE SAFETY
 SYSTEMS.
  
 12. ON THE LIFE SAFETY SHEETS, NOTE #13, AMEND TO
 REFLECT 2A:10BC RATED FIRE EXTINGUISHERS ARE TO BE USED
 AS PER LOCAL CODES.
  
 13. PLEASE EXPLAIN WHY THERE IS NO LIFE SAFETY PLAN FOR
 FLOORS ABOVE THE 5TH FLOOR.
  
 14. ON THE APPROPIATE EXTERIOR ELEVATION SHEET,
 SHOW/DISPLAY THE NUMERICAL ADDRESS FOR THE SITE. AS PER
 WEST PALM BEACH CODE, THE ADDRESS NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH/STROKE.
  
 15. SINCE THE BUILDING WILL BE EQUIPPED WITH FIRE ALARM
 AND FIRE SPRINKLER SYSTEMS, A ACCESS BOX (KNOX) FOR THE
 PREMISES SHALL BE REQUIRED. SHOW/DISPLAY THE LOCATION
 OF THE KNOX BOX ON THE APPROPIATE EXTERIOR ELEVATION
 SHEET. FOR KNOX APPLICATIONS CONTACT WEST PALM BEACH
 FIRE PREVENTION AT 561-804-4724.
  
 16. TRASH CHUTE SHALL COMPLY WITH NFPA 82. ADD COMMENT
 TO DRAWING A9.02 SHEET.
  
 17. STAIRWELL IDENTIFICATION SIGNS REQUIRED. THESE
 SIGNS SHALL IDENTIFY STAIR NUMBER, FLOOR LEVEL,
 TERMINUS TOP AND BOTTOM.
  
 18. PROVIDE PRESCRIPTIVE STRENGHTS FOR STAIRS'
 HANDRAILS/GUARDRAILS.
  
 19. IN REFERENCE TO THE WIRE SECURITY PARTITION WITH
 DOOR (LEVEL 5, DOOR #45) SHOWN ON SHEET A10.02, CONTACT
 BATTALLION CHIEF (FIRE MARSHAL) MIKE CARSILLO AT
 561-804-4724 FOR FEASIBILITY OF THIS ARRANGEMENT.
  
 20. ON SHEET A11.01, EXPLAIN CRITERIA FOR THE LABELED
 RATING FOR SOME STORAGE DOORS WHILE OTHERS ARE NOT;
 LIST LABELED DOOR FIRE RATING FOR THE FIRE COMMAND
 CENTER - 126, DOMESTIC WATER PUMP - 143, STORAGE ROOM
 -144, ELEVATOR MACHINE ROOM - 205, MECHANICAL ROOM
 (302), POOL EQUIPMENT - 402, BOILER ROOM - 403.
 ELECTRICAL CLOSET - 524, ELECTRICAL CLOSET - 624.
  
 21. DOORS AND WINDOWS REQUIRED TO BE FIRE RATED SHALL
 COMPLY WITH NFPA 80.
  
 22. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE
 SELF-CLOSING AND SELF-LATCHING. ADD COMMENT TO DOOR
 NOTES - SHEET A11.01 - UNDER THE GUEST UNITS SECTION.
  
 23. THERE ARE TWO STAIR #2 SHOWN ON A15.03 & A15.07
 SHEETS. PLEASE EXPLAIN.
  
 24. ON THE LIFE SAFETY SHEETS, SHOW EXIT LIGHTS
 CORRELATING TO THE ELECTRICAL LIGHTING SHEETS.
  
 25. ON SHEET LS1 IN THE EXIT DISCHARGE CALCULATIONS FOR
 THE LOBBY ZONE, THERE ARE TWO EXIT #2'S. AMEND TO
 REFLECT 3 EXITS AS SHOWN ON THE DRAWING. SHEET LS2 THRU
 LS5, CALCULATIONS SHOULD BE FOR STAIR 2 & 3, NOT 1 & 2.
  
 26. IS ANY EMERGENCY LIGHTING (SEE SHEET E10) PROPOSED
 FOR STAIR #1?
  
 27. A FIRE ALARM SYSTEM USING AN APPROVED, EMERGENCY
 VOICE / ALARM COMMUNICATION SYSTEM SHALL BE INSTALLED
 IN ACCORDANCE WITH NFPA 72.
  
 28. INDICATE WHAT MESSAGE IS PLANNED FOR THE FIRE ALARM
 VOICE FEATURE OF THE FIRE ALARM SYSTEM.
  
 29. ON SHEET FA10, FIRE ALARM SEQUENCE OF OPERATIONS -
 D, AMEND TO REFLECT THAT SMOKE DUCT DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 30. AN APPROVED SINGLE-STATION SMOKE ALARM SHALL BE
 INSTALLED IN EVERY GUEST ROOM AND EVERY LIVING AREA AND
 SLEEPING ROOM WITHIN A GUEST SUITE. AMEND TO REFLECT AS
 SUCH ON THE APPROPIATE FA SHEETS, INCLUDING THE FIRE
 ALARM LEGEND (FA9) SHEET. BE ADVISED THAT SMOKE
 DETECTORS (SD) ARE TIED INTO THE BUILDING'S FIRE ALARM
 SYSTEM WHEREAS SMOKE ALARMS (SA) ALERT THE OCCUPANT(S)
 OF THE DWELLING UNIT ONLY.
  
 31. THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH NFPA 13; LISTED QUICK-RESPONSE OR
 RESIDENTIAL SPRINKLERS SHALL BE USED THROUGHOUT GUEST
 ROOMS AND GUEST ROOM SUITES.
  
 32. ALL AREAS OF THE BUILDING TO BE SPRINKLERED. WHY IS
 THERE NO SPRINKLER COVERAGE IN STORAGE ROOMS 125 & 125
 FOR EXAMPLE.
  
 33. KNOX LOCKING CAPS WILL REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS. INCLUDE IN SCHEMATIC 3/FP9 ON
 SHEET FP9 DRAWING. FOR APPLICATIONS CONTACT WEST PALM
 BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
  
 34. IN ADDITION TO ELECTRONIC SWITCHES, CHAIN AND LOCK
 WILL BE REQUIRED ON THE DOUBLE DETECTOR CHECK VALVE
 ASSEMBLY. INCLUDE/SHOW IN SCHEMATIC 4/FP10 ON SHEET
 FP10 DRAWING.
  
 35. A FIRE SPRINKLER PIPE INSPECTION (CODE:603) SHALL
 BE REQUIRED AS PER WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT. REPLACE NOTE ON SHEET FP9 , PIPE
 AND FITTING SPECIFICATION (D) WHICH REFERENCES THE CITY
 OF COCONUT CREEK FLORIDA FIRE RESCUE.
  
 36. EMERGENCY GENERATORS PROVIDING POWER TO EMERGENCY
 LIGHTING SHALL BE INSTALLED, TESTED, AND MAINTAINED IN
 ACCORDANCE WITH NFPA 110.
  
 37. REQUIREMENTS FOR STANDBY POWER SHALL BE AS
 SPECIFIED IN 11.8.4.2 OF NFPA 101, LIFE SAFETY CODE.
  
 38. THE CENTRAL CONTROL STATION (FIRE COMMAND
 CENTER/ROOM) SHALL CONTAIN THE FOLLOWING AS LISTED IN
 11.8.5 OF NFPA 101, LIFE SAFETY CODE.
  
 39. ELEVATORS SHALL BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF ASME A17.1, SAFETY CODE FOR ELEVATORS
 AND ESCALATORS. ALL NEW ELEVATORS SHALL CONFORM TO THE
 FIREFIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS.
  
 40. IN HIGH-RISE BUILDINGS, ONE ELEVATOR SHALL BE
 PROVIDED WITH A POWER SUPPLY AND SHALL BE AVAILABLE FOR
 USE BY THE FIRE DEPARTMENT IN CASE OF EMERGENCY AND/OR
 PARAMEDICAL USE.
  
 41. A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR
 ARRANGEMENT, EXIT LOCATIONS, AND ROOM IDENTIFICATION
 SHALL BE POSTED IN AN AHJ APPROVED LOCATION, OR
 IMMEDIATELY ADJACENT TO, EVERY GUEST ROOM DOOR IN
 HOTELS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE THE COMMENTS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-01-13 Cont ID  
Sent By rregueir Date 2009-01-13 Time 19:57 Rev Time 0.00
Received By rregueir Date 2008-12-28 Time 17:42 Sent To PC
Notes
2009-01-13 20:02:16REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE COORDINATE THE ARCHITECTURAL AND LIFE SAFETY
 PLANS REGARDING THE LOCATION OF ALL FIRE RESISTANCE
 RATED WALL ASSEMBLIES. THIS IS NEEDED IN ORDER TO
 DETERMINE THE LOCATION OF REQUIRED PROTECTION AT DUCT
 PENETRATIONS AND AIR TRANSFER OPENINGS IN ACCORDANCE
 WITH FBCM 607.5. EXAMPLES: SEE LAUNDRY ROOM 132 AREA
 AND FIRE PUMP ROOM 145. THIS IS NOT INTENDED TO BE AN
 EXHAUSTIVE LIST OF ALL DISCREPANCIES. PLEASE CHECK ALL
 SIMILAR PLANS FOR COORDINATION.
  
 2. M1: THE FLOOR PLAN SHOWS MULTIPLE DUCT PENETRATIONS
 OF FIRE RESISTANCE RATED WALL ASSEMBLIES WITH NO
 PROTECTION. THERE ARE TOO MANY LOCATIONS ON THIS PAGE
 TO LIST. SHOW HOW THESE PENETRATIONS ARE TO BE
 PROTECTED IN ACCORDANCE WITH FBCM 607.5. ALSO, THE
 SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH FIRE
 DAMPER AND SMOKE DAMPER SHALL BE SHOWN AND PROPERLY
 IDENTIFIED ON THE BUILDING PLANS BY THE DESIGNER IN
 ACCORDANCE WITH FBCM 607.8.
  
 3. M1: PLAN NOTE #9 APPEARS TWICE ON FLOOR PLAN: ONCE
 FOR IT ROOM AND FIRE COMMAND CENTER. THE CONDENSER FOR
 THE FIRE COMMAND CENTER IS LOCATED ON THE SECOND FLOOR
 OF THE GARAGE AND NOT ON THE ROOF OF THE EMPLOYEE BREAK
 ROOM AS INDICATED BY THE NOTE. PLEASE CLARIFY AND
 CORRECT. FBCB 106.1.1.
  
 4. M1: WHILE IT APPEARS THAT ALL FAN-COIL UNITS (FCU)
 ON THE EQUIPMENT SCHEDULE HAVE UNIQUE DESIGNATIONS, THE
 MARKINGS WHICH IDENTIFY INDIVIDUAL FCUS ON THE FLOOR
 PLANS ARE UNCLEAR. EXAMPLE: FCU 1-19 APPEARS IN
 EMPLOYEE BREAK ROOM 129 AND PREFUNCTION 122. EXAMPLE:
 THE FCU IN WORKROOM 113 HAS NO DESIGNATION AND DOES NOT
 APPEAR ON THE FIRST FLOOR FCU SCHEDULE. THIS IS NOT
 INTENDED TO BE AN EXHAUSTIVE LIST. PLEASE CHECK ALL FCU
 DESIGNATIONS ON FLOOR PLANS AND COORDINATE WITH
 EQUIPMENT SCHEDULE AND PIPING PLANS. FBCM 304.1 AND
 FBCB 106.1.1
  
 5. M1: THE EXHAUST FAN ABOVE GM OFFICE 110 HAS NO
 DESIGNATION ON FLOOR PLAN AND CANNOT BE CORRELATED WITH
 EQUIPMENT SCHEDULE. PLEASE IDENTIFY THIS AND ALL
 APPLIANCES ON FLOOR PLANS TO FACILITATE A THOROUGH
 REVIEW AND CONFIRM SUITABILITY OF THE APPLIANCE FOR THE
 INTENDED USE. FBCM 501.1 AND FBCB 106.1.1
  
 6. M1: THE KITCHEN GREASE EXHAUST DUCT IS SHOWN ON
 FLOOR PLAN PENETRATING AT LEAST ONE FIRE RESISTANCE
 RATED WALL ASSEMBLY. A GREASE DUCT SERVING A TYPE I
 HOOD THAT PENETRATES A FIRE RATED CEILING, FIRE RATED
 WALL OR FLOOR SHALL BE ENCLOSED FROM THE POINT OF
 PENETRATION TO THE OUTLET TERMINAL IN ACCORDANCE WITH
 FBCM 506.3.10. THE DUCT SHALL BE ENCLOSED IN ACCORDANCE
 WITH THE BUILDING CODE REQUIREMENTS FOR SHAFT
 CONSTRUCTION PER THIS SECTION. SEE FBCM 506.3.10 FOR
 ADDITIONAL REQUIREMENTS RELATED TO THIS SHAFT
 ENCLOSURE.
  
 7. M1: KITCHEN EXHAUST DUCT SHALL SLOPE AT A MINIMUM OF
 1/4 INCH PER FOOT IN THE DIRECTION OF THE HOOD IN
 ACCORDANCE WITH FBCM 506.3.7. GIVEN THE LENGTH OF THE
 HORIZONTAL DUCT, PLEASE VERIFY THAT THIS SLOPE IS
 POSSIBLE WHILE MAINTAINING REQUIRED CEILING HEIGHTS.
 ALSO, ANY PORTION OF SUCH SYSTEM HAVING SECTIONS NOT
 PROVIDED WITH ACCESS FROM THE DUCT ENTRY OR DISCHARGE
 SHALL BE PROVIDED WITH CLEANOUT OPENINGS IN ACCORDANCE
 WITH FBCM 506.3.8. CLEANOUTS LOCATED ON HORIZONTAL
 SECTIONS OF DUCTS SHALL BE SPACED NOT MORE THAN 20 FEET
 APART IN ACCORDANCE WITH FBCM 506.3.9.
  
 8. M1: THE 50X30 DUCT ATTACHED TO THE 100% FRESH AIR
 UNIT FOR MAKEUP AIR, DOES IT ONLY GO UP TO THE SECOND
 FLOOR OR DOES IT ALSO GO TO CEILING GRILLS ON THE FIRST
 FLOOR? THE DESIGN INTENT IS UNCLEAR SINCE PAGE M2 SHOWS
 A 40X22 DUCT FROM THE FIRST FLOOR AT THIS LOCATION, NOT
 50X30. PLEASE COORDINATE PAGES, ENSURING DUCT IS
 PROPERLY SIZED FOR THE REQUIRED AIRFLOW. FBCM 304.1 AND
 FBCB 106.1.1
  
 9. M1: PLAN NOTE #4 APPEARS IN CENTER OF SERVICE
 CORRIDOR 127 BUT ITS INTENT AT THIS LOCATION IS
 UNCLEAR. IT STATES ?DOUBLE WALL INSTALLED D ROOF CAP.?
 PLEASE CLARIFY THE NOTE AND ITS INTENT AT THIS
 LOCATION. FBCB 106.1.1.
  
 10. M1: THE FIRST FLOOR APPEARS TO BE SEPARATED INTO
 MULTIPLE SMOKE ZONES. THESE ZONES ARE NOT IDENTIFIED
 ANYWHERE ON PLANS. ARE THESE SMOKE ZONES SEPARATED BY
 SMOKE BARRIERS? THERE IS NOT ENOUGH INFORMATION
 PROVIDED TO PERFORM A THOROUGH REVIEW OF THE SMOKE
 CONTROL SYSTEMS IN THIS BUILDING. THE CONSTRUCTION
 DOCUMENTS SHALL INCLUDE SUFFICIENT INFORMATION AND
 DETAIL TO ADEQUATELY DESCRIBE THE ELEMENTS OF THE
 DESIGN NECESSARY FOR THE PROPER IMPLEMENTATION OF THE
 SMOKE CONTROL SYSTEMS. THESE DOCUMENTS SHALL BE
 ACCOMPANIED BY SUFFICIENT INFORMATION AND ANALYSIS TO
 DEMONSTRATE COMPLIANCE WITH THESE PROVISIONS IN
 ACCORDANCE WITH FBCB 909.2. A RATIONAL ANALYSIS
 SUPPORTING THE TYPES OF SMOKE CONTROL SYSTEMS TO BE
 EMPLOYED, THEIR METHODS OF OPERATION, THE SYSTEMS
 SUPPORTING THEM AND THE METHODS OF CONSTRUCTION TO BE
 UTILIZED SHALL ACCOMPANY THE SUBMITTED CONSTRUCTION
 DOCUMENTS AND SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
 ITEMS INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6 IN
 ACCORDANCE WITH FBCB 909.4. THIS APPLIES TO THE
 COMPLETE SYSTEM THROUGHOUT THE BUILDING. THERE WILL BE
 ADDITIONAL COMMENTS RELATED TO THIS ITEM LATER IN THIS
 REVIEW.
  
 11. M1 THROUGH M7: PLEASE CLARIFY THE HVAC SYMBOL
 LEGENDS ON EACH PAGE. THERE ARE MULTIPLE SYMBOLS AND
 ABBREVIATIONS USED ON FLOOR PLANS WHICH ARE NOT
 REPRESENTED IN THE SYMBOL LEGEND. EXAMPLE: THE SYMBOL
 WHICH INDICATES ON THE LEGEND THAT IT REPRESENTS A FIRE
 DAMPER IS IDENTICAL TO THE SYMBOL WHICH REPRESENTS
 EXISTING R/A. NEITHER ONE APPEARS TO BE REPRESENTATIVE
 OF AN ACTUAL SYMBOL ON THE FLOOR PLANS. ALSO, WHY ARE
 THERE INDICATIONS IN THE LEGEND FOR ?EXISTING?
 MATERIALS? THIS PROJECT IS 100% NEW CONSTRUCTION WITH
 NO EXISTING CONDITIONS. PLEASE CLARIFY AND CORRECT.
 FBCB 106.1.1
  
 12. M1: THE LAUNDRY ROOM COMBUSTION AIR CALCULATIONS
 INDICATE OPENING SIZE OF COMBUSTION AIR DUCTS IS BASED
 ON 1 SQ.IN PER 4000 BTU/H. THIS FORMULA IS ONLY
 APPLICABLE WHEN COMMUNICATING WITH THE OUTDOORS THROUGH
 VERTICAL DUCTS. WHEN HORIZONTAL DUCTS ARE USED, AS
 SHOWN ON THIS FLOOR PLAN, EACH OPENING SHALL HAVE A
 MINIMUM SIZE OF 1 SQ.IN PER 2000 BTU/H IN ACCORDANCE
 WITH FBCFG 304.6.1. THIS REQUIRES EACH OPENING TO BE
 THE MINIMUM SIZE, NOT THE SIZE OF THE TWO DUCTS
 COMBINED. SHOW HOW ADEQUATE COMBUSTION AIR SHALL BE
 PROVIDED FOR THESE APPLIANCES IN ACCORDANCE WITH FBCFG
 304.6. ALSO, THE PLANS REFERENCE THE FBC, MECHANICAL,
 WHILE THE GOVERNING CODE IS THE FBC, FUEL GAS. PLEASE
 CORRECT.
  
 13. M1: GARAGE AREA FLOOR PLAN SHOWS A PLENUM CEILING
 IN THIS AREA BUT THERE ARE DUCTS SHOWN. PLEASE CLARIFY
 WHETHER THIS IS A DUCTED OR PLENUM SYSTEM. FBCM 603.1,
 FBCB 106.1.1. ALSO, IS THE PARKING VENT FAN SHOWN IN
 THIS AREA A SUPPLY OR EXHAUST FAN? AIRFLOW DIRECTIONAL
 ARROWS AND INTAKE LOUVER INDICATE EXHAUST BUT THE
 EMERGENCY MODE NOTE INDICATES IT IS A SUPPLY FAN. NOTE:
 IF THIS IS A SUPPLY FAN, IT EXCEEDS 2000 CFM AND WOULD
 REQUIRE A DUCT SMOKE DETECTOR IN ACCORDANCE WITH FBCM
 606.2.1.
  
 14. M1 GENERATOR ROOM: NO INFORMATION WAS PROVIDED
 REGARDING THE GENERATOR, FUEL SOURCE, FUEL STORAGE,
 PIPING, REFUELING OR LOCATION OF GENERATOR EXHAUST.
 PROVIDE ALL MISSING INFORMATION REQUIRED TO DEMONSTRATE
 COMPLIANCE WITH FBCM 401.5, 915.1 AND 915.2. LIQUID
 FUELED GENERATOR INSTALLATIONS SHALL ALSO COMPLY WITH
 NFPA 37, NFPA 30 AND IF PROVIDING EMERGENCY POWER FOR
 LIFE SAFETY SYSTEMS, NFPA 110.
  
 15. M1: IN BREAKFAST ROOM 103, FLOOR PLAN SHOWS TWO
 SMOKE EXHAUST GRILLS BUT ONLY ONE HAS A CFM AND GRILL
 DESIGNATION. PLEASE CORRECT.
  
 16. M1 THRU M3: THE ZONE FANS DO NOT CORRESPOND WITH
 FLOOR PLANS AND EQUIPMENT SCHEDULE. EXAMPLE: THE ZONE
 #2 FAN ON PAGE M3 SHOWS 6000 CFM BUT THE FLOOR PLAN ON
 M1 CALLS FOR 5600 CFM WHILE THE EQUIPMENT SCHEDULE ON
 M12 ONLY CALLS FOR 1040 CFM. WHICH IS CORRECT? PLEASE
 CLARIFY THE DESIGN INTENT AS WELL AS THE SPECIFIC
 LOCATION OF EACH APPLIANCE BY COORDINATING THE FLOOR
 PLANS, SCHEDULES AND DESIGN REQUIREMENTS TO DEMONSTRATE
 COMPLIANCE WITH FBCM 513.2 AND FBCB 106.1.1.
  
 17. M1, M3, M12: THE EXHAUST FANS SHOWN ON FLOOR PLANS
 AT FIRE COMMAND ROOM 126 AND MECHANICAL ROOM 302 ARE
 BOTH MARKED AS ZONE 3. THE SCHEDULE ON M12 SHOWS ZONE 3
 AT THE FIRE COMMAND ROOM 126. WHICH IS CORRECT? THE
 ZONE 3 FAN ON PAGE M3 CALLS FOR 10,440 CFM WHILE THE
 ZONE 3 FAN ON M1 CALLS FOR 3600 CFM. THERE IS NO FAN ON
 THE EQUIPMENT SCHEDULE WHICH CORRESPONDS WITH THE 10400
 CFM WHICH IS CALLED FOR ON THE FLOOR PLAN. PLEASE
 CLARIFY THE DESIGN INTENT AS WELL AS THE SPECIFIC
 LOCATION OF EACH APPLIANCE BY COORDINATING THE FLOOR
 PLANS, SCHEDULES AND DESIGN REQUIREMENTS TO DEMONSTRATE
 COMPLIANCE WITH FBCM 513.2 AND FBCB 106.1.1.
  
 18. M1: THERE IS AN UNDESIGNATED EXHAUST FAN ABOVE GM
 OFFICE 110. PLEASE GIVE THIS FAN A DESIGNATION ON THE
 FLOOR PLAN AND IDENTIFY THE SMOKE ZONE ASSOCIATED WITH
 THIS FAN PER FBCM 513.2.
  
 19. M2: THERE ARE MULTIPLE DUCT PENETRATIONS AND AIR
 TRANSFER OPENINGS SHOWN ON FLOOR PLAN AT FIRE
 RESISTANCE RATED WALL AND FLOOR/CEILING ASSEMBLIES
 WITHOUT PROTECTION. EXAMPLES: THE 24X24 DUCT
 PENETRATIONS FROM THE 1ST FLOOR AND UP TO THE 3RD
 FLOOR, THE 8X8 SUPPLY FROM THE 3RD FLOOR, THE TOILET
 EXHAUST FROM THE 1ST FLOOR, THE LOUVER PENETRATION FROM
 THE WOMEN?S RESTROOM INTO THE PARKING GARAGE AREA.
 THESE ARE ONLY EXAMPLES AND NOT INTENDED TO BE AN
 EXHAUSTIVE LIST. PLEASE CHECK THE ENTIRE FLOOR PLAN TO
 ENSURE ALL OPENINGS AND PENETRATIONS IN RATED
 ASSEMBLIES ARE PROTECTED IN ACCORDANCE WITH FBCM
 SECTION 607.
  
 20. M2: THE TWO 24X24 SMOKE EXHAUST DUCTS IN THE
 PARKING GARAGE ADJACENT TO THE PREFUNCTION AND LOBBY
 AREAS ARE EXPOSED TO VEHICLE TRAFFIC. DUCTS INSTALLED
 IN LOCATIONS WHERE THEY ARE EXPOSED TO MECHANICAL
 DAMAGE BY VEHICLES OR FROM OTHER CAUSES SHALL BE
 PROTECTED BY APPROVED BARRIERS IN ACCORDANCE WITH FBCM
 603.13.
  
 21. M2: EF 2-1, WHICH APPEARS ADJACENT TO A STAIR
 ENCLOSURE, IS NOT SHOWN ON THE EQUIPMENT SCHEDULE ON
 PAGE M12. PLEASE CLARIFY. ALSO, IS THIS A SUPPLY OR
 EXHAUST FAN? BASED ON THE STAIR ENCLOSURE RISER DIAGRAM
 IT APPEARS TO BE A SUPPLY FAN FOR STAIR PRESSURIZATION.
 IF THIS IS THE CASE, THIS FAN IS SHOWN TO BE WITHIN THE
 BUILDING. THIS FAN IS REQUIRED TO BRING ALL AIR
 DIRECTLY FROM THE OUTDOORS AND BE SEPARATED FROM THE
 REST OF THE BUILDING BY MIN. 2 HOUR FIRE RESISTANCE
 RATED CONSTRUCTION IN ACCORDANCE WITH FBCM 401.4. THE
 LOCATION OF THE INTAKE FOR THIS SYSTEM IS ALSO SUBJECT
 TO THE REQUIREMENTS OF FBCM 401.5.1.
  
 22. M2: FLOOR PLAN SHOWS FCU 2-1 IN VESTIBULE 204 AND
 ELEV. MACHINE ROOM 205. WHICH IS THE CORRECT LOCATION
 FOR THIS FCU? PLEASE COORDINATE FLOOR PLAN WITH
 EQUIPMENT SCHEDULE ON M12 AND C.U. PIPING DIAGRAM ON
 M13.
  
 23. M2: PROVIDE THE MISSING SIZE OF THE RECTANGULAR
 SUPPLY DUCT IN MEETING ROOM 201 IN ACCORDANCE WITH FBCM
 603.1 AND FBCB 106.1.1.
  
 24. M2: THE KITCHEN EXHAUST FAN IS SHOWN ON THE PLANS
 DIRECTLY ADJACENT TO THE BUILDING EXTERIOR AND THE
 PARAPET WALL. EXHAUST OUTLETS SHALL BE LOCATED NOT LESS
 THAN 10 FEET HORIZONTALLY FROM PARTS OF THE SAME OR
 CONTIGUOUS BUILDINGS IN ACCORDANCE WITH FBCM
 506.3.12.3. PLEASE SHOW THE EXHAUST TERMINATION IN A
 LOCATION WHICH COMPLIES WITH THIS SECTION.
  
 25. M2: IT IS NOT CLEAR ON PLANS HOW THE LOW ROOF ABOVE
 THE EMPLOYEE BREAK ROOM WILL BE ACCESSED FOR SERVICE,
 MAINTENANCE OR REPLACEMENT OF THE APPLIANCES INSTALLED
 AT THIS LOCATION. WHERE EQUIPMENT AND APPLIANCES
 REQUIRING ACCESS ARE INSTALLED ON ROOFS OR ELEVATED
 STRUCTURES AT A HEIGHT EXCEEDING 16 FEET, SUCH ACCESS
 SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS OF
 ACCESS IN ACCORDANCE WITH FBCM 306.5. PLEASE SHOW A
 PERMANENT MEANS OF ACCESS TO THIS SPACE.
  
 26. M2: FLOOR PLAN SHOWS A 3 INCH VTR NEXT TO THE
 KITCHEN MAKEUP AIR FAN INTAKE. FRESH AIR INTAKES SHALL
 NOT BE LOCATED CLOSER THAN 10 FEET FROM ANY VENT OUTLET
 OR SANITARY SEWER VENT OUTLET IN ACCORDANCE WITH FBCM
 401.5.1. PLEASE SHOW THE DISTANCE BETWEEN THIS VENT AND
 THE INTAKE OF THE MAKEUP AIR UNIT TO BE IN COMPLIANCE
 WITH THIS SECTION.
 27. M2: THE EQUIPMENT SCHEDULE ON M12 CALLS FOR FCU 2-3
 AT THE MENS/WOMENS RESTROOMS. NO SUCH FCU COULD BE
 FOUND ON THE FLOOR PLANS. PLEASE COORDINATE THIS FLOOR
 PLAN WITH EQUIPMENT SCHEDULE ON M12 AND C.U. PIPING
 DIAGRAM ON M13 IN ACCORDANCE WITH FBCM 603.1 AND FBCB
 106.1.1.
  
 28. M3: THE EVACUATION FAN INTAKE THROUGH THE WALL FROM
 MECHANICAL ROOM 302 INTO THE STAIR/PREFUNCTION ROOM IS
 MISSING A CFM DESIGNATION. PLEASE PROVIDE THE MISSING
 INFORMATION IN ACCORDANCE WITH FBCM 513.2 AND FBCB
 106.1.1.
  
 29. M3: FLOOR PLAN SHOWS FCU 3-6 IN VESTIBULE 301 AND
 ELEVATOR MACHINE ROOM 304. WHICH LOCATION IS CORRECT
 FOR THIS FCU? WHAT IS THE CORRECT DESIGNATION FOR THE
 FCU WHICH IS INCORRECTLY IDENTIFIED ON THE FLOOR PLAN?
 PLEASE COORDINATE THIS FLOOR PLAN WITH EQUIPMENT
 SCHEDULE ON M12 AND C.U. PIPING DIAGRAM ON M13 IN
 ACCORDANCE WITH FBCM 603.1 AND FBCB 106.1.1.
  
 30. M3: IN CONJUNCTION WITH THE ABOVE COMMENT, CFU 3-5
 AND FCU 3-6 DO NOT APPEAR ON THE FCU SCHEDULE ON PAGE
 M12. PLEASE COORDINATE THIS FLOOR PLAN WITH EQUIPMENT
 SCHEDULE ON M12 AND C.U. PIPING DIAGRAM ON M13 IN
 ACCORDANCE WITH FBCM 603.1 AND FBCB 106.1.1.
  
 31. MECHANICAL ROOM 303 IS SERVING AS A RETURN AIR
 PLENUM. THIS ROOM APPEARS TO BE CONSTRUCTED OF
 UNFINISHED CONCRETE BLOCK ACCORDING TO ARCHITECTURAL
 PLANS. BUILDING CAVITIES WHICH WILL BE USED AS RETURN
 AIR PLENUMS SHALL BE LINED WITH A CONTINUOUS AIR
 BARRIER MADE OF DURABLE NON-POROUS MATERIALS IN
 ACCORDANCE WITH FBCM 603.8. ALSO, CAVITIES DESIGNED FOR
 AIR TRANSPORT SUCH AS MECHANICAL CLOSETS, CHASES, AIR
 SHAFTS, ETC. SHALL BE LINED WITH AN AIR BARRIER AND
 SEALED IN ACCORDANCE WITH SECTION 603.9 AND SHALL BE
 INSULATED IN ACCORDANCE WITH TABLE 13-410.1.ABC.2.2 OF
 CHAPTER 13 OF THE FLORIDA BUILDING CODE, BUILDING. OF
 PRIMARY CONCERN ARE THE MECHANICAL ROOM WALLS ADJACENT
 TO THE PARKING GARAGE AND THE ELEVATOR MACHINE ROOM.
 THE OTHER TWO WALLS WILL COMPLY WITH THIS 603.8
 EXCEPTION: SURFACES BETWEEN THE PLENUM AND CONDITIONED
 SPACES FROM WHICH THE RETURN/MIXED AIR IS DRAWN. PLEASE
 SHOW HOW THESE WALLS ARE TO BE INSULATED AND FINISHED
 IN ACCORDANCE WITH THESE SECTIONS.
  
 32. M3: THERE ARE MULTIPLE DUCT PENETRATIONS AND AIR
 TRANSFER OPENINGS SHOWN ON FLOOR PLAN AT FIRE
 RESISTANCE RATED WALL AND FLOOR/CEILING ASSEMBLIES
 WITHOUT PROTECTION. EXAMPLE: THE SUPPLY DUCT
 PENETRATIONS AND AIR TRANSFER OPENINGS AT MECHANICAL
 ROOM 303. THESE ARE ONLY EXAMPLES AND NOT INTENDED TO
 BE AN EXHAUSTIVE LIST. PLEASE CHECK THE ENTIRE FLOOR
 PLAN TO ENSURE ALL OPENINGS AND PENETRATIONS IN RATED
 ASSEMBLIES ARE PROTECTED IN ACCORDANCE WITH FBCM
 SECTION 607.
  
 33. M3: MECHANICAL ROOM 302 FLOOR PLAN SHOWS TWO
 FIRE/SMOKE DAMPERS INLINE IN THE SMOKE EXHAUST
 DUCTWORK. THERE IS NO FIRE OR SMOKE BARRIER OR
 PARTITION SHOWN AT THESE LOCATIONS. WHAT IS THE PURPOSE
 OF THESE OPENING PROTECTIVES AT THESE LOCATIONS? FIRE
 DAMPERS, SMOKE DAMPERS AND COMBINATION FIRE/SMOKE
 DAMPERS LOCATED WITHIN AIR DISTRIBUTION AND SMOKE
 CONTROL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH
 THE REQUIREMENTS OF THIS SECTION, AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS AND LISTING
 PER FBCM 607.
  
 34. M4: EF 4-1 IS IDENTIFIED ON THE EQUIPMENT SCHEDULE
 AS A STAIR PRESSURIZATION FAN. IS THIS A SUPPLY FAN?
 BASED ON THE STAIR ENCLOSURE RISER DIAGRAM IT APPEARS
 TO BE A SUPPLY FAN FOR STAIR PRESSURIZATION. IF THIS IS
 THE CASE, THIS FAN IS SHOWN TO BE WITHIN THE BUILDING.
 THIS FAN IS REQUIRED TO BRING ALL AIR DIRECTLY FROM THE
 OUTDOORS AND BE SEPARATED FROM THE REST OF THE BUILDING
 BY MIN. 2 HOUR FIRE RESISTANCE RATED CONSTRUCTION IN
 ACCORDANCE WITH FBCM 401.4. THE LOCATION OF THE INTAKE
 FOR THIS SYSTEM IS ALSO SUBJECT TO THE REQUIREMENTS OF
 FBCM 401.5.1.
  
 35. M5: THE DUCT SYSTEM FOR FCU 5-19 IN ROOM 508 IS
 MISSING SIZE AND CFM DESIGNATION. PLEASE PROVIDE THE
 MISSING INFORMATION IN ACCORDANCE WITH FBCM 603.1 AND
 FBCB 106.1.1.
  
 36. M5: ON FLOOR PLAN, EF 5-4 AND EF 5-6 ARE BOTH SHOWN
 IN MENS ROOM 527. ALSO, EF 5-4 IS SHOWN IN ROOMS 527
 AND 528. PLEASE CLARIFY THE LOCATION OF THIS EQUIPMENT
 IN ACCORDANCE WITH FBCM 50101 AND FBCB 106.1.1.
  
 37. M5: NOTE #5 ON PLANS CALLS FOR A MAKEUP AIR SUPPLY
 FAN FOR THE DRYERS IN THE LAUNDRY ROOM. NO SUCH SUPPLY
 FAN IS SHOWN ON THE FLOOR PLAN OR THE EQUIPMENT
 SCHEDULE. PLEASE CLARIFY IN ACCORDANCE WITH FBCM 504.5
 AND FBCB 106.1.1. IF THERE IS TO BE SUCH A FAN, NOTE #5
 CALLS FOR A SUPPLY FAN IN EXCESS OF 2000 CFM. A SMOKE
 DETECTOR MAY BE REQUIRED AT THIS LOCATION IN ACCORDANCE
 WITH FBCM 606.2.1.
  
 38. M5: NOTE #5 PART 3 CALLS FOR AN EXHAUST FAN WITH
 BAROMETRIC DAMPER TO BE INSTALLED IN THE LAUNDRY ROOM.
 NO SUCH FAN IS SHOWN ON PLANS OR THE EQUIPMENT
 SCHEDULE. PLEASE CLARIFY IN ACCORDANCE WITH FBCM 501.1
 AND FBCB 106.1.1.
  
 39. M5: FLOOR PLAN SHOWS 3 FAN-COIL UNITS IN THE
 LAUNDRY ROOM CEILING. THESE UNITS HAVE NO TAG OR
 DESIGNATION. PLEASE IDENTIFY THESE UNITS AND COORDINATE
 WITH THE EQUIPMENT SCHEDULE ON M12 AND THE PIPING
 SCHEDULE ON M13.
  
 40. M5: THE FLOOR PLAN SHOWS A FRESH AIR SUPPLY FLEX
 DUCT ROUTED TO CLOSET 516 WITH NO SIZE, GRILL OR CFM
 DESIGNATION. PLEASE PROVIDE MISSING INFORMATION IN
 ACCORDANCE WITH FBCM 603.1 AND FBCM 106.1.1.
  
 41. M5: THE FLOOR PLAN SHOWS A D2 DAMPER AT ONE OF THE
 EXHAUST DUCT PENETRATIONS OF THE SHAFT. WHAT IS THE
 PURPOSE OF THIS DAMPER? THE LOCATION AND POSSIBLE
 FUNCTION DO NOT CORRESPOND WITH THE DAMPER SCHEDULE
 SHOWN ON PAGE M9. PLEASE CLARIFY OR CORRECT PER FBCM
 513.1 AND FBCB 106.1.1.
  
 42. M5 THROUGH M7: THERE ARE MULTIPLE DUCT PENETRATIONS
 OF RATED SHAFT ENCLOSURES SHOWN ON FLOOR PLANS. DUCT
 PENETRATIONS OF SHAFT ENCLOSURES SHALL BE PROTECTED
 WITH FIRE AND SMOKE DAMPERS IN ACCORDANCE WITH FBCM
 607.5.5.1.
  
 43. M5 THROUGH M7: A NOTE ON THE FLOOR PLAN POINTS TO
 WHAT APPEARS TO BE AN EXHAUST RISER AND IDENTIFIES IT
 AS A FRESH AIR RISER. PLEASE CLARIFY IN ACCORDANCE WITH
 FBCM 603.1.
  
 44. M5 THROUGH M7: THERE ARE MULTIPLE DUCT PENETRATIONS
 ON SUPPLY AND EXHAUST AIR SYSTEMS PENETRATING THE RATED
 CORRIDOR WALLS. NOTE #1 ON FLOOR PLAN CLAIMS AN
 EXCEPTION FOR FIRE DAMPERS AS ALLOWED UNDER FBCM
 607.5.3(2). HOWEVER, THESE DUCT PENETRATIONS DO NOT
 QUALIFY FOR THIS EXCEPTION BECAUSE THEY DO NOT MEET ALL
 6 PARTS OF EXCEPTION #2. THESE DUCTS HAVE OPENINGS
 WHICH COMMUNICATE WITH THE CORRIDOR AND THEREFORE FIRE
 DAMPERS ARE REQUIRED. ALSO, MANY OF THESE DUCT
 PENETRATIONS AS SHOWN ON PLAN ARE FLEX DUCT. FLEXIBLE
 DUCTS AND AIR CONNECTORS SHALL NOT PASS THROUGH ANY
 FIRE-RESISTANCE-RATED ASSEMBLY IN ACCORDANCE WITH FBCM
 607.7.
 IN ADDITION, DUCT PENETRATIONS OF FIRE RESISTANCE RATED
 CORRIDOR WALLS SHALL BE PROTECTED WITH SMOKE DAMPERS IN
 ACCORDANCE WITH FBCM 607.5.4.
 NOTE: DUCTS AND AIR TRANSFER OPENINGS THAT PENETRATE
 FIRE-RESISTANCE-RATED ASSEMBLIES AND ARE NOT REQUIRED
 TO HAVE DAMPERS BY FBCM 607 SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTION 712 OF THE FLORIDA BUILDING
 CODE, BUILDING. PROVIDE A THROUGH-PENETRATION FIRESTOP
 SYSTEM DETAIL FOR DUCT PENETRATIONS WHICH WILL NOT BE
 PROTECTED BY FIRE DAMPERS.
  
 45. M5 THROUGH M7: MANY FLEX DUCTS FOR O.A. INTO GUEST
 ROOMS AND FCU SUPPLY DIFFUSERS ARE MISSING SIZES AND
 SOME ARE MISSING CFM AND GRILL DESIGNATIONS. PLEASE
 PROVIDE ALL MISSING INFORMATION ON AIR DISTRIBUTION
 SYSTEM COMPONENTS IN ACCORDANCE WITH FBCM 603.1.
  
 46. M5 THROUGH M7: THE SEQUENCE OF OPERATIONS FOR THE
 SMOKE CONTROL SYSTEM IN THESE AREAS IN UNCLEAR. WHAT IS
 THE LOCATION OF SMOKE BARRIERS? WHAT ROLE (IF ANY) DO
 THE EXHAUST RISERS PLAY IN THE SMOKE CONTROL SYSTEM?
 WHY ARE THE SUPPLY FANS AT THE ENDS OF THE CORRIDORS
 MARKED AS EXHAUST FANS (EF)? PLEASE PROVIDE A COMPLETE
 RATIONAL ANALYSIS FOR THE BUILDING SMOKE CONTROL SYSTEM
 WITH A DETAILED SEQUENCE OF OPERATION. THE ANALYSIS
 SHALL INCLUDE ALL PERMUTATIONS OF SYSTEMS? STATUS IN
 ACCORDANCE WITH FBCM 513.4 THROUGH 513.4.6. SEE
 FOLLOWING COMMENT FOR ADDITIONAL INFORMATION.
 NOTE: A COMPLETE REVIEW OF THE BUILDING SMOKE CONTROL
 SYSTEM IS NOT POSSIBLE AT THIS TIME. ADDITIONAL
 COMMENTS RELATED TO THIS SYSTEM IN A FUTURE REVIEW ARE
 LIKELY.
  
 47. SMOKE CONTROL: EQUIPMENT SUCH AS, BUT NOT LIMITED
 TO, FANS, DUCTS, AUTOMATIC DAMPERS AND BALANCE DAMPERS
 SHALL BE SUITABLE FOR THEIR INTENDED USE, SUITABLE FOR
 THE PROBABLE EXPOSURE TEMPERATURES THAT THE RATIONAL
 ANALYSIS INDICATES, AND AS APPROVED BY THE CODE
 OFFICIAL IN ACCORDANCE WITH FBCM 513.10. FLEXIBLE AND
 RIGID FIBERGLASS DUCTS WILL NOT BE ACCEPTED AS PART OF
 THE SMOKE CONTROL SYSTEM. IN ADDITION TO OTHER
 REQUIREMENTS, BELT-DRIVEN FANS SHALL HAVE 1.5 TIMES THE
 NUMBER OF BELTS REQUIRED FOR THE DESIGN DUTY WITH THE
 MINIMUM NUMBER OF BELTS BEING TWO. FANS SHALL BE
 SELECTED FOR STABLE PERFORMANCE BASED ON NORMAL
 TEMPERATURE AND, WHERE APPLICABLE, ELEVATED TEMPERATURE
 IN ACCORDANCE WITH FBCM 513.10.5. PROVIDE DOCUMENTATION
 SHOWING ALL COMPONENTS OF THE SMOKE CONTROL SYSTEM ARE
 SUITABLE FOR THEIR INTENDED USE IN ACCORDANCE WITH
 THESE SECTIONS.
  
 48. M5: NOTE #6 ON THIS PAGE CALLS FOR A PRESSURE
 SENSOR TO ENSURE ELEVATOR SHAFT IS EQUALLY PRESSURIZED
 WITH CORRIDOR. NO INFORMATION COULD BE FOUND ON PLANS
 OR EQUIPMENT SHOWN ON THE PLANS FOR ELEVATOR SHAFT
 PRESSURIZATION. HOW IS THIS TO BE ACCOMPLISHED? IS THIS
 TO BE INTEGRATED WITH THE SMOKE CONTROL SYSTEM? IS THIS
 CONDITION WITH THE PRESSURE SENSOR TO BE ONLY ON THIS
 FLOOR OR ON ALL GUEST ROOM FLOORS? IF IT IS ONLY ON
 THIS FLOOR IT DOES NOT APPEAR POSSIBLE TO SERVE ITS
 STATED PURPOSE. PLEASE CLARIFY AND INCLUDE THIS
 CONDITION IN THE RATIONAL ANALYSIS FOR THE SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH FBCM 513.1.
  
  
 49. M5 THROUGH M7: IN THE GUEST ROOMS, SOME BATHROOM
 EXHAUST LOCATIONS ARE MARKED WITH AN EF DESIGNATION
 WHILE OTHERS ARE NOT, BUT ALL ARE CONNECTED TO THE SAME
 COMMON DUCTS. ARE THERE EXHAUST FANS AT THE LOCATIONS
 WITH THE EF DESIGNATION? PLEASE CLARIFY IN ACCORDANCE
 WITH FBCM 501.1 AND FBCB 106.1.1.
  
 50. M5 THROUGH M7: IT IS NOT CLEAR HOW RETURN AIR WILL
 GET BACK TO FAN-COIL UNITS IN THE GUEST ROOMS. PLEASE
 CLARIFY BY PROVIDING THE SIZE AND LOCATION OF RETURN
 AIR OPENINGS, TRANSFER AIR OPENINGS AND THE LOCATION OF
 RETURN AIR PLENUM CEILINGS IN THE ROOMS. SHOW
 COMPLIANCE WITH FBCM 601.4 AND 603.8.
  
 51. M5 THROUGH M7: FLOOR PLAN SHOWS A DESIGNATION FOR
 AN FCU IN THE ELEVATOR LOBBIES BUT NO FCU IS SHOWN AT
 THIS LOCATION. PLEASE CLARIFY, COORDINATE WITH
 EQUIPMENT SCHEDULE ON M12 AND PIPING SCHEDULE ON M13 IN
 ACCORDANCE WITH FBCM 603.1 AND FBCB 106.1.1.
  
 52. M6: THE FCU IN ROOM 622 APPEARS TO HAVE 3 SUPPLY
 OUTLETS MISTAKENLY DRAWN IN WHERE ONLY 2 SHOULD BE. IS
 THIS THE CORRECT DESIGN? PLEASE CLARIFY PER FBCM 603.1.
  
 53. M7: THIS PLAN SHOWS EF 6-2 OUT IN SPACE SOMEWHERE
 AWAY FROM THE BUILDING. PLEASE CORRECT OR CLARIFY THE
 INTENT OF THIS FAN AT THIS LOCATION.
  
 54. M8: THE STAIR PRESSURIZATION FANS ON THE ROOF HAVE
 NO EQUIPMENT DESIGNATION ON THE PLANS. PLEASE IDENTIFY
 THESE FANS ON THE FLOOR PLAN TO COORDINATE WITH THE
 EQUIPMENT SCHEDULE ON M12. ALSO, THESE FANS APPEAR TO
 EXCEED 2000 CFM AND THEREFORE DUCT SMOKE DETECTORS ARE
 REQUIRED IN ACCORDANCE WITH FBCM 606.2.1.
  
 55. M8: ARE THE OARTUS ON THE ROOF ATTACHED TO OR
 PROVIDED WITH ERVS? WHILE IT IS UNCLEAR IF THE EXHAUST
 SYSTEMS LOCATED IN GUEST ROOM CORRIDORS ARE AN INTEGRAL
 PART OF THE BUILDING SMOKE CONTROL SYSTEM, PLEASE TAKE
 NOTE THAT ERVS MAY NOT BE USED AS PART OF A SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH FBCM 514.2(3)
  
 56. M8: DO ELEVATOR SHAFTS HAVE ANY TYPE OF VENTING?
 HOISTWAYS OF ELEVATORS PENETRATING MORE THAN THREE
 STORIES SHALL BE PROVIDED WITH A MEANS FOR VENTING
 SMOKE AND HOT GASES TO THE OUTER AIR IN CASE OF FIRE IN
 ACCORDANCE WITH FBCB 3004.1. VENTS SHALL BE LOCATED IN
 ACCORDANCE WITH FBCB 3004.2 AND SIZED IN ACCORDANCE
 WITH FBCB 3004.3. ALSO, ELEVATOR SHAFT VENTS SHALL BE
 EQUIPPED WITH MOTORIZED DAMPERS THAT ARE CAPABLE OF
 BEING AUTOMATICALLY CLOSED DURING NORMAL BUILDING
 OPERATION AND ARE INTERLOCKED TO OPEN AS REQUIRED BY
 FIRE AND SMOKE DETECTION SYSTEMS IN ACCORDANCE WITH
 FBCB 13-409.1.ABC.3.1.
  
 57. ELEVATORS: WHERE STANDBY POWER IS CONNECTED TO
 ELEVATORS, THE MACHINE ROOM VENTILATION OR AIR
 CONDITIONING SHALL BE CONNECTED TO THE STANDBY POWER
 SOURCE IN ACCORDANCE WITH FBCB 3003.1.4.
  
 58. M9: THE FRESH AIR AND SMOKE EVAC RISER CALLS FOR
 EXHAUST SYSTEM TO BE USED ON AFFECTED FLOOR BUT THE
 EXHAUST SYSTEM TO BE USED AND ANY CONTROLS OR
 ASSOCIATED DAMPERS ARE NOT IDENTIFIED ON PLANS. PLEASE
 COORDINATE THIS RISER DIAGRAM WITH THE RATIONAL
 ANALYSIS AND THE COMPLETE SEQUENCE OF OPERATIONS TO BE
 PROVIDED IN ACCORDANCE WITH FBCM 513.1. SEE ALSO
 COMMENTS 46 AND 47 ABOVE.
  
 59. M9: THE DAMPER CONTROL SEQUENCE SHOWS A D5 DAMPER
 BUT NO SUCH DAMPER IS SHOWN ON FLOOR PLANS OR RISER
 DIAGRAMS. PLEASE CLARIFY AND COORDINATE ALL SMOKE
 CONTROL COMPONENTS AS REQUESTED IN PREVIOUS COMMENTS.
  
 60. M9: THE STAIR PRESSURIZATION RISER SHOWS EACH DUCT
 PENETRATION OF THE STAIR SHAFT PROTECTED WITH FIRE
 DAMPERS EXCEPT FOR THE ONE ON THE 5TH FLOOR. WHY IS
 THIS FLOOR DIFFERENT FROM THE OTHERS? PLEASE SHOW HOW
 THIS PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH
 FBCM 607.5.
  
 61. M10 AND M11: THERE ARE MULTIPLE APPLIANCES AND
 PIECES OF EQUIPMENT SHOWN ON THESE PLANS WHICH WILL BE
 EXPOSED TO WIND. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT
 AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM
 301.13. PLEASE PROVIDE COMPLETE DOCUMENTATION SHOWING
 HOW EACH APPLIANCE EXPOSED TO WIND IS TO BE SECURED TO
 THE STRUCTURE FOR WIND RESISTANCE. THIS INCLUDES ALL
 RTUS, CONDENSING UNITS AND FANS. IN ADDITION TO THE
 ATTACHMENT REQUIREMENTS, PLEASE PROVIDE MANUFACTURER?S
 DOCUMENTATION SHOWING EACH APPLIANCE WHICH IS EXPOSED
 TO WIND THAT IS IT DESIGNED TO RESIST ANTICIPATED WIND
 PRESSURES IN ACCORDANCE WITH THIS SECTION.
  
 62. M10 AND M11: AHU DETAIL SHOWS A SECONDARY DRAIN
 OUTLET FROM THE AUXILIARY DRAIN PAN. HOW WILL THIS
 SERVE AS AUXILIARY DRAIN PROTECTION? SHOW COMPLIANCE
 WITH ONE OF THE ALLOWED METHODS LISTED UNDER FBCM
 307.2.3. ALSO, THIS DETAIL APPEARS SPECIFIC TO AHUS.
 WILL THERE BE A SEPARATE HANGING DETAIL FOR FAN-COILS
 OR IS THIS DETAIL APPLICABLE TO BOTH? PLEASE SHOW HOW
 ALL CONDENSATE DRAINS ARE TO BE TRAPPED IN ACCORDANCE
 WITH FBCM 307.2.4.
 NOTE: PLUMBING PLANS SHOW CONDENSATE RISERS TERMINATING
 IN THE PARKING GARAGE, PLEASE INDICATE HOW GASSES FROM
 THE GARAGE WILL BE PREVENTED FROM MIGRATING TO OCCUPIED
 AREAS VIA THE CONDENSATE DRAIN PIPING.
  
 63. M11: THE DETAIL FOR THE ROOFTOP STAND SHOWS A
 HEIGHT OF 18 INCHES FROM THE BASE OF THE LEG. THIS
 HEIGHT MAY NOT BE SUFFICIENT AS CLEARANCE ABOVE THE
 ROOFING MATERIAL SHALL BE IN ACCORDANCE WITH FBCB TABLE
 1509.7.
  
 64. M12: THE EF SCHEDULE HAS SEVERAL NOTES AT THE
 BOTTOM. ALL OF THESE NOTES DO NOT APPEAR TO BE
 APPLICABLE TO ALL FANS. PLEASE PROVIDE A MEANS WITHIN
 THE SCHEDULE TO DETERMINE WHICH NOTES APPLY TO WHICH
 FANS IN ACCORDANCE WITH FBCM 501.1 AND FBCB 106.1.1.
  
 65. M12: THE STAIR PRESSURIZATION CALCS LIST A STAIR 3
 BUT NO SUCH PRESSURIZED STAIR COULD BE LOCATED ON PANS.
 STAIR 3 IS SHOWN AS AN OPEN STAIR BETWEEN FIRST AND
 SECOND FLOORS. PLEASE CLARIFY IN ACCORDANCE WITH FBCB
 909.20.4.
  
 66. M12: THROUGHOUT THE PLANS AND THE EQUIPMENT
 SCHEDULES THERE ARE DISCREPANCIES. EXAMPLE: THE STAIR
 PRESSURIZATION FANS ON THE SCHEDULE CALL FOR 12,500 CFM
 EACH BUT ON THE RISER DIAGRAM THEY CALL FOR 10,000 CFM
 EACH. EXAMPLE: THE FRESH AIR RTU ON THE ROOF CALLS FOR
 8,600 CFM BUT IT CALLS FOR 86,000 CFM ON THE EQUIPMENT
 SCHEDULE. EF 2-2 IS MISSING FROM THE EF SCHEDULE. MANY
 PREVIOUS COMMENTS ALSO DEALT WITH DISCREPANCIES WITH
 EQUIPMENT SCHEDULE.
 NOTE: THESE ARE JUST SOME EXAMPLES AND ARE NOT INTENDED
 TO SERVE AS AN EXHAUSTIVE LIST. PLEASE COORDINATE ALL
 FLOOR PLANS WITH EQUIPMENT SCHEDULES TO PROVIDE CLEAR
 DIRECTION AS TO THE DESIGN INTENT AND LOCATION AND
 RATING OF ALL APPLIANCES.
  
 67. M13: THE PIPING DIAGRAMS ARE OF POOR QUALITY AND
 SOME ARE ILLEGIBLE. PLEASE PROVIDE THIS INFORMATION IN
 A CLEAR AND LEGIBLE FORMAT IN ACCORDANCE WITH FBCB
 106.1.1. THESE DIAGRAMS CAN NOT BE THOROUGHLY REVIEWED
 AT THIS TIME. HOWEVER, MANY DISCREPANCIES BETWEEN
 PIPING DIAGRAMS AND FLOOR PLANS AS FAR AS FCU
 DESIGNATIONS ARE EVIDENT. PLEASE CORRECT ANY
 DISCREPANCIES AND COORDINATE PLANS AS REQUESTED IN
 PREVIOUS COMMENTS.
  
 68. KITCHEN HOOD PLANS: THERE APPEAR TO BE OVERLAPPING
 LAYERS ON THESE PLANS. ALSO, SOME PARTS OF THE PLAN DID
 NOT FIT ON THE PAGE AND WERE CUT OFF. ALSO, SOME PARTS
 ARE WITHIN THE BINDER FOR THE ROLL OF PLANS AND CAN NOT
 BE VIEWED. PLEASE PROVIDE CLEAR AND LEGIBLE PLANS FOR A
 THOROUGH REVIEW IN ACCORDANCE WITH FBCB 106.1.1.
  
 69. KITCHEN HOOD PLANS: THE SCHEDULE CALLS FOR 12X12
 GREASE EXHAUST DUCT. FLOOR PLANS ON M1 CALL FOR 10X10
 DUCT. IF THE DUCT IS 10X10 AT A QUANTITY OF 1800 CFM
 THE VELOCITY WILL EXCEED THE MAXIMUM ALLOWED VELOCITY
 OF 2500 FPM. GREASE DUCT SYSTEMS SERVING A TYPE I HOOD
 SHALL BE DESIGNED AND INSTALLED SO AS TO PROVIDE AN AIR
 VELOCITY WITHIN THE DUCT SYSTEM OF NOT LESS THAN 1,500
 FEET PER MINUTE AND NOT GREATER THAN 2,500 FEET PER
 MINUTE IN ACCORDANCE WITH FBCM 506.3.4.
  
 70. KITCHEN HOOD PLANS: THE EF SCHEDULE CALLS FOR 850
 CFM WHILE THE HOOD SCHEDULE CALLS FOR 1800 CFM. WHICH
 IS CORRECT? PLEASE PROVIDE A CONSISTENT DESIGN TO
 FACILITATE A THOROUGH REVIEW OF THE KITCHEN GREASE
 EXHAUST SYSTEM PER FBCM 506.1.
  
 71. KITCHEN HOOD PLANS: THE HOOD SCHEDULE SHOWS A 105
 INCH LONG HOOD WITH TWO SUPPLY COLLARS WHILE THE PLAN
 VIEW OF THE HOOD SHOWS A 48 INCH WIDE HOOD WITH ONE
 COLLAR. WHICH IS CORRECT? PLEASE PROVIDE A CONSISTENT
 DESIGN TO FACILITATE A THOROUGH REVIEW OF THE KITCHEN
 GREASE EXHAUST SYSTEM PER FBCM 506.1.
  
 72. PROVIDE ENERGY CALCULATIONS FOR PLAN REVIEW.
 HEATING, VENTILATING AND AIR-CONDITIONING SYSTEMS OF
 ALL STRUCTURES SHALL BE DESIGNED AND INSTALLED FOR
 EFFICIENT UTILIZATION OF ENERGY IN ACCORDANCE WITH
 CHAPTER 13 OF THE FLORIDA BUILDING CODE, BUILDING PER
 FBCM 301.2.
  
 73. PROVIDE COOLING LOAD CALCS FOR ALL SYSTEMS WHICH
 PROVIDE COOLING FOR HUMAN COMFORT IN ACCORDANCE WITH
 FBCB 13-407.1.ABC.1.
  
 74. PROVIDE OUTSIDE AIR CALCULATIONS SHOWING OCCUPANCY
 CLASSIFICATIONS, OCCUPANT LOADS, VENTILATION RATES
 REQUIRED AND VENTILATION PROVIDED FOR ALL HABITABLE
 SPACES IN ACCORDANCE WITH FBCM 403.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH A
 DESCRIPTION OF HOW EACH COMMENT HAS BEEN ADDRESSED AND
 WHERE THE REQUIRED INFORMATION CAN BE FOUND. PLEASE
 RETURN ONE SET OF OLD OR VOIDED PLANS FROM THIS REVIEW
 FOR REFERENCE.
  
 NOTE: THERE WAS MUCH INFORMATION NOT PROVIDED FOR THIS
 REVIEW. EVERY EFFORT WAS MADE TO PERFORM A THOROUGH
 REVIEW DURING THIS CYCLE TO PREVENT NEW COMMENTS DURING
 A SUBSEQUENT CYCLE. HOWEVER, ONCE ALL REQUESTED
 INFORMATION IS PROVIDED NEW COMMENTS ARE POSSIBLE DUE
 TO INFORMATION BEING REVIEWED FOR THE FIRST TIME OR DUE
 TO ANY DESIGN CHANGES MADE SUBSEQUENT TO THIS REVIEW.
  
 NOTE: THIS PROJECT HAS BEEN SUBMITTED FOR PLAN REVIEW
 ONLY AND NOT FOR PERMIT. IF THE PERMIT APPLICATION IS
 SUBMITTED BY THE CONTRACTOR ON OR AFTER MARCH 1, 2009,
 THESE PLANS SHALL BE SUBJECT TO RE-REVIEW FOR
 COMPLAINCE WITH THE NEW 2007 FLORIDA BUILDING CODE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
2008-12-29 09:55:42TO "COMM" BD#4/PLANS ON RACK/3 ROLLS

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-10 Cont ID  
Sent By kstevens Date 2009-01-10 Time 20:16 Rev Time 0.00
Received By kstevens Date 2009-01-07 Time 18:59 Sent To  
Notes
2009-01-10 20:20:05DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
  
 **********PLAN REVIEW ONLY**********
  
 1. SHT GN-2 CODE DATA TO INCLUDE THE 2007 AMENDMENTS.
 SECTION 106.1.1.
  
 2. SHT GN-2 GUEST UNIT INFORMATION:
 SECTION 11-9.1.3, SLEEPING ACCOMMODATION FOR PERSONS
 WITH HEARING IMPAIRMENTS.
 IN ADDITION TO THOSE ACCESSIBLE SLEEPING ROOMS AND
 SUITES REQUIRED BY SECTION 11-9.1.2, SLEEPING ROOMS AND
 SUITES THAT COMPLY WITH SECTION 11-9.3 SHALL BE
 PROVIDED IN CONFORMANCE WITH THE FOLLOWING TABLE.
 NUMBER OF ELEMENTS =151 TO 200 / ACCESSIBLE ELEMENTS 6.
 PLEASE INDICATE WHERE THE SIX ELMENTS WILL BE LOCATED.
 INDICATE WITH ROOM NUMBERS IN THE GUEST INFORMATION.
  
 3. SHT GN-2 GUEST UNIT INFORMATION:
 SECTION 11-9.1.4 CLASSES OF SLEEPING ACCOMMODATIONS.
 (1) IN ORDER TO PROVIDE PERSONS WITH DISABILITIES A
 RANGE OF OPTIONS EQUIVALENT TO THOSE AVAILABLE TO OTHER
 PESONS SERVED BY THE FACILITY, SLEEPING ROOMS AND
 SUITES REQUIRED TO BE ACCESSIBLE BY SECTION 11-9.1.2
 SHALL BE DISPERSED AMONG THE VARIOUS CLASSES OF
 SLEEPING ACCOMMODATIONS AVAILABLE TO PATRONS OF THE
 PLACE OF TRANSIENT LODGING. THERE ARE NO TWO BEDROOM
 UNITS THAT ARE ACCESSIBLE. PLEASE SHOW COMPLIANCE.
  
 4. SHT GN-2 PER SECTION 11-9.1.2 IN ALL BUILDINGS,
 STRUCTURES AND FACILITIES LICENSED AS A HOTEL, OR
 "RESORT CONDOMINIUM" PURSANT TO CHAPTER 509, FLORIDA
 STATUES, A NUMBER OF ROOMS EQUALING 5 PERCENT OF THE
 GUEST ROOMS MINIMUM THE NUMBER OF ACCESSIBLE ROOMS
 REQUIRED BY THE TABLE BELOW SHALL PROVIDE ADDITIONAL
 SPECIAL ACCESSIBLITY FEATURES OF SECTION 11-9.2.3. 3
 UNITS ARE REQUIRED. PLEASE INDICATE THE ROOM NUMBERS OF
 THE 3 UNITS.
  
 5. SHT GN-2 PLUMBING FIXTURE COUNT CALCULATIONS.
 INDICATE THE SQUARE FOOTAGE FOR ALL PUBLIC SPACES ON
 THE GROUND FLOOR AND SECOND FLOOR. INCLUDE THE AREAS
 FOR ALL BUSINESS, ASSEMBLY, STORAGE ETC. AREAS PER
 TABLE 403.1.
  
 6. SHTS C-3 & C-6 ALL PLUMBING WORK WITHIN THE
 FOOTPRINT OF THE BUILDING SHALL BE INSTALLED BY A
 LICENSED PLUMBING CONTRACTOR WITH MATERIALS APPROVED IN
 TABLE 702.2 OF THE FBC-2004 PLUMBING CODE. PER FS 489
 THIS IS NOT WITHIN THE SCOPE AND LICENSURE OF A UTILITY
 OR SITE CONTRACTOR.
  
 7. SHT A2.02 OVERFLOW SCUPPERS INDICATE REFERENCE TO
 PLUMBING DRAWINGS. THESE WERE NOT LOCATED ON THE
 PLUMBING DRAWINGS NOR ARE THEY SHOWN ON THE BUILDING
 ELEVATIONS. (ONLY TWO WERE FOUND ON THE NORTH
 ELEVATION). PLEASE SUBMIT A DETAIL FOR ALL OVERFLOW
 SCUPPERS SHOWING THE HEIGHT, WIDTH AND INDICATE THE
 MEASUREMENT OFF THE ROOF TO THE FLOW LINE, MINIMUM 2"
 AND MAXIMUM 4"SECTIONS 106.1.2 & 1503.4.3. SHOW
 SCUPPERS ON ALL ELEVATIONS.
  
 8. SHT A2.03 MAKES REFERENCE TO OVERFLOW SCUPPER AT THE
 SOUTH EAST CORNER OF THE ROOF. THE SCUPPERS WERE NOT
 LOCATED ON THE ELEVATIONS. PLEASE CLARIFY. SECTIONS
 106.1.1 & 1503.4.3.
  
 9. SHTS A2.05 & A2.06 MAKES REFERENCE TO OVERFLOW
 SCUPPERS. THE SCUPPERS WERE NOT LOCATED ON THE
 ELEVATIONS. PLEASE CLARIFY. SECTIONS 106.1.1 &
 1503.4.3.
  
 10. SHT A2.07 ROOM 709. CLARIFY THE NOTE WHICH STATES,
 UNIT J FLOORS 7-8 (HC ACCESSIBLE) AND ROOM 711 UNIT F
 FLOORS 7-9 (HC ACCESSIBLE). THIS DOES NOT CORRELATE
 WITH THE GUEST UNIT INFORMATION ON SHT GN-2. PLEASE
 CORRLEATE. SECTIONS 106.1.1 & 11-9.1.2.
  
 11. SHT A2.08 PLEASE SUBMIT CALCULATIONS FOR EACH ROOF
 DRAIN. SHOW THE SQUARE FOOT AREA DRAINED BY EACH ROOF
 DRAIN ALONG WITH 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO THE AREA.
  
 12. SHT A 2.08 THE ROOF FOR THE ELEVATORS AND THE ROOF
 FOR STAIR NUMBER 2 DO NOT SHOW THE REQUIRED SECONDARY
 ROOF DRAINS. PLEASE SHOW THE DRAINS REQUIRED BY
 SECTIONS 1107.1 & 1107.2.
  
 13. SHT A14.06 DETAIL A5 THE CONTROLS SHALL BE LOCATED
 AS SHOWN IN FIGURE 11-34.
  
 14. SHT A14.06 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C.
 C. 11-4-16-6 DISPENSERS
 ___LAV
 A. 11-4.19.2 HEIGHT & CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 15. SHT A14.09 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C.
 C. 11-4-16-6 DISPENSERS
 ___LAV
 A. 11-4.19.2 HEIGHT & CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 16. SHT A14.13 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C.
 C. 11-4-16-6 DISPENSERS
 ___LAV
 A. 11-4.19.2 HEIGHT & CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCET
  
 17. SHT A14.14 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C.
 C. 11-4-16-6 DISPENSERS
 ___LAV
 A. 11-4.19.2 HEIGHT & CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 18. SUBMIT A FINISH SCHEDULE FOR THE WALLS & FLOOR IN
 THE PUBLIC AND COMMON USE TOILET ROOMS TO SHOW
 COMPLIANCE WITH SECTION 1210. SECTION 106.1.2.
  
 19. SHT A16.01 DETAILS A1, A4, E13, J6, J13,L6 & L10.
 SHOW THE GRAB BAR SIZE BEHIND THE WATER CLOSET AS 36
 INCHES LONG AS REQUIRED IN SECTION 11-4.16.4 & FIGURE
 28. SOME DETAILS SHOW THE GRAB BAR AS 24", SOME DETAILS
 SHOW THE GRAB AS 36" AND SOME SHOW NO MEASUREMENT.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 20. SHT A16.01 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___LAV
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 21. SHT A16.02 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C
 A. 11-4.16.4 GRAB BARS (36" REQD. BUT SHOWN AS 24"
 BEHIND THE W/C)
  
 ___LAV
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 ___TOILET ROOMS
 A. 11-4.22.3 UNOBSTRUCTED TURNING AREA
  
 21. SHT P1 SHOWS SUMP PUMPS FROM THE ELEVATORS
 CONNECTING DIRECTLY TO THE SANITARY. PER SECTION 301.6
 THIS IS PROHIBITED. IF DRAINING TO THE SANITARY, AN
 INTERCEPTOR MAY BE REQUIRED. AN OUTLET TO PUMP CONTENTS
 INTO A RECEPTICLE AND PROPER DISPOSAL AS HAZARDOUS
 MATERIAL IS ACCEPTABLE. PLEASE INDICATE METHOD. SECTION
 106.1.2.
  
 22. SHTS P1, P2 & P3 SHOWS TRENCH DRAINS CONNECTING TO
 THE SANITARY. PLEASE INDICATE WHAT WILL DRAIN INTO THE
 TRENCH DRAIN. IF STORM WATER, THEN IT MUST CONNECT TO
 THE STORM SYSTEM AND THE AIR ADMITTENCE VALVE, (STUDOR
 VENT), IS NOT REQUIRED. ARTICLE III SECTION 90-124(6).
 IF SANITARY DRAINAGE THE AAV IS REQUIRED TO HAVE A
 RELIEF VENT PER SECTION 917.13.2. PLEASE CLARIFY.
  
 23. SHT P7 DRAWING TITLE PLUMBING 7TH - PENTHOUSE PLAN
 SHOWS A 3/4 INCH HOT WATER RETURN. IS THIS TYPICAL FOR
 ALL FLOORS? IF NOT IT SHALL BE A SEPARATE SHEET OR BE
 INDICATED AS FOR WHATEVER FLOORS IT IS ON. IS SHT P6
 (6TH FLOOR), DIFFERENT FROM THE 7TH THRU PENTHOUSE
 FLOORS? PLEASE CLARIFY. SECTIONS 106.1.1 & 601.1.
  
 24. SHT P8 PER SECTIONS 1107.1 1107.2 SECONDARY ROOF
 DRAINS OR EMERGENCY OVERFLOW SCUPPERS ARE REQUIRED.
 PLEASE INDICATE THE LOCATION OF THE REQUIRED SEPARATE
 SYSTEM.
  
 25. SHT P8 SEE SHEET A2.08 WHEN MAKING CALCULATIONS FOR
 THE ROOF DRAINAGE, KEEP IN MIND THE RIDGE IS NOT IN THE
 CENTER OF THE ROOF SO MORE SQUARE FOOTAGE WILL BE
 DIRECTED TO THE DRAINS ON ONE SIDE OF THE ROOF THAN THE
 OTHER. TABLE 1106.3.
  
 26. SHT P12 ENLARGED KITCHEN PLAN. ITEM 18, (DISH
 WASHER), SHALL NOT DISCHARGE INTO THE GREASE SYSTEM,
 AND IS REQUIRED TO DISCHARGE INTO THE SANITARY SYSTEM.
 ARTICLE III SECTION 90-124(7)(B).
  
 27. SHT P12 ENLARGED KITCHEN PLAN. THE WATER FILTER
 SHALL MEET THE REQUIREMENTS OF NSF 42 PER SECTION
 611.1. PLEASE SUBMIT MANUF. SPECIFICATIONS SHOWING
 COMPLIANCE. SECTION 106.1.2.
  
 28. SHT P12 WATER PIPING DIAGRAM. A VACUUM RELIEF VALVE
 IS REQUIRED PER SECTION 504.2. PLEASE SHOW AT THE TOP
 OF THE COLD WATER SUPPLY DROP TO THE WATER HEATERS.
  
 29. SHT P12 WATER HEATER PIPING DIAGRAM EXPANSION TANK.
 SUBMIT MANUF SPECIFICATIONS INDICATING MODEL NUMBER AND
 SUBMIT CALCULATIONS OR MANUF. CHART SHOWING THE CORRECT
 SIZE OF THE EXPANSION TANK. SECTION 607.3.2.
  
 30. SHT P12 WATER HEATER PIPING DIAGRAM DOES NOT RELECT
 ENLARGED BOILER ROOM PIPING. THE DIAGRAM ON SHT P24
 DOES REFLECT THE PIPING. PLEASE INDICATE WITH A NOTE
 DIRECTING ATTENTION TO THE RISER ON SHT P24 AS WELL,
 LIKE THE NOTE DIRECTING ATTENTION TO THE PIPING DIAGRAM
 AT THE BOILER ROOM. SECTIONS 106.1.1 & 601.1.
  
 31. SHT P12 TYPICAL ENLARGED "UNIT S" PLAN. PLEASE
 INDICATE WHERE THE HOT WATER TO THE TUB CONNECTS TO THE
 WATER SUPPLY LINE OVERHEAD. THE WATER RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN AT THE RISER. PLEASE
 CORRELATE. SECTIONS 106.1.1, 106.1.2 & 607.4.
  
 32. SHT P13 UNIT D SANITARY RISER DIAGRAM SHOWER IS NOT
 VENTED AND THE FLOOR PLAN SHOWS A TUB. UNIT D WATER
 RISER SHOWS A SHOWER AS WELL. PLEASE CORRELATE.
 SECTIONS 106.1.1, 701.1 & 901.2.1.
  
 33. SHT P14 UNIT F/UNIT H WATER & SANITARY RISERS
 INDICATE A SHOWER IN UNIT H, BUT THE FLOOR PLAN SHOWS A
 TUB. PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 34. SHT P14 UNIT G SANITARY AND WATER RISER DIAGRAMS DO
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS
 106.1.1, 601.1 & 701.1.
  
 35. SHT P15 UNITS Q & R SANITARY & WATER RISER DIAGRAMS
 ARE REVERSE FROM THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 36. SHT P16 ALL SANITARY RISER DIAGRAMS. THE VENT
 STACKS SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK.
 THE VENT SHALL CONNECT TO THE STACK AT OR BELOW THE
 LOWEST HORIZONTAL BRANCH. SECTION 903.4.
  
 37. SHT P16 TYPICAL RISER G SHOWS 9 FU FOR THE 5TH
 FLOOR BUT HAS THE SAME FIXTURES AS ALL THE OTHER FLOORS
 SHOWN AS 14 FU. PLEASE CLARIFY & CORRELATE. TABLE
 710.1(2).
  
 38. SHT P17 TYPICAL RISER B STARTS OUT WITH 1-1/4" COLD
 WATER THEN INCREASES TO 1-1/2" FOR THE NEXT FOUR
 FLOORS. PLEASE CLARIFY. SECTIONS 106.1.1 & 601.1.
  
 39. SHT P18 SHOWS SUMP PUMPS FROM THE ELEVATORS
 CONNECTING DIRECTLY TO THE SANITARY. PER SECTION 301.6
 THIS IS PROHIBITED. IF DRAINING TO THE SANITARY, AN
 INTERCEPTOR MAY BE REQUIRED. AN OUTLET TO PUMP CONTENTS
 INTO A RECPTICLE AND PROPER DISPOSAL AS HAZARDOUS
 MATERIAL IS ACCEPTABLE. PLEASE INDICATE METHOD. SECTION
 106.1.2.
  
 40. SHT P18 FLOOR DRAINS IN THE TOILET ROOMS 130 & 131
 ARE NOT VENTED AS SHOWN. SECTION 901.2.1. THE FLOOR
 DRAINS SHOULD DISCHARGE DOWNSTREAM OF THE VENTED LAVS.
 SECTION 901.2.
  
 41. SHT P18 GREASE INTERCEPTORS SHALL BE SIZED BY THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, LABORATORY
 SUPERVISOR AT HER OFFICE, (561) 822-2271, BY FAX (561)
 822-2279 OR BY E-MAIL [email protected]. A WRITTEN
 DETERMINATION IS REQUIRED FROM THE UTILITY DEPT.
 ARTICLE III SECTION 90-124(7)(F) AND SECTION 1003.
  
 42. SHT SHT P18 PLEASE INDICATE WHAT WILL DRAIN INTO
 THE TRENCH DRAIN. IF STORM WATER, THEN IT MUST CONNECT
 TO THE STORM SYSTEM AND THE AIR ADMITTANCE VALVE,
 (STUDOR VENT), IS NOT REQUIRED. ARTICLE III SECTION
 90-124(6). IF SANITARY DRAINAGE THE AAV IS REQUIRED TO
 HAVE A RELIEF VENT PER SECTION 917.13.2. PLEASE
 CLARIFY.
  
 43. SHT P18 INDICATE WHERE THE CONTINUATION FOR THE
 SANITARY RISER A1 CAN BE LOCATED. SECTIONS 106.1.2 &
 701.1.
  
 44. SHT P19 3" FLOOR DRAIN WITH SEDIMENT BUCKET (2FU).
 INDICATE HOW THE STORM WATER WILL BE KEPT OUT OF THE
 SANITARY SYSTEM. (DRAIN NOT REQUIRED). ARTICLE III
 90-124 (6). ALSO THE AIR ADMITTANCE VALVE, (STUDOR
 VENT), REQUIRES A RELIEF VENT PER SECTION 917.3.1.
  
 45. SHT P19 CLEANOUTS ARE REQUIRED AT THE BASE OF ALL
 STACKS. SECTION 708.3.4.
  
 46. SHT P25 SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE PERMIT:
  
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 B. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (FOR DRYERS)
  
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 E. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (MANUAL VALVE AND UNION
 NOT SHOWN).
  
 47 SHT P25 THE GAS PIPING SHALL BE SIZED BY FBC-2004
 FUEL GAS OR SUBMIT A COPY OF THE TABLE USED. THE SOURCE
 OF THE TABLE SHALL BE INDICATED ON THE TABLE.
  
 48. SHT P26 PLUMBING RWL 2ND FLOOR. PLEASE INDICATE IF
 THE RISER ENDS ON THE 2ND FLOOR OR CONTINUES UP TO THE
 3RD & 4TH FLOORS AS INDICATED ON THE RWL RISER DIAGRAM
 1ST FLOOR GARAGE. CLARIFY. SECTIONS 106.1.1 & 1101.1.
  
 49. SHT P26 VERIFY SQUARE FOOTAGE ON 8" 90785 SF AND
 ACCUMULATED BELOW. (SEE SHT P27). SECTIONS 106.1.1 &
 TABLE 1106.3.
  
 50. SHT P27 RECHECK ADDITION ON 6" DOWNSTREAM OF 6"
 (2157 SF) ON RWL 4TH FLOOR GARAGE AND DOWNSTREAM.
 SECTION 106.1.1 & TABLE 1106.3.
  
 51. SHT P27 RISER DIAGRAM 3RD FLOOR PLEASE INDICATE IF
 THE RISER ENDS ON THE 2ND FLOOR OR CONTINUES UP TO THE
 3RD & 4TH FLOORS AS INDICATED ON THE RWL RISER DIAGRAM
 1ST FLOOR GARAGE. CLARIFY. SECTIONS 106.1.1 & 1101.1.
  
 52. SHT P29 SEE ATTACHED COPY OF THE CITY WPB UNITLIY
 DETAIL FOR GREASE INTERCEPTORS. GREASE INTERCEPTOR
 DETAIL SHALL BE APPROVED BY THE UTILITY DEPT. OR GREASE
 INTERCEPTOR DETAIL SHALL REFLECT APPROVED DETAIL.
 SECTION 1003.2.
  
 53. SHT P30 SAFE WASTE DETAILS FCO & FD. PER SECTION
 1002.1 DOUBLE TRAPING IS PROHIBITED. PLEASE CHANGE
 DETAILS.
  
 54. SHT P30 ICE MACHINE DETAIL. THE WATER FILTER SHALL
 MEET THE REQUIREMENTS OF NSF 42. SECTION 611.1.
  
 55. SUBMIT A CONDENSATE BUILDING ISOMETRIC RISER
 DIAGRAM AND CONDENSATE RISER DIAGRAMS SHOWING ALL PIPE
 SIZES, TRAPS, VENTS, AND INDICATE MATERIAL. SECTIONS
 106.3.5.1.3 & 314.2.2.
  
 56. CONDENSATE IS SHOWN TERMINATING AT THE CATCH BASINS
 IN THE FIRST FLOOR GARAGE. CONCERNS FOR THE POSSIBILITY
 OF THE EXHAUST FUMES ENTERING THE UNITS SHALL BE
 ADDRESSED. PLEASE INDICATE HOW THIS WILL BE ADDRESSED.
 SECTION 106.1.2 (MORE INFORMATION REQUIRED).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ******IMPORTANT****** PLEASE RESUBMIT PLUMBING PLANS
 WITH THE HIGHLIGHTED SHEETS TO HELP EXPEDITE FUTURE
 PLAN REVIEWS. THANK YOU
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-01-12 Cont ID  
Sent By mflis Date 2009-01-15 Time   Rev Time 0.00
Received By mflis Date 2009-01-15 Time 09:08 Sent To  
Notes
2009-01-15 09:09:01ZONING REVIEW: FAILED
  
 ** PLAN REVIEW**
  
 1) UNITY OF TITLE WILL REQUIRED WITH BUILDING PERMIT
 SUBMISSION.
 2) THE PROJECT WILL BE REQUIRED TO BE REPLATTED PRIOR
 TO CERTIFICATE OF OCCUPANCY; PLEASE CONTACT VINCE NOEL
 AT 561 494-1040.
 3) TDR CERTIFCATE FOR INCENTIVE DEVELOPMENT AREA SHALL
 BE REQUIRED.
 3) TREE REMOVAL PERMIT APPROVAL SHALL BE REQUIRED FOR
 RELOCATION OF EXISTING TREES WHICH OCCUR ON THE SITE.
 PLEASE COORDINATE WITH ROBERT KUSSNER, LANDSCAPE
 PLANNER, AT (561) 822-1435.
 4) LP-1 - THE HIBISCUS STREET LANDSCAPE PLAN SHALL BE
 MODIFIED IN COORDINATION WITH CITY LANDSCAPE PLANNER TO
 ACCOMMODATE DATE PALMS AND ADJUST PLANT MATERIALS AT
 DRIVEWAY BULB-OUTS.
 5) C-4 - LIGHT POLES ARE INDICATED TO BE
 RELOCATED.STREET LIGHT POST AND FIXTURE SHALL BE CITY
 STANDARD - ?LUMEC? CAT.
 #175MH-L50-PCFC-SE3-OTA/240V-SFO-1-BKTX (BLACK): MOGUL
 BASE; POST TOP MOUNTING; LAMP CENTER IS 17?-0? ABOVE
 GRADE HEIGHT, OR SIMILAR AS APPROVED BY THE CITY.
 6) C-6 - LIGHT POLES SHALL BE ALIGNED WITH THE CENTER
 POINT OF STREET TREES (NORTH TO SOUTH).
 7) A1.01 - PROVIDE DIMENSIONS FROM BUILDING TO PROPERTY
 LINE ON ALL SIDES, AND BUILDING FACE TO BACK OF CURB ON
 HIBISCUS STREET AT SEVERAL LOCATIONS.
 8) A2.02 (AND OTHERS) - ALL COMPACT SPACES SHALL BE
 MARKED AS "COMPACT" ON THE PAVING OR WITH VERTICAL
 SIGNAGE.
 9) A2.02 - WILL BOLLARDS BE REQUIRED IN FRONT ON DOOR
 204? PLEASE CONFIRM. NO BOLLARDS SHALL BE PLACED IN ADA
 ACCESSIBLE ROUTES OR SIDE AILES IN ANY LOCATION.
 10) A2.02 (AND OTHERS) - PROVIDE A DIMENSION STRING
 INDICATING DEPTH OF PARKING SPACES IN A FEW LOCATIONS
 AND FOR STANDARD AND COMPACT SPACES.
 11) PLANS SHALL INDICATE TRASH STAGING AND PICK-UP
 LOCATIONS SPECIFICALLY. PLEASE PROVIDE A NOTE THAT
 DESCRIBES HOWN THE PICK PROCESS WILL OPERATION FOR
 REVIEW AND CONFIRMATION BY ENGINEERING SERVICES.
 12) PHOTOMETRICS FOR SIDEWALK AREAS ALONG HIBISCUS
 SHALL BE PROVIDED.
 13) C-6- CONFIRM ALL SLOPES AND TRANSITIONS FROM
 BUILDING TO SIDEWALK. NO RAILINGS OR ACCESS RAMPS ARE
 PERMITTED IN PUBLIC SIDEWALK.
 14) CONFIRM COMPLIANCE WITH DAC CASE APPROVAL FOR ALL
 VARIANCES.
 15) LP-1- ON EAST SIDE OF BUILDING AT STREET, WILL A
 FENCE OR GATE BE PROVIDED TO PREVENT PEOPLE FROM
 WALKING BACK TO THE BREAKFAST AREA? UNCLEAR IN THESE
 DRAWINGS, THOUGH HEDGING IS INDICATED.
 16) CONFIRM THAT ADA VAN ACCESSIBLE HEIGHTS ARE
 PROVIDED. INDICATE IN BUILDING SECTIONS.
 17) ANY CANOPIES OR OTHER ARCHITECTURAL FEATURES WHICH
 IMPINGE UPON THE RIGHT-OF-WAY WILL REQUIRE AIR RIGHTS
 EASEMENTS.
 18) BUILDING SIGNAGE SHALL COMPLY WITH CITY
 REQUIREMENTS AND SHALL REQUIRE A SEPARATE BUILDING
 PERMIT SUBMITTAL.
  
 MATT FLIS - 822-1445
  
  