Plan Review Details - Permit 08120504
Plan Review Stops For Permit 08120504
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-12-03 Cont ID  
Sent By jgomez Date 2009-12-03 Time 10:58 Rev Time 0.00
Received By jgomez Date 2009-12-03 Time 09:54 Sent To PC
Notes
2009-12-03 11:02:59BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE THE ENERGY CALCULATIONS. NEED TO INCLUDE THE
 A/C INFORMATION AND REVISE THE HOT WATER HEATER
 INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-11-05 Cont ID  
Sent By jgomez Date 2009-11-05 Time 16:42 Rev Time 0.00
Received By jgomez Date 2009-11-05 Time 16:05 Sent To  
Notes
2009-11-05 16:47:22RESIDENTIAL (R3) ADDITION, BUILDING REVIEW FOURTH
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 OF 2004 FBC. NEED TO PROVIDE REVISED FORM 2004R.
 ENERGY CALCULATIONS SUBMITTED ARE FOR 2001 CODE AND
 THESE WERE THE ONES THAT WERE REJECTED ON PREVIEWS
 REVIEW BECAUSE OF THE WRONG CODE.
  
 3- SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS
 REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL
 CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF
 BATHROOM ADDITION. (REPEAT COMMENT). SPECIFY SIZE OF
 EXISTING EGRESS WINDOW THAT IS SHOWN NOW AND SIZE OF
 EXISTING WINDOW TO BE BLOCKED WITH NEW BATHROOM TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS. PLANS
 SUBMITTED STILL DON'T SPECIFY THE SIZE OF EXISTING
 WINDOW TO REMAIN. EGRESS REQUIREMENTS HAVE BEEN REDUCED
 BY ELIMINATING ONE WINDOW. SEE SEC. 501.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 4- SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 472 (REPEAT COMMENT). SURVEYS SUBMITTED ARE
 COPIES OF THE SIGNATURE. RESUBMIT SURVEYS WITH ORIGINAL
 SIGNATURE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-05-28 Cont ID  
Sent By jgomez Date 2009-05-28 Time 10:09 Rev Time 0.00
Received By jgomez Date 2009-05-28 Time 09:57 Sent To  
Notes
2009-05-28 10:30:30RESIDENTIAL (R3) ADDITION, BUILDING REVIEW THIRD
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5120) TO CHECK IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT. (REPEAT COMMENT. NOT ADDRESSED AT ALL-
 THREE TIMES).
  
 3- GABLE END DETAIL SHOWN ON SHEET A-3 IS A DETAIL THAT
 WAS PASTED TO ORIGINAL DRAWING. REVISE ORIGINAL DRAWING
 AS REQUIRED. PASTING TO ORIGINAL DRAWINGS IS NOT
 ALLOWED ON SIGNED AND SEALED DRAWINGS. SIGNED AND
 SEALED DRAWINGS ARE NOT ALLOWED TO BE ALTERED IN ANY
 WAY.
  
 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 OF 2004 FBC. (NO ENERGY CALCULATIONS WERE
 SUBMITTED AT THIS TIME).
  
 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES. (REPEAT COMMENT. NOT ADDRESSED AT
 ALL. THREE TIMES).
  
 B) PROVIDE TWO COPIES OF PRODUCT APPROVAL NOA
 05-1018.01 SUBMITTED FOR WINDOWS. ONLY ONE COPY WAS
 PROVIDED.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT. NOT ADDRESSED AT ALL. THREE TIMES).
  
 7- MIN. THICKNESS OF STUCCO ON FRAME CONSTRUCTION IS
 7/8" AS REQUIRED BY SEC. R703.6.4.3 OF 2004 FLORIDA
 RESIDENTIAL CODE ( ASTM C926 AND ASTM C-1063). (REPEAT
 COMMENT). EXTERIOR ELEVATIONS ON SHEET A-1 SPECIFIES
 5/8" STUCCO THICKNESS. REVISE AS REQUIRED.
  
 8- SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS
 REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL
 CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF
 BATHROOM ADDITION. (REPEAT COMMENT). SPECIFY SIZE OF
 EXISTING EGRESS WINDOW THAT IS SHOWN NOW AND SIZE OF
 EXISTING WINDOW TO BE BLOCKED WITH NEW BATHROOM TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-08 Cont ID  
Sent By jgomez Date 2009-04-08 Time 16:42 Rev Time 0.00
Received By jgomez Date 2009-04-08 Time 16:42 Sent To PC
Notes
2009-04-08 16:49:06RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5120) TO CHECK IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT. (REPEAT COMMENT. NOT ADDRESSED AT
 ALL).
  
 3- DIMENSIONS SHOWN ON FLOOR PLANS ARE NOT LEGIBLE.
 THEY ARE EXTREMELY LIGHT TO READ. REVISE AS REQUIRED.
 SEC. 106.1.3 CITY AMENDMENTS TO FBC 2004.
  
 4- SPECIFY CURRENT CODE 2004 FLORIDA RESIDENTIAL CODE
 WITH 2007 REVISIONS. CODE TABULATION INFORMATION ON
 SHEET A-1 IS REFERRING TO 2007 FBC. THIS PERMIT
 APPLICATION WAS SUBMITTED UNDER THE 2004 FLORIDA
 RESIDENTIAL CODE WITH 2007 REVISIONS. REVISE AS
 REQUIRED.
  
 5- PROVIDE COMPLETE GABLE END DETAIL THAT SHOWS
 COMPLIANCE WITH SEC. R609.4 OF 2004 FLORIDA RESIDENTIAL
 CODE. (REPEAT COMMENT). DETAIL SHOWN ON SHEET A-3 IS
 FOR WOOD FRAMED WALL. NEED DETAIL FOR MASONRY
 CONSTRUCTION AS SHOWN ON FLOOR PLANS. PROVIDE COMPLETE
 SPECIFICATIONS FOR SIZE AND FASTENING OF BOTTOM SILL
 PLATE, GABLE END FASTENING TO THE BOTTOM SILL AND GABLE
 END OUTLOOKERS (ROOF RAFTERS) TO GABLE END TRUSS TO
 SHOW COMPLIANCE WITH SEC. R601.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 6- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 OF 2004 FBC.
 A) PLEASE MAKE SURE CORRECT 2004 REVISED FORM IS USED.
 (REPEAT COMMENT). FORM SUBMITTED WAS FORM 600A-2001.
 THIS FORM IS NOT ONLY THE OLD CODE, BUT IS NOT THE
 REVISED FORM EITHER. NEED TO USE FORM 600A-2004R.
  
 B) OVERHANG HEIGHT SHOWN ON PAGE TWO IS INCORRECT. SEE
 SEC. 13-601.2.A.3 AND FIGURE 6.1 OF 2004 FBC TO SEE HOW
 THE DIMENSIONS FOR THE OVERHANG HEIGHT AND LENGTH ARE
 TAKEN AND REVISE AS REQUIRED.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. (REPEAT
 COMMENT).
  
 D) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 7- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES. (REPEAT COMMENT. NOT ADDRESSED AT
 ALL).
  
 B) HURRICANE SHUTTERS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED COPY. ALSO, CLEARLY
 MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS
 (EG: WALL MOUNTED, BUILD OUT, ETC.) AND SPECIFIC ANCHOR
 TYPE AND SPACING TO BE USED. (REPEAT COMMENT. NOT
 ADDRESSED AT ALL).
 ***NOTE: ENGINEER'S WINDOW SCHEDULE ON SHEET A-1
 SPECIFIES IMPACT GLASS, WHILE PRODUCT APPROVAL
 SUBMITTED IS FOR NON-IMPACT GLASS. COORDINATE
 INFORMATION AS REQUIRED TO MATCH.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT. NOT ADDRESSED AT ALL).
  
 9- MIN. THICKNESS OF STUCCO ON FRAME CONSTRUCTION IS
 7/8" AS REQUIRED BY SEC. R703.6.4.3 OF 2004 FLORIDA
 RESIDENTIAL CODE ( ASTM C926 AND ASTM C-1063). (REPEAT
 COMMENT). EXTERIOR ELEVATIONS ON SHEET A-1 AND BUILDING
 SECTION ON SHEET A-2 SPECIFY 5/8" STUCCO THICKNESS.
 REVISE AS REQUIRED.
  
 10- SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS
 REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL
 CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF
 BATHROOM ADDITION. (REPEAT COMMENT. NOT ADDRESSED AT
 ALL).
  
 11- SPECIFY SAFETY GLASS FOR WINDOW BY TUB AREA AS
 REQUIRED BY SEC. R308.4 OF 2004 FLORIDA RESIDENTIAL
 CODE. (REPEAT COMMENT). WINDOW SCHEDULE CALLS FOR
 IMPACT GLASS, BUT PRODUCT APPROVAL SUBMITTED IS FOR
 NON-IMPACT GLASS. COORDINATE INFORMATION AS REQUIRED TO
 MATCH.
  
 12- RETURN REVIEWED SET AFTER CORRECTIONS ARE DONE TO
 ORIGINAL DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 13- SURVEY CAN'T BE COPIED BECAUSE OF COPYRIGHT ISSUES.
 REMOVE SURVEY INFORMATION ON SHEET A-1. DRAWINGS TO
 SHOW SITE PLAN, NOT COPY OF SURVEY. BESIDES THIS SURVEY
 CAN'T BE USED FOR CONSTRUCTION. SEE NOTE #5 ON SURVEY.
 (REPEAT COMMENT. NOT ADDRESSED AT ALL).
  
 14- CLARIFY WHY KNEE WALL SHOWS ONLY ONE TOP PLATE IF
 THIS IS A BEARING WALL?. SEE CHAPTER 6 OF 2004 FLORIDA
 RESIDENTIAL CODE. (REPEAT COMMENT). PLANS SUBMITTED NOW
 SPECIFY ROOF TRUSS, BUT DRAWING STILL SHOWS KNEE WALL.
 REVISE AS REQUIRED.
  
 15- SPECIFY R-VALUES ON CEILING AND WALLS. COORDINATE
 WITH THE ENERGY CALCULATIONS. (REPEAT COMMENT). MISSING
 INFORMATION FOR WALLS.
  
 16- SPECIFY HOW LONG ARE THE BOLTS SPECIFIED TO HOLD
 THE 2X8 WOOD PLATE SHOWN ON BUILDING SECTION A/2.
 (REPEAT COMMENT. NOT ADDRESSED AT ALL).
  
 17- SPECIFY ROOF VENTILATION TO COMPLY WITH SEC. R806
 OF 2004 FLORIDA RESIDENTIAL CODE. PLANS AND SECTIONS
 SUBMITTED DON'T PROVIDE ANY INFORMATION.
  
 18- SPECIFY FIREBLOCKING MATERIAL AND LOCATION IN WALL
 SECTION TO VERIFY COMPLIANCE WITH SEC. R602.1.2 OF 2004
 FLORIDA RESIDENTIAL CODE. BUILDING SECTION DOESN'T
 PROVIDE ANY INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-15 Cont ID  
Sent By jgomez Date 2009-01-15 Time 15:32 Rev Time 0.00
Received By jgomez Date 2009-01-15 Time 13:02 Sent To PC
Notes
2009-01-15 15:55:32RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5120) TO CHECK IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.
  
 3- DIMENSIONS SHOWN ON FLOOR PLAN AND FOUNDATION PLAN
 DON'T MATCH DIMENSIONS SHOWN ON SURVEY. REVISE AS
 REQUIRED.
  
 4- SURVEY SUBMITTED:
 A) ADDITION DIMENSIONS DON'T MATCH PLANS. REVISE AS
 REQUIRED.
  
 B) PROPERTY IS LOCATED ON FLOOD ZONE "C", NOT "X".
 REVISE AS REQUIRED. FLOOD ZONE STILL IS BASED ON FLOOD
 INSURANCE RATE MAP (FIRM) DATED MARCH 1ST OF 1979.
  
 C) SURVEY NEED ORIGINAL SIGNATURE, NOT COPY AS REQUIRED
 BY SEC. 61G17-7.0025 OF FLORIDA ADMINISTRATIVE CODE AND
 CHAPTER 472 FLORIDA STATUTE.
  
 D) GENERAL NOTE #5 STATES THAT THIS SURVEY IS NOT TO BE
 USED FOR CONSTRUCTION. NEED TO PROVIDE SURVEY THAT IS
 SUITABLE FOR CONSTRUCTION.
  
 5- PROVIDE COMPLETE DESIGN CRITERIA. SPECIFY CURRENT
 CODE 2004 FLORIDA RESIDENTIAL CODE WITH 2007 REVISIONS.
 SPECIFY ALL LIVE, DEAD, AND WIND LOADS AS REQUIRED BY
 SEC. R301 AND R301.2.1.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 6- NAME AND SIGNATURE OF PERSON RESPONSIBLE FOR THE
 DESIGN NEED TO BE ON ALL DRAWINGS.
  
 7- PLANS TO SPECIFY LOCATION OF VERTICAL REINFORCEMENT
 IN FILLED CELLS. SHOW ON PLANS LOCATION OF VERTICAL
 REINFORCEMENT INCLUDING THE CORNERS AND AT BOTH ENDS OF
 OPENINGS AS REQUIRED BY SECTIONS R606 AND R609 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 8- PROVIDE COMPLETE GABLE END DETAIL THAT SHOWS
 COMPLIANCE WITH SEC. R609.4 OF 2004 FLORIDA RESIDENTIAL
 CODE. PROVIDE FULL HEIGHT WALL WITH RAKE BEAM OR
 PROVIDE COMPLETE DETAIL THAT PROVIDES CONTINUOUS
 STRUCTURAL SUPPORT AND BRACING TO COMPLY WITH THIS CODE
 SECTION. SPECIFY EVERY FRAMING MEMBER AND CONNECTIONS.
  
 9- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 OF 2004 FBC.
 ***NOTE: PLEASE MAKE SURE CORRECT 2004 REVISED FORM IS
 USED. ALSO, COMPLETE ALL INFORMATION AND MAKE SURE ALL
 CORRESPONDING PARTIES SIGN AND DATE BOTTOM OF FORM.
  
 10- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES.
  
 B) HURRICANE SHUTTERS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED COPY. ALSO, CLEARLY
 MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS
 (EG: WALL MOUNTED, BUILD OUT, ETC.) AND SPECIFIC ANCHOR
 TYPE AND SPACING TO BE USED.
  
 C) ALL SIMPSON OR USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS.
 NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE CONNECTOR.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 12- OWES $1.30 FOR RADON FEES AS REQUIRED BY CHAPTER
 10D-91 OF FLORIDA ADMINISTRATIVE CODE SUBPART B.
  
 13- SHEET 1:
 A) *SPECIFY 2 LAYERS OF WATER RESISTANT BARRIER OVER
 FRAME CONSTRUCTION AS REQUIRED BY SEC. R703.6.3 OF 2004
 FLORIDA RESIDENTIAL CODE.
 **CLARIFY HOW IS THE 5/8" STUCCO ON SELF FURRING PAPER
 BACKED LATH ATTACHED TO THE CONCRETE BLOCK.
 ***MIN. THICKNESS OF STUCCO ON FRAME CONSTRUCTION IS
 7/8" AS REQUIRED BY ASTM C926 AND ASTM C-1063. REVISE
 AS REQUIRED.
  
 B) SPECIFY CALCULATED OPENINGS DESIGN PRESSURES AS
 REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS
 REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL
 CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF
 BATHROOM ADDITION.
  
 D) SPECIFY SAFETY GLASS FOR WINDOW BY TUB AREA AS
 REQUIRED BY SEC. R308.4 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 E) SEE COMMENTS ON PLANS AND RETURN REVIEWED SET OF
 PLANS AFTER CORRECTIONS ARE DONE TO ORIGINAL DRAWINGS.
  
 F) SURVEY CAN'T BE COPIED BECAUSE OF COPYRIGHT ISSUES.
 REMOVE SURVEY INFORMATION. DRAWINGS TO SHOW SITE PLAN,
 NOT COPY OF SURVEY. BESIDES THIS SURVEY CAN'T BE USED
 FOR CONSTRUCTION. SEE NOTE #5 ON SURVEY.
  
 G) ROOF FRAMING PLAN: SPECIFY THE CALCULATED UPLIFT
 LOADS AND SPECIFIC CONNECTORS AS REQUIRED TO VERIFY
 COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 H) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS SHOWING
 HOW JOINING THE NEW ADDITION TO THE EXISTING BUILDING
 AT ROOF AREA AND WALL AREA.
 ALSO, FOUNDATION PLAN TO SPECIFY HOW LONG AND HOW MUCH
 EMBEDMENT IS REQUIRED FOR #5 DOWELS SPECIFIED TO
 CONNECT NEW CONCRETE SLAB TO EXISTING.
  
 14- SHEET 2:
 A) BUILDING SECTION:
 *SPECIFY TWO LAYERS OF VAPOR BARRIER ON FRAMED
 CONSTRUCTION. SEC. R703.6.3 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 **CLARIFY WHY KNEE WALL SHOWS ONLY ONE TOP PLATE IF
 THIS IS A BEARING WALL?. SEE CHAPTER 6 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 ***SPECIFY ALL STRUCTURAL CONNECTORS TO SHOW COMPLIANCE
 WITH THE CONTINUOUS LOAD PATH OF SEC. R601.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 ****SPECIFY R-VALUES ON CEILING AND WALLS. COORDINATE
 WITH THE ENERGY CALCULATIONS.
  
 *****SPECIFY HOW LON ARE THE BOLTS SPECIFIED TO HOLD
 THE 2X8 WOOD PLATE.
  
 ******SPECIFY HOW ARE THE 2X8 ROOF RAFTERS JOINED TO
 THE 2X6 CEILING JOISTS.
  
 15- DESIGNER TO REVIEW COMMENTS SHOWN ON REVIEWED SET
 OF PLANS AND RETURN REVIEWED SET AFTER CORRECTIONS ARE
 DONE TO THE ORIGINAL DRAWINGS TO EXPEDITE REVIEW
 PROCESS AND MAKE SURE ALL COMMENTS ARE ADDRESSED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-28 Cont ID  
Sent By dpalmer Date 2009-10-28 Time 15:52 Rev Time 0.00
Received By dpalmer Date 2009-10-28 Time 15:52 Sent To  
Notes
2009-10-28 15:52:43** REDLINED PLANS. **
  
 1) 2005 NEC
  
 2) BATH CIRCUIT PER 210.52D, 210.11.C.3
  
 3) LOAD CALCULATIONS STATE ONLY ONE SMALL APPLIANCE
 CIRCUIT YET SHOWN IN CALCS. 220.53,210.11.C.1
  
 4) WATER HEATER INDICATES 40AMP OCP ON #10 AWG WHICH IS
 TOO HIGH. VIF THE KW RATING OF WATER HEATER AND CORRECT
 BRANCH CIRCUIT SIZING PER 422.13, 310.16, 240.4
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-06-01 Cont ID  
Sent By dpalmer Date 2009-06-01 Time 10:10 Rev Time 0.00
Received By dpalmer Date 2009-06-01 Time 10:10 Sent To  
Notes
2009-06-01 10:10:20*** DENIED PLANS ****
  
 ** PLANS ARE COMING BACK FOR COMMENTS FROM OTHER
 TRADES. ALSO PLANS HAVE ITEMS TAPED/ATTACHED TO SIGNED
 AND SEALED PLANS WHICH IS NOT PERMITTED.
 PLANS COULD HAVE BEEN REDLINED HOWEVER SOME ITEMS NOW
 NEED TO BE CORRECTED WHICH ARE NEW.
  
 1) NOTE: PLEASE BE SURE THE 2005 NEC IS NOTED ON PLANS.
  
 2) NOTE: PLEASE SEE FBC R313.2.1. PLEASE PROVIDE A
 LAYOUT FOR EXISTING DWELLING SHOWING EXISTING OR NEW
 SMOKE ALARMS MEETING CURRENT NFPA-72 2002.
  
 3) NOTE: DEDICATED CIRCUIT FOR BATH SHALL MEET
 210.11C3. 20AMP AND #12. PANEL SCHEDULE DOES NOT LIST.
 PLEASE SEE THAT THE PANEL SCHEDULE ONLY LIST ONE SMALL
 APPLIANCE CIRCUIT. IS THIS CORRECT? 210.11C1, 220.52.
  
 4) NOTE: ON PLANS OTHER THAN ELECTRICAL THE NEW A/C
 SYSTEM IS GOING IN AT THIS TIME OF THE ADDITION.
 PLEASE SHOW THE REQUIRED DISCONNECT PER 441.11, 440.12.
 PLEASE ALSO SHOW THE NEW OR EXISTING GFI PER
 210.63,210.8A3 FOR A/C EQUIPMENT
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-01 Cont ID  
Sent By dpalmer Date 2009-04-01 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2009-04-01 Time 11:37 Sent To P
Notes
2009-04-01 12:05:18REDLINED PLAN, DEDICATED CIRCUIT REQUIRED PER 210.11C3,
 MUST BE 20AMP AND #12,
 NO A/C WORK BEING DONE AT THIS TIME.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-31 Cont ID  
Sent By dpalmer Date 2008-12-31 Time 10:41 Rev Time 0.00
Received By dpalmer Date 2008-12-31 Time 10:41 Sent To M
Notes
2008-12-31 10:41:39** DENIED REVIEW **
  
  
 1) NOTE: PLEASE SEE FS 481.229, 471.003. WHEN MEETING
 EXCEPTIONS IN THE STATUTES AS MENTIONED PLANS ARE STILL
 REQUIRED TO BE DONE BY THE DESIGN PROFESSIONAL AS
 LISTED.
 THE PLANS SUBMITTED DO NOT CONTAIN ANY TITLE BLOCKS,
 PRINTED NAME, SIGNATURE, OR SIGNED AND SEALED.
  
 2) NOTE: PLANS MENTIONS USE OF POSSIBLE EXISTING
 LAUNDRY CIRCUIT OR RECEPTACLE CIRCUIT. IT IS NOT
 PERMISSIBLE TO USE THE LAUNDRY CIRCUIT. PLEASE SEE
 210.52D, 210.11C2 AND 210.11C3.
 THE LAUNDRY CIRCUIT MUST BE SEPARATE AND BE AVAILABLE
 FOR LAUNDRY.
 THE BATH SHALL BE DEDICATED AS LISTED IN THE ABOVE
 SECTIONS. THERE IS TWO SEPARATE WAYS TO WIRE THE
 BATHROOMS HOWEVER THE PLANS DO NOT INDICATE COMPLIANCE
 WITH EITHER.
 MUST BE 20AMP AND #12 WHEN WIRING FOR GFI.
  
 2) NOTE: PLANS DO NOT INDICATE ANY NEW ELECTRICAL FOR
 PROPOSED A/C SYSTEM.
 PLEASE SEE 210.63, 210.8A, 440.11 FOR MISSING GFI
 RECEPTACLES, DISCONNECTS ETC
  
 3) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 THE EXISTING ELECTRICAL SERVICE WITH NEW PROPOSED A/C
 LOADS.
 PLEASE SEE NEC 220.83.
 PLEASE INDICATE THE SIZE OF THE ELECTRICAL SERVICE IN
 ORDER TO DETERMINE IF THE EXISTING IS ADEQUATE FOR NEW
 LOADS.
 215.5,230.2
  
 4) NOTE: PLEASE SEE FBC 108.3 WHICH REQUIRES THE
 APPLIED VALUE TO INCLUDE ALL LABOR, DESIGN COST,
 MATERIALS ETC EVEN IF ANY OF THESE ARE OWNER SUPPLIED.
 PLEASE SEE VALUATIONS BASED ON THE ADOPTED ICC
 STANDARDS APPEARS THIS WILL CHANGE THE VALUE AS
 APPLIED.
 THE APPLIED SQ FT NOTES 100 SQ FT YET BASED ON THE
 PLANS THE SQ FT IS HIGHER.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-12-01 Cont ID  
Sent By btrobaug Date 2009-12-01 Time 09:19 Rev Time 0.00
Received By btrobaug Date 2009-12-01 Time 09:19 Sent To B
Notes
2009-12-01 09:20:10TO JULIO./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-10-28 Cont ID  
Sent By rmcdouga Date 2009-10-28 Time 10:23 Rev Time 0.00
Received By rmcdouga Date 2009-10-27 Time 10:23 Sent To  
Notes
2009-10-28 10:24:14SENT TO R-21

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-05-22 Cont ID  
Sent By dpalmer Date 2009-05-22 Time 15:12 Rev Time 0.00
Received By dpalmer Date 2009-05-22 Time 15:12 Sent To  
Notes
2009-05-22 15:17:22TO R-18

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-27 Cont ID  
Sent By mcruz Date 2009-03-27 Time 10:10 Rev Time 0.00
Received By mcruz Date 2009-03-25 Time 10:10 Sent To Z
Notes
2009-03-27 10:10:33PLACED IN Z BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-30 Cont ID  
Sent By adarroug Date 2008-12-30 Time 15:15 Rev Time 0.00
Received By adarroug Date 2008-12-30 Time 15:15 Sent To E
Notes
2008-12-30 15:15:28TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-15 Cont ID  
Sent By jgomez Date 2009-01-15 Time 15:55 Rev Time 0.00
Received By jgomez Date 2008-12-23 Time 15:11 Sent To  
Notes
2008-12-23 15:12:09TO "SFR" "Z"

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2009-11-05 Cont ID  
Sent By jgomez Date 2009-11-05 Time 15:00 Rev Time 0.00
Received By jgomez Date 2009-11-05 Time 15:00 Sent To  
Notes
2009-11-05 15:00:48PAID PR# 09019590.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2009-07-24 Cont ID  
Sent By rregueir Date 2009-07-24 Time 13:28 Rev Time 0.00
Received By rregueir Date 2009-07-24 Time 13:28 Sent To  
Notes
2009-07-24 13:28:49NO ENERGY CALCULATIONS SUBMITTED, NO MECHANICAL PERMIT
 APPLIED FOR. SEPARATE PLANS AND PERMIT REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-04-08 Cont ID  
Sent By hmoser Date 2009-04-08 Time 14:27 Rev Time 0.00
Received By hmoser Date 2009-04-08 Time 14:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-01-12 Cont ID  
Sent By hmoser Date 2009-01-12 Time 14:54 Rev Time 0.00
Received By hmoser Date 2009-01-12 Time 14:54 Sent To P
Notes
2009-01-12 15:01:2201/12/2009
 PLEASE PROVIDE DUCT SIZE FOR NEW BATHROOM DUCT . PLEASE
 SEE SECTION M1602 PROHIBITED SOURCES #4 . 2004 FBCR
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-10-29 Cont ID  
Sent By kstevens Date 2009-10-29 Time 11:20 Rev Time 0.00
Received By kstevens Date 2009-10-29 Time 11:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-06-01 Cont ID  
Sent By kstevens Date 2009-06-01 Time 11:07 Rev Time 0.00
Received By kstevens Date 2009-06-01 Time 11:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-04-08 Cont ID  
Sent By lwagner Date 2009-04-08 Time 09:38 Rev Time 0.00
Received By lwagner Date 2009-04-08 Time 09:08 Sent To M
Notes
2009-04-08 09:42:44*******NOTE*********
 SHEET A-1 STATES 2007 CODE. PERMIT # 08120504 WOULD BE
 FBC 2004.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-13 Cont ID  
Sent By kstevens Date 2009-01-13 Time 08:25 Rev Time 0.00
Received By kstevens Date 2009-01-12 Time 16:53 Sent To B
Notes
2009-01-13 08:43:50DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE CODE CRITERIA. PERSENT CODE ADOPTED IS
 FBC-2004 WITH 2007 AMENDMENTS. SECTION 106.1.1
  
 2. BOTH SHEETS. NOTE: ALL PLANS, SPECIFICATIONS, AND
 ACCOMPANYING DATA BEING FILED FOR PUBLIC RECORD SHALL
 CONTAIN THE PRINTED NAME OF THE RESPONSIBLE PERSON WITH
 THE ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION.
 PER SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY AND SHOW THE REQUIRED
 TITLE BLOCK INFORMATION AS REQUIRED IN FAC
 61G1-15.23002(2) AND 61G1-16.004.
  
 3. SHT 2 SANITARY RISER DIAGRAM. THE LAVS ARE NOT
 VENTED AS SHOWN AND THE VENT PAST THE LAVS IS A
 HORIZONTAL DRY VENT WHICH IS PROHIBITED PER
 FBC-2004,PLUMBING, SECTION 905.3. VENT CONNECTIONS TO
 DRAINAGE SYSTEM. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. SHOW VENT STACK AS A
 CONTINUATION OF THE WASTE STACK FOR THE LAVS.
  
 4. SHT 2 WATER RISER DIAGRAM. FIXTURE FITTINGS, FAUCETS
 AND DIVERTERS SHALL BE INSTALLED AND ADJUSTED SO THAT
 THE FLOW OF HOT WATER FROM THE FITTINGS CORRESPONDS TO
 THE LEFT-HAND SIDE OF THE FIXTURE FITTING. SECTION
 607.4. RISER SHOWS THE HOT WATER TO THE RIGHT SIDE OF
 THE FIXTURES. PLEASE CORRECT RISER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2009-11-24 Cont ID  
Sent By astelly Date 2009-11-24 Time 17:36 Rev Time 0.00
Received By astelly Date 2009-11-24 Time 17:36 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2009-05-31 Cont ID  
Sent By mcruz Date 2009-05-31 Time 15:28 Rev Time 0.00
Received By mcruz Date 2009-05-31 Time 15:24 Sent To E
Notes
2009-05-31 15:28:56PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. THE SITE PLAN INDICATES A SLIGHT INCREASE IN THE
 DIMENSIONS OF THE PROPOSED BATHROOM ADDITION. PLEASE
 INDICATE ON THE SURVEY THE SETBACK DIMENSIONS FROM THE
 PROPOSED ADDITION TO ALL ADJACENT PROPERTY LINES.
 PURSUANT TO THE ZLDR, SECTION 94-72(A)(2):
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT -
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 ADDITIONALLY, PLEASE ENSURE THAT THE PERMIT DESCRIPTION
 IS REVISED ACCORDING TO THE PROPOSED REVISED SITE PLAN.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-03-27 Cont ID  
Sent By mcruz Date 2009-03-27 Time 15:34 Rev Time 0.00
Received By mcruz Date 2009-03-27 Time 15:30 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-30 Cont ID  
Sent By mcruz Date 2008-12-30 Time 12:30 Rev Time 0.00
Received By mcruz Date 2008-12-30 Time 12:27 Sent To I
Notes
2008-12-30 12:30:36PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. THE PERMIT APPLICATION INDICATES THE PROPOSED
 ADDITION IS 10X12 IN SIZE, BUT THE SURVEY INDICATES
 THAT THE PROPOSED ADDITION IS 10X5.9. PLEASE CLARIFY.
  
 3. INDICATE THE SEPARATION DISTANCE OF THE PROPOSED
 ADDITION TO THE EXISTING SHED. NOTE: PURSUANT TO
 SECTION 94-304(B)(3) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), ACCESSORY STRUCTURES SHALL BE
 LOCATED NO CLOSER THAN SIX (6) FEET TO THE PRINCIPAL
 STRUCTURE.
  
 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED/RELOCATED
 A/C EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR,
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved