Plan Review Details - Permit 08120508
Plan Review Stops For Permit 08120508
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-09 Cont ID  
Sent By jgomez Date 2009-04-09 Time 14:22 Rev Time 0.00
Received By jgomez Date 2009-04-09 Time 14:22 Sent To  
Notes
2009-04-09 14:26:14RESIDENTIAL (R3) ALTERATION BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 **NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY TO CHECK IF IMPACT FEES ARE DUE. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 (REPEAT COMMENT). PLANS SUBMITTED NEED TO HAVE PALM
 BEACH COUNTY IMPACT FEES STAMP.
  
 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) STORM SHUTTERS. (REPEAT COMMENT). NONE SUBMITTED.
 IT'S NO CLEAR IF DOORS ARE GOING TO NEED HAVE IMPACT
 GLAZING OR NOT. THERE WAS NO PRODUCT APPROVAL SUBMITTED
 FOR DOUBLE FRENCH DOORS AND PRODUCT APPROVAL SUBMITTED
 FOR SINGLE DOOR (ENTRY?) REQUIRES SHUTTERS. CLARIFY AND
 COORDINATE PRODUCT APPROVALS ACCORDINGLY.
  
 ** IF SHUTTERS ARE REQUIRED, THEN PROVIDE COMPLETE
 INSTALLATION SCHEDULE. (REPEAT COMMENT). SEE ATTACHED
 SAMPLE. AND CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC
 MOUNTING CONDITIONS WALL SECTION (EG: WALL MOUNT, BUILD
 OUT, ETC) AND SPECIFIC ANCHOR TYPE AND SPACING TO BE
 USED TO VERIFY COMPLIANCE WITH THE PRODUCT APPROVAL AND
 CALCULATED DESIGN PRESSURES.
  
 B) ENTRY DOOR AS SHOWN ON FLOOR PLANS. (REPEAT
 COMMENT). PRODUCT APPROVAL FL5114 SUBMITTED IS FOR
 GLAZED DOOR. FLOOR PLANS SHOW SOLID DOOR.
 CLARIFY/REVISE AS REQUIRED. THIS GLAZED DOOR REQUIRES
 SHUTTERS.
 COORDINATE WITH ITEM #3A ABOVE.
  
 C) PAIR OF FRENCH DOORS AS SHOWN ON PLANS. NONE
 SUBMITTED AT THIS TIME. (REPEAT COMMENT).
  
 D) FLAT ROOF ASSEMBLY. (REPEAT COMMENT). THERE WAS NOT
 PRODUCT APPROVAL SUBMITTED. COORDINATE WITH ITEM # D(2)
 BELOW.
  
 NOTE: ON FLAT ROOF PRODUCT APPROVAL SPECIFY AND PROVIDE
 THE FOLLOWING:
 *CLEARLY SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. SEE LIST OF APPROVED ASSEMBLIES ON PRODUCT
 APPROVAL. (REPEAT COMMENT).
  
 **CLEARLY SPECIFY WHICH FASTENING OPTION IS GOING TO BE
 USED TO FASTEN THE FLAT ROOF BASE SHEET. (REPEAT
 COMMENT).
  
 *** ENGINEER'S RAS 117 CALCULATIONS SUBMITTED:
 (1) ROOFING SYSTEM: THERE IS NOT WARRIOR ROOFING
 MANUFACTURER MODIFIED ROOF SYSTEM. SEE PRODUCT APPROVAL
 AND REVISE AS REQUIRED. REFER TO PRODUCT APPROVAL
 SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED AND REVISE
 AS REQUIRED.
  
 (2) PRODUCT APPROVAL: NOA #07-0111.03 WAS SUPERSEDED BY
 NOA 07-0730.03. SEE ATTACHED COPY FROM MIAMI-DADE
 WEBSITE. PROVIDE CURRENT NOA.
  
 (3) WHERE IS THE MAXIMUM DESIGN PRESSURE OF 525 LBS/FT2
 TAKEN FROM?. SEE PRODUCT APPROVAL.
  
 (4) NAIL ENHANCING DESCRIPTION IS NOT CLEAR. PROVIDE
 SKETCH SHOWING NAIL ENHANCING. COORDINATE WITH PRODUCT
 APPROVAL.
  
 (5) CLARIFY WHERE IS THE FM APPROVED, ASTM D-4601, TYPE
 112 AND UL INFORMATION DESCRIBED IN THE LAST PARAGRAPH
 TAKEN FROM? AND COORDINATE INFORMATION WITH PRODUCT
 APPROVAL SUBMITTED.
  
 E) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5- BRING ANY REVISED PLANS FOR HISTORIC REVIEW APPROVAL
 STAMP PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 6- SHEET 4.1:
 A) CLARIFY WHAT'S CONNECTOR #22. SHOWN ON ROOF FRAMING
 PLAN. WHAT'S LUS10 AS SHOWN ON CONNECTOR SCHEDULE?.
 (REPEAT COMMENT. NOT ADDRESSED). UNABLE TO FIND THIS
 CONNECTOR. SEE MANUFACTURER CATALOG AND REVISE AS
 REQUIRED.
  
 B) COMPONENT AND CLADDING PRESSURE ZONES (REPEAT
 COMMENT): REVISE INTERMEDIATE NAILING SPACING ON ROOF
 ZONE 3. NEED TO BE 4"O.C. ALSO, REVISE INTERMEDIATE
 NAILING SPACING FOR ROOF ZONE 1 AND 2 (6"O.C.). SEE
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE AND
 REVISE AS REQUIRED.
  
 C) NEED TO PROVIDE ROOF CROSS VENTILATION AS REQUIRED
 BY SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. THERE
 ARE 2 VENTILATION OPENINGS SPECIFIED. THEY DON'T
 PROVIDE ROOF CROSS VENTILATION BECAUSE ROOF FRAMING
 PLANS SHOWS 2X12 SOLID ROOF RAFTERS. (REPEAT COMMENT).
 NOTE ON SHEET 4.1 REGARDING NEW BEAM OPEN TO EXISTING
 RAFTERS TO PROVIDE CROSS VENTILATION DOESN'T RESOLVE
 THE CROSS VENTILATION ISSUE. LOCATION OF VENTS ON NORTH
 AND SOUTH ELEVATIONS ONLY PROVIDE VENTILATION AT THE
 END ROOF RAFTERS. AND THERE IS NOT VENTILATION PROVIDED
 FOR INTERIOR ROOF RAFTERS. SEE SEC. R806.2 FOR
 ALTERNATIVE WAY OF COMPLYING WITH THIS SECTION AND
 REVISE AS REQUIRED. ALSO, USING ICYNENE INSULATION MAY
 BE ANOTHER ALTERNATIVE. IF USING ICYNENE, THEN PROVIDE
 MANUFACTURER SPECIFICATIONS AND COORDINATE WITH ENERGY
 CALCULATIONS.
  
 D) CLARIFY ROOF SCUPPERS AND ROOF DRAINS. (REPEAT
 COMMENT). CLARIFICATION OF SIZES WAS REQUESTED ON
 PREVIOUS CHECKLIST. SIZES WERE REVISED BUT OVERFLOW
 SCUPPER CAN'T BE 2" MAX. ABOVE ROOF DECK AND JUST ABOVE
 ROOF DRAIN IF ROOF DRAIN IS 4"X12". REVISE AS REQUIRED
 TO COMPLY WITH SEC. R903.4 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 7- SHEET 5.1:
 A) EXTERIOR DOOR HEAD JAMB DETAIL. REVISE SIZE OF
 STRUCTURAL BUCK. 1X4 STRUCTURAL BUCK IS NOT ADEQUATE TO
 PROVIDE DOOR FRAME FULL SUPPORT AS REQUIRED BY SEC.
 R613.6 OF 2004 FLORIDA RESIDENTIAL CODE. ALSO, SEE
 PRODUCT APPROVAL FOR FRAME SIZE. (REPEAT COMMENT). SIZE
 WAS CHANGED FROM 2X4 TO 1X4. STILL THE WIDTH OF THIS
 BUCK DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME.
 REVISE AS REQUIRED.
  
 B) COMPONENTS AND CLADDING PRESSURES ZONES. CLARIFY WHY
 NAILING SPACING (4" AND 6") IS MORE STRICT FOR WALL
 ZONE 4 THAN WALL ZONE 5 (6" AND 12"). ON THE OTHER
 HAND, WALLS IN THIS PROJECT ARE MASONRY WALLS, NOT WOOD
 FRAMED WALLS.
  
 8- SHEET 6.1, TYPICAL WALL SECTION:
 A) CLARIFY SPECS GIVEN FOR THE FLAT ROOF ASSEMBLY. SEE
 PRODUCT APPROVAL FOR CORRECT INFORMATION. INFORMATION
 SUBMITTED IS FOR PITCHED ROOFS, NOT FOR LOW SLOPE
 ROOFS. REVISE AS REQUIRED. (REPEAT COMMENT).
 UNDERLAYMENT SPECIFICATIONS NEED TO BE COORDINATED WITH
 SELECTED APPROVED FLAT ROOF ASSEMBLY. REVISE
 SPECIFICATIONS AS REQUIRED.
  
 9- REVISE ENERGY CALCULATIONS:
 A) PROVIDE PROJECT ADDRESS AND COMPLETE ALL THE
 INFORMATION ON TOP OF FORM. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 B) ARE THE ENERGY CALCULATIONS FOR THE ENTIRE HOUSE OR
 FOR AREA OF WORK ONLY. IS NEW INSULATION PROVIDED FOR
 THE ENTIRE HOUSE IN WALLS AND CEILINGS. ALSO, SEE TYPE
 OF WALLS ON EXISTING STRUCTURE. THIS INFORMATION IS NOT
 SHOWN ON PLANS. (REPEAT COMMENT. NOT ADDRESSED).
  
 C) PROVIDE COMPLETE MANUFACTURER'S SPECIFICATIONS
 SHOWING THE U-FACTOR AND SHGC FACTOR SHOWN ON ITEMS 7A
 AND 7B WHEN THE DEFAULT FACTOR IS NOT USED. (IN
 ADDITION WINDOWS AND DOORS NEED TO SHOW SUCH RATING FOR
 INSPECTION AFTER INSTALLATION). (REPEAT COMMENT. NOT
 ADDRESSED).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-16 Cont ID  
Sent By jgomez Date 2009-01-16 Time 17:00 Rev Time 0.00
Received By jgomez Date 2009-01-16 Time 17:00 Sent To PC
Notes
2009-01-16 17:04:57RESIDENTIAL (R3) ALTERATION BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 **NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY TO CHECK IF IMPACT FEES ARE DUE. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) STORM SHUTTERS:
 *PROVIDE COMPLETE PRODUCT APPROVAL REPORT AND MAKE SURE
 DRAWINGS MATCH FLORIDA PRODUCT APPROVAL REPORT.
 DRAWINGS SUBMITTED (05-270) DON'T MATCH FLORIDA PRODUCT
 APPROVAL FL6968.
  
 **PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED
 SAMPLE. AND CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC
 MOUNTING CONDITIONS WALL SECTION (EG: WALL MOUNT, BUILD
 OUT, ETC) AND SPECIFIC ANCHOR TYPE AND SPACING TO BE
 USED TO VERIFY COMPLIANCE WITH THE PRODUCT AND
 CALCULATED DESIGN PRESSURES.
 NOTE: SEE REVISED DESIGN PRESSURES PRIOR TO COMPLETING
 INSTALLATION SCHEDULE. SEE ITEM 10B BELOW.
  
 B) "INSWING" ENTRY DOOR AS SHOWN ON FLOOR PLANS.
 CLARIFY IF PRODUCT APPROVAL FL5114 SUBMITTED IS THE ONE
 GOING TO BE INSTALLED ON THE FRONT DOOR.
 NOTE: THIS DOOR REQUIRES SHUTTERS. COORDINATE WITH ITEM
 #3A ABOVE.
  
 C) PAIR OF FRENCH DOORS AS SHOWN ON PLANS. NONE
 SUBMITTED AT THIS TIME.
  
 D) FLAT ROOF ASSEMBLY. PRODUCT APPROVAL SUBMITTED (NOA
 06-0105.04) IF FOR CLAY ROOFING TILE. THERE IS NOT CLAY
 TILE SHOWN ON DRAWINGS. ALSO, THE OTHER PRODUCT
 APPROVAL SUBMITTED (NOA 06-0113.03) IS FOR PITCHED ROOF
 UNDERLAYMENT ONLY.
 NOTE: ON FLAT ROOF PRODUCT APPROVAL SPECIFY AND PROVIDE
 THE FOLLOWING:
 *CLEARLY SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. SEE LIST OF APPROVED ASSEMBLIES ON PRODUCT
 APPROVAL.
  
 **CLEARLY SPECIFY WHICH FASTENING OPTION IS GOING TO BE
 USED TO FASTEN THE FLAT ROOF BASE SHEET.
  
 ***PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 FOR NAIL ENHANCING AT PERIMETER AND
 CORNER AREAS. SEE GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA. IF CALCULATIONS NEED TO BE SIGNED AND SEALED, THEN
 PROVIDE SUCH INFORMATION SIGNED AND SEALED.
 NOTE: GENERAL LIMITATION #9 CAN'T BE USED IN THIS JOB.
  
 E) SINGLE HUNG WINDOWS. INFORMATION SUBMITTED IS
 MISSING THE PRODUCT APPROVAL COVER PAGE WITH THE
 FLORIDA PRODUCT APPROVAL NUMBER.
 ALSO, DRAWINGS ARE NOT LEGIBLE. NEED TO PROVIDE LEGIBLE
 DRAWINGS.
  
 F) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 G) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND SHEET WHERE THE CONNECTOR IS SHOWN. THIS
 APPLIES TO CONNECTORS ONLY. OTHER PRODUCT APPROVALS
 NEED TO PROVIDE COMPLETE REPORT. VISIT
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL FLORIDA PRODUCT
 APPROVALS.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5- BRING ALL REVISED PLANS FOR HISTORIC REVIEW APPROVAL
 STAMP PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 6- SHEET 2.1: CLARIFY WHY THERE IS NOT FILLED CELLS AND
 VERTICAL REINFORCEMENT SHOWN ON SOUTH WALL.
 ALSO, SPECIFY VERTICAL REINFORCEMENT SPACING ON THE
 OTHER WALLS AS REQUIRED BY SEC. R609.3.3 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7 SHEET 3.1: REVISE DESIGN PARAMETERS SPECIFICATIONS.
 REFERENCE ASCE 7-02 WHICH IS THE CURRENT CODE, NOT ASCE
 7-05.
  
 8- SHEET 4.1:
 A) CLARIFY WHAT'S CONNECTOR #22. SHOWN ON ROOF FRAMING
 PLAN. WHAT'S LUS10 AS SHOWN ON CONNECTOR SCHEDULE?.
  
 B) SPECIFY SIZE OF NEW 2 PLY GIRDER SHOWN ON ROOF
 FRAMING PLAN WHERE EXISTING ROOF MEETS NEW ROOF.
 ALSO, SPECIFY CONNECTION AT BOTH ENDS TO VERIFY
 COMPLIANCE WITH CALCULATED UPLIFT PRESSURES OF SEC.
 R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) CLARIFY WHY IS THERE A NOTE ON ROOF FRAMING PLAN
 SAYING AREA OF REMODEL AND 2ND FLOOR. THIS IS ONLY A
 ONE STORY CONSTRUCTION.
  
 D) COMPONENT AND CLADDING PRESSURE ZONES IS MISSING THE
 NAILING AT INTERMEDIATE SUPPORTS FOR ROOF ZONE #3. SEE
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 MIN. TYPE AND NAILING REQUIRED FOR ROOF ZONE #3.
  
 E) REVISE/CLARIFY GENERAL ROOF NOTE #7. COORDINATE WITH
 ITEM 9D ABOVE.
  
 F) NEED TO PROVIDE ROOF CROSS VENTILATION AS REQUIRED
 BY SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. THERE
 ARE 2 VENTILATION OPENINGS SPECIFIED. THEY DON'T
 PROVIDE ROOF CROSS VENTILATION BECAUSE ROOF FRAMING
 PLANS SHOWS 2X12 SOLID ROOF RAFTERS.
  
 G) CLARIFY SIZE OF ROOF SCUPPERS. ROOF DRAIN SECTION
 CALLS FOR 4"X12" SCUPPERS, WHILE NOTE BY ROOF FRAMING
 PLAN CALLS FOR 6"X14" SCUPPERS.
  
 9- SHEET 5.1:
 A) EXTERIOR DOOR HEAD JAMB DETAIL. REVISE SIZE OF
 STRUCTURAL BUCK. 2X4 STRUCTURAL BUCK IS NOT ADEQUATE TO
 PROVIDE DOOR FRAME FULL SUPPORT AS REQUIRED BY SEC.
 R613.6 OF 2004 FLORIDA RESIDENTIAL CODE. ALSO, SEE
 PRODUCT APPROVAL FOR FRAME SIZE.
  
 B) DESIGN PRESSURES SHOWN ON COMPONENTS AND CLADDING
 DON'T CORRESPOND TO EXPOSURE "C". REVISE DESIGN
 PRESSURES AS REQUIRED.
  
 C) CLARIFY WHY ALL EXTERIOR ELEVATIONS MAKE REFERENCE
 TO NEW 2ND STORY. THERE IS NO 2 STORY CONSTRUCTION ON
 THIS PROJECT.
  
 10- SHEET 6.1, TYPICALL WALL SECTION:
 A) CLARIFY SPECS GIVEN FOR THE FLAT ROOF ASSEMBLY. SEE
 PRODUCT APPROVAL FOR CORRECT INFORMATION. INFORMATION
 SUBMITTED IS FOR PITCHED ROOFS, NOT FOR LOW SLOPE
 ROOFS. REVISE AS REQUIRED.
  
 B) REVISE INFORMATION REGARDING ROOF TRUSSES AT
 24"O.C.. SEE ROOF FRAMING PLAN FOR FRAMING MEMBERS
 SPECIFIED.
  
 C) SPACING FOR 2X10 LEDGER ANCHORS DON'T MATCH
 INFORMATION GIVEN ON ROOF FRAMING PLAN. REVISE AS
 REQUIRED.
  
 D) REVISE NOTE REGARDING TWO STORY CONSTRUCTION.
  
 11- REVISE ENERGY CALCULATIONS:
 A) PROVIDE PROJECT ADDRESS AND COMPLETE ALL THE
 INFORMATION ON TOP OF FORM.
  
 B) ARE THE ENERGY CALCULATIONS FOR THE ENTIRE HOUSE OR
 FOR AREA OF WORK ONLY. IS NEW INSULATION PROVIDED FOR
 THE ENTIRE HOUSE IN WALLS AND CEILINGS. ALSO, SEE TYPE
 OF WALLS ON EXISTING STRUCTURE. THIS INFORMATION IS NOT
 SHOWN ON PLANS.
  
 C) PROVIDE COMPLETE MANUFACTURER'S SPECIFICATIONS
 SHOWING THE U-FACTOR AND SHGC FACTOR SHOWN ON ITEMS 7A
 AND 7B WHEN THE DEFAULT FACTOR IS NOT USED. (IN
 ADDITION WINDOWS AND DOORS NEED TO SHOW SUCH RATING FOR
 INSPECTION AFTER INSTALLATION).
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 12- SOIL TEST REPORT SUBMITTED TO BE ADDRESSED TO
 CORRECT BUILDING DEPARTMENT AND ADDRESS. THIS IS THE
 CITY OF WEST PALM BEACH, NOT PALM BEACH COUNTY. AND
 CORRECT ADDRESS IS 200 2ND STREET, WPB, FL 33401.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-04-09 Cont ID  
Sent By dpalmer Date 2009-04-09 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2009-04-09 Time 15:40 Sent To  
Notes
2009-04-09 15:41:01** DENIED**
  
 1) NOTE: 2ND TIME, NO DESIGNER OF RECORD ON PLANS.
 PLEASE SEE FS 481.229, 471.003 WHEN MEETING EXCEPTIONS
 DESIGNER/ PERSON RESPONSIBLE FOR PLANS MUST PRINT
 NUMBER, ANY LICENSE NUMBER AND SIGN PLANS.
 PLANS DO NOT SHOW ANY DESIGNER OF RECORD.
  
 2) NOTE: 2ND TIME: PLANS SHOW A 5KW INSTANT TYPE WATER
 HEATER HOWEVER A 5KW UNIT WILL NOT HEAT WATER IN A
 HOUSE OF THIS SIZE. TYPICALLY A 5KW UNIT INSTANT TYPE
 APPLIANCE WILL BE FOR A SINGLE POINT OF USE ONLY.
 PLEASE ALSO SEE THE PANEL SCHEDULE STATES 50AMP
 BREAKER. IF THE UNIT WAS 5KW THE 50AMP OCP IS TOO HIGH
 PER 422.11.
 PLEASE SEE LISTING OF UNIT BEING PROPOSED. 110.3
 240.4,310.16 AND PLEASE BE SURE TO REVISE LOAD
 CALCULATIONS ACCORDING TO NEW UNIT.
  
 3) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW ALSO AS
 ALL REQUIRE SMALL APPLIANCE TYPE CIRCUITS. PLANS SHOW
 ALL COUNTER SPACE GFI RECEPTACLES ON ONE OF THE SMALL
 APPLIANCE CIRCUITS. THIS COULD HAVE BEEN A REDLINED
 ITEM HOWEVER PLANS ARE COMING BACK FOR OTHER COMMENTS.
 SEE 210.11C1, 210.52B1, 220.53
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-31 Cont ID  
Sent By dpalmer Date 2008-12-31 Time 11:25 Rev Time 0.00
Received By dpalmer Date 2008-12-31 Time 11:25 Sent To M
Notes
2008-12-31 11:25:38** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FS 481.229, 471.003. WHEN MEETING
 EXCEPTIONS IN THE STATUTES AS MENTIONED PLANS ARE STILL
 REQUIRED TO BE DONE BY THE DESIGN PROFESSIONAL AS
 LISTED.
 THE PLANS SUBMITTED DO NOT CONTAIN ANY TITLE BLOCKS,
 PRINTED NAME, SIGNATURE, OR SIGNED AND SEALED.
  
 2) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 FOR
 REQUIRED LOADS ON CIRCUITS FOR SMALL APPLIANCES, DINING
 AND BREAKFAST ROOM. THE TWO SMALL APPLIANCE CIRCUITS
 ARE SHOWN WITH THE 1.5KVA HOWEVER NOT THE OTHER TWO.
  
 3) NOTE: PLEASE SEE 210.63,210.8A FOR MISSING GFI FOR
 CONDENSING UNIT.
  
 4) NOTE: PLEASE VERIFY THE SIZE OF THE PROPOSED
 INSTA-HOT. IT IS NOT TYPICAL THAT THIS SMALL OF THIS
 TYPE OF UNIT WILL FEED ALL LOCATIONS ON THE PLANS AS
 SHOWN.
 THE MANUFACTURE OF THE EQUIPMENT SHOULD HAVE
 INFORMATION ON THE SIZE OF THE UNIT AND HOW THIS WILL
 WORK WITH PROPOSED.
 THIS IS ONLY NOTED AS THIS IS NOT AN ELECTRICAL
 VIOLATION AS SHOWN ON PLANS.
 HOWEVER IF THE UNIT IS INDEED LARGER WITH THE KW RATING
 THE SIZE OF THE BRANCH CIRCUIT, THE LOAD AND THE OVER
 CURRENT PROTECTION WILL NEED TO BE REVISED.
 220,310,240, ETC.
 PLEASE VERIFY WITH THE LISTED EQUIPMENT.110.3
 PLEASE SEE 110.26 FOR MINIMUM CLEARANCE REQUIREMENTS.
  
 5) NOTE: PLEASE SEE 210.8A7 FOR REQUIRED GFI PROTECTION
 OF ALL 15/20AMP RECEPTACLES WITHIN 6FT OF A LAUNDRY
 SINK. THIS WAS A CHANGE IN THE 2005 NEC AND IS REQUIRED
 EVEN FOR DEDICATED WASHER CIRCUITS.
  
 6) NOTE: RISER IS MISSING THE REQUIRED EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO SUB PANEL.
 250.6,250.24,250.110, ETC SIZE PER 250.122.
  
 7) NOTE: PLEASE COORDINATE RISER AND PANEL. PANEL IS
 SHOWN AS MLO YET RISER INDICATES MAIN.
 240,230. FBC 106.1.1 FOR CLARITY OF PLANS AND
 COORDINATION.
  
 8) NOTE; PLEASE INDICATE THE REQUIRED LIGHT FIXTURES AT
 EGRESS LOCATIONS WHICH ARE SHOWN AS *J* FOR JUNCTION
 BOX AT THIS TIME. SOME SORT OF LIGHT FIXTURE WILL BE
 REQUIRED.
 210.70, LS101 7.8
  
 9) NOTE: PLANS SHOW BOTH DISPOSAL AND DISHWASHER ON
 SEPARATE RECEPTACLES WHICH IS OK HOWEVER PLEASE BE SURE
 TO SEE 210.4B. PLEASE CLARIFY IF THE DISPOSAL IS GOING
 TO SELF ACTUATED OR THERE WILL BE SWITCHED RECEPTACLE.
 300.
 FBC 106.1.1 FOR CLARITY, COORDINATION AND ADDITIONAL
 INFORMATION.
  
 10) NOTE: SOME LOCATIONS ON PLANS INDICATE THE ENTIRE
 RECEPTACLE BEING SWITCHED. THIS IS OK HOWEVER IF THIS
 IS THE CASE AN ADDITIONAL RECEPTACLE MEETING 210.52 IS
 REQUIRED. IF THESE ARE ACTUALLY HALF SWITCHED
 RECEPTACLES PLEASE ADJUST SYMBOL BEING SHOWN. THE
 SYMBOL LEGEND DOES CONTAIN A HALF SWITCH RECEPTACLE
 SYMBOL.
 FBC 106.1.1.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-06 Cont ID  
Sent By adarroug Date 2009-04-06 Time 09:17 Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 09:17 Sent To  
Notes
2009-04-06 09:18:01TO "R14"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-30 Cont ID  
Sent By adarroug Date 2008-12-30 Time 15:01 Rev Time 0.00
Received By adarroug Date 2008-12-30 Time 15:01 Sent To E
Notes
2008-12-30 15:01:18TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-16 Cont ID  
Sent By jgomez Date 2009-01-16 Time 17:05 Rev Time 0.00
Received By jgomez Date 2008-12-26 Time 10:46 Sent To  
Notes
2008-12-26 10:47:54TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-04-23 Cont ID  
Sent By rkussner Date 2009-04-23 Time 14:51 Rev Time 0.00
Received By rkussner Date 2009-04-23 Time 14:51 Sent To Z
Notes
2009-04-23 15:18:23***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-448 (D)(2), THE LANDSCAPE
 PLAN SHALL CONTAIN ITEMS (A) THROUGH (R) OF THIS
 SECTION
  
 2. ALL PLANT MATERIAL SHALL BE ACCURATELY IDENTIFIED AS
 TO NAME, SPECIES, QUANTITY, SIZE AND SPACING.
  
 3. PURSUANT TO SECTION 94-442(B)(2)(A), AT LEAST ONE
 SHADE TREE, FLOWERING OR FRUIT TREE SHALL BE PLANTED
 FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR PORTION
 THEREOF. AT LEAST ONE SHRUB SHALL BE PLANTED FOR EACH
 500 SQUARE FEET OF OPEN SPACE OR PORTION THERELOF.
  
 4. PURSUANT TO SECTION 94-442 (D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. GRASS AREAS
 SHALL BE SODDED.
  
 5. PURSUANT TO SECTION 94-445 (4)(G)(3), AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED
 LANDSCAPE AREAS FOR ALL PROPERTIES. THIS INCLUDES THE
 ENTIRE SITE AND THE RIGHT-OF-WAY. AN IRRIGATION PERMIT
 IS REQUIRED.
  
 6. SUBMIT A COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-04-17 Cont ID  
Sent By hmoser Date 2009-04-17 Time 10:43 Rev Time 0.00
Received By hmoser Date 2009-04-17 Time 10:43 Sent To  
Notes
2009-04-17 10:44:34NO MECHANICAL PLANS SUBMITTED .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-01-13 Cont ID  
Sent By hmoser Date 2009-01-13 Time 09:06 Rev Time 0.00
Received By hmoser Date 2009-01-13 Time 09:06 Sent To P
Notes
2009-01-13 09:10:571/13/2009
 PLEASE REFER TO SECTION M1602.4 2004 FBCR BALANCED
 RETURN AIR .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-04-30 Cont ID  
Sent By kstevens Date 2009-04-30 Time 11:23 Rev Time 0.00
Received By kstevens Date 2009-04-30 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-13 Cont ID  
Sent By kstevens Date 2009-01-13 Time 09:37 Rev Time 0.00
Received By kstevens Date 2009-01-13 Time 09:37 Sent To B
Notes
2009-01-13 10:02:17DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 EXISTING BUILDING
 FBC-2004 RESIDENTIAL
 FBC-2004 CHAPTER 1
  
 1. SHTS 2.1 & 3.1. THE PROPOSED FLOOR PLAN SHOWS THE
 WASH MACHINE, BUT THE DEMO SHEET SHOWS NO EXISTING WASH
 MACHINE CONNECTIONS TO THE SANITARY. PLEASE INDICATE
 THE LOCATION OF THE EXISTING WASH MACHINE TO DETERMINE
 IF THE SANITARY HAS BEEN DEMO'D ACCORDING TO SECTION
 704.5. SECTION 106.1.2..
  
 2. SHT 2.1 DEMO NOTE NUMBER 8. A GAS PERMIT IS REQUIRED
 FOR THE GAS DEMO WORK. PLEASE INDICATE THE LOCATION OF
 THE GAS PIPING WORK ON THE EXISTING FLOOR PLAN DEMO.
 SECTION 106.1.2.
  
 3. SHT 3.1. A WATER HEATER IS REQUIRED. SECTION 607.1.
 SHOW THE LOCATION OF THE WATER HEATER ON THE FLOOR
 PLAN. SECTION 106.1.2.
  
 4. SHT 6.1 DETAIL 3/6.1 SANITARY RISER DIAGRAM. THE
 BRANCH LINE TO THE WASH MACHINE IS REQUIRED TO BE 3"
 PER SECTION 406.3. PLEASE INDICATE PIPE SIZE ON RISER
 DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2009-05-01 Cont ID  
Sent By mcruz Date 2009-05-01 Time 10:43 Rev Time 0.00
Received By mcruz Date 2009-04-23 Time 13:37 Sent To  
Notes
2009-05-01 10:44:44PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. COMPLY WITH ALL LANDSCAPING COMMENTS. IF YOU HAVE
 FURTHER QUESTION OR NEED CLARIFICATION ON LANDSCAPE
 PLAN COMMENTS, PLEASE CONTACT, ROBERT KUSSNER,
 LANDSCPAE PLANNER, AT 561.822.1462.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-30 Cont ID  
Sent By mcruz Date 2008-12-30 Time 13:12 Rev Time 0.00
Received By mcruz Date 2008-12-30 Time 13:06 Sent To I
Notes
2008-12-30 13:12:08PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved