Plan Review Details - Permit 08120521
| Plan Review Stops For Permit 08120521 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-03-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-03-02 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-03-02 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2009-03-02 16:32:10 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. A SHUTTER PRODUCT APPROVAL WAS PROVIDED. PLEASE | | | COMPLETE THE ATTACHED INSTALLATION SCHEDULE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-01-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-01-02 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-01-02 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2009-01-02 10:43:10 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE. | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3, | | | PROVIDE CALCULATIONS. | | | | | | 2. ON THE FLOOR PLAN SHOW: WINDOW LOCATIONS, SIZES, | | | WINDOW TYPE, ROOM DESIGNATIONS; DOOR LOCATIONS. NOTE | | | EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE | | | FOR BEDROOMS, FBC R310, FBC EB 505.1. THE CLEAR OPENING | | | FOR BEDROOMS CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | 3. IT APPEARS THAT OPENINGS C AND D ON THE FLOOR PLAN | | | ARE DOORS; IS THIS CORRECT? PLEASE REVISE TO SPECIFY | | | "DOORS" OR GRAPHICALLY SHOW A DOOR IN THESE LOCATIONS | | | USING STANDARD ARCHITECTURAL GRAPHICS. FBC*106. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2009-02-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-02-19 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-02-19 |
Time |
10:45 |
Sent To |
B |
|
| Notes |
| 2009-02-19 10:52:14 | | | | | | | NO ELECTRICAL PLANS SUBMITTED, NO RESPONSE TO REVIEW | | | COMMENTS OTHER THAN THE DESCRIPTION OF THE PROJECT HAS | | | CHANGED. THERE IS NO ELECTRICAL WORK TO BE DONE UNDER | | | THIS PERMIT./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-12-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-12-30 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-12-30 |
Time |
09:43 |
Sent To |
B |
|
| Notes |
| 2008-12-30 09:51:16 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED | | | WITH THE APPLICATION. 106.1 FBC AS AMENDED. "REPAIR | | | ELECTRICAL" IS STATED IN THE DESCRIPTION ON THE | | | APPLICATION BUT NO PLANS WERE SUBMITTED. HAND DRAWN | | | PLANS ARE NOT ACCEPTABLE FOR RECORD RETENTION OR | | | CLARITY IN THE FIELD. 106.1.3 FBC AS AMENDED. | | | | | | 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE | | | PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-02-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-18 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-18 |
Time |
13:43 |
Sent To |
E |
|
| Notes |
| 2009-02-18 13:43:39 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-01-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-01-02 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-12-24 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2008-12-24 09:42:11 | TO "E" BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|