Plan Review Details - Permit 08120528
Plan Review Stops For Permit 08120528
Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-07-02 Cont ID  
Sent By mawillia Date 2009-07-02 Time 14:49 Rev Time 0.00
Received By mawillia Date 2009-07-02 Time 13:07 Sent To  
Notes
2009-07-02 13:47:40*****REVISION (NEW ENGINEER OF RECORD - DATED
 6/15/2009, APPROVED*****
  
  
 THIS REVISION REFLECTS A CHANGE IN THE ENGINEER OF
 RECORD (FROM EDGARDO CORDOBA, P.E. TO JAMES M. CURTIS,
 P.E.) ONLY, NO PIPING REVISIONS. REVISED PLAN SHEETS
 FP1 THRU FP7 WERE STAMPED, INITIALED, AND DATED

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-06-23 Cont ID  
Sent By mwennerg Date 2009-06-23 Time 14:50 Rev Time 0.00
Received By mwennerg Date 2009-06-23 Time 14:50 Sent To  
Notes
2009-06-23 14:52:06REVISION #3 DATED 6/5/09 SHEET FP3 OF 7.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-03-31 Cont ID  
Sent By mawillia Date 2009-03-31 Time 11:44 Rev Time 0.00
Received By mawillia Date 2009-03-31 Time 10:42 Sent To  
Notes
2009-03-31 11:11:03*****REVISION #2, APPROVED*****
  
  
 REVISED PLAN SHEETS FP2 THRU FP7 WERE STAMPED,
 INITIALED, AND DATED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-03-12 Cont ID  
Sent By mwennerg Date 2009-03-12 Time 10:11 Rev Time 0.00
Received By mwennerg Date 2009-03-12 Time 10:11 Sent To  
Notes
2009-03-12 10:12:29STANDPIPE CONNECTIONS TO BE 2 1/2"-1 1/2" REDUCER WITH
 CHAIN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-01-12 Cont ID  
Sent By mawillia Date 2009-01-12 Time 22:43 Rev Time 0.00
Received By mawillia Date 2009-01-12 Time 22:42 Sent To  
Notes
2009-01-12 22:52:49*****DENIED****
  
  
 1. THE ACTUAL SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. KNOX LOCKING CAPS WILL REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS. INCLUDE COMMENT TO AN
 APPROPIATE PLAN SHEET. FOR APPLICATIONS CONTACT WEST
 PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
  
 3. IN ADDITION TO ELECTRONIC SWITCHES, CHAIN AND LOCK
 WILL BE REQUIRED ON THE DOUBLE DETECTOR CHECK VALVE
 ASSEMBLY. INCLUDE COMMENT ON AN APPROPIATE PLAN SHEET.
  
 4. A FIRE SPRINKLER PIPE INSPECTION (CODE:603) SHALL BE
 REQUIRED AS PER WEST PALM BEACH CONSTRUCTION SERVICES
 DEPARTMENT.
  
 5. SAFETY MARGIN ON THE SPRINKLER SYSTEM SHALL BE NO
 LESS THAN 5.0 PSI; HYDRAULIC CALCULATIONS SHOWS A PSI
 OF 2.492 ON PAGE 2 OF FP4 - 5TH FLOOR CORRIDOR .
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-06-22 Cont ID  
Sent By rmcdouga Date 2009-06-22 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2009-06-22 Time 08:42 Sent To  
Notes
2009-06-22 08:42:59SENT TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-18 Cont ID  
Sent By adarroug Date 2009-03-18 Time 09:43 Rev Time 0.00
Received By adarroug Date 2009-03-18 Time 09:43 Sent To FIRE
Notes
2009-03-18 09:43:16TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-02 Cont ID  
Sent By adarroug Date 2009-03-02 Time 13:09 Rev Time 0.00
Received By adarroug Date 2009-03-02 Time 13:09 Sent To FIRE
Notes
2009-03-02 13:09:26TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-12 Cont ID  
Sent By mawillia Date 2009-01-12 Time 22:43 Rev Time 0.00
Received By mawillia Date 2008-12-26 Time 10:51 Sent To  
Notes
2008-12-26 10:51:36TO "F" BOX