| Plan Review Stops For Permit 08120504 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2009-12-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-12-03 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-12-03 |
Time |
09:54 |
Sent To |
PC |
|
| Notes |
| 2009-12-03 11:02:59 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE THE ENERGY CALCULATIONS. NEED TO INCLUDE THE | | | A/C INFORMATION AND REVISE THE HOT WATER HEATER | | | INFORMATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2009-11-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-11-05 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-11-05 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2009-11-05 16:47:22 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW FOURTH | | | CHECKLIST. | | | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 | | | REVISIONS. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | | UP. | | | | | | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | 13-600 OF 2004 FBC. NEED TO PROVIDE REVISED FORM 2004R. | | | ENERGY CALCULATIONS SUBMITTED ARE FOR 2001 CODE AND | | | THESE WERE THE ONES THAT WERE REJECTED ON PREVIEWS | | | REVIEW BECAUSE OF THE WRONG CODE. | | | | | | 3- SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS | | | REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL | | | CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF | | | BATHROOM ADDITION. (REPEAT COMMENT). SPECIFY SIZE OF | | | EXISTING EGRESS WINDOW THAT IS SHOWN NOW AND SIZE OF | | | EXISTING WINDOW TO BE BLOCKED WITH NEW BATHROOM TO | | | VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS. PLANS | | | SUBMITTED STILL DON'T SPECIFY THE SIZE OF EXISTING | | | WINDOW TO REMAIN. EGRESS REQUIREMENTS HAVE BEEN REDUCED | | | BY ELIMINATING ONE WINDOW. SEE SEC. 501.2 OF 2004 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 4- SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY | | | CHAPTER 472 (REPEAT COMMENT). SURVEYS SUBMITTED ARE | | | COPIES OF THE SIGNATURE. RESUBMIT SURVEYS WITH ORIGINAL | | | SIGNATURE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2009-05-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-05-28 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-05-28 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2009-05-28 10:30:30 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW THIRD | | | CHECKLIST. | | | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 | | | REVISIONS. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | | UP. | | | | | | 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY (2300 N. JOG RD (561)233-5120) TO CHECK IF | | | IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY | | | OF PAID RECEIPT. (REPEAT COMMENT. NOT ADDRESSED AT ALL- | | | THREE TIMES). | | | | | | 3- GABLE END DETAIL SHOWN ON SHEET A-3 IS A DETAIL THAT | | | WAS PASTED TO ORIGINAL DRAWING. REVISE ORIGINAL DRAWING | | | AS REQUIRED. PASTING TO ORIGINAL DRAWINGS IS NOT | | | ALLOWED ON SIGNED AND SEALED DRAWINGS. SIGNED AND | | | SEALED DRAWINGS ARE NOT ALLOWED TO BE ALTERED IN ANY | | | WAY. | | | | | | 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | 13-600 OF 2004 FBC. (NO ENERGY CALCULATIONS WERE | | | SUBMITTED AT THIS TIME). | | | | | | 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY | | | DCA RULE 9B-72 FOR: | | | A) ROOF SHINGLES. (REPEAT COMMENT. NOT ADDRESSED AT | | | ALL. THREE TIMES). | | | | | | B) PROVIDE TWO COPIES OF PRODUCT APPROVAL NOA | | | 05-1018.01 SUBMITTED FOR WINDOWS. ONLY ONE COPY WAS | | | PROVIDED. | | | | | | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | (REPEAT COMMENT. NOT ADDRESSED AT ALL. THREE TIMES). | | | | | | 7- MIN. THICKNESS OF STUCCO ON FRAME CONSTRUCTION IS | | | 7/8" AS REQUIRED BY SEC. R703.6.4.3 OF 2004 FLORIDA | | | RESIDENTIAL CODE ( ASTM C926 AND ASTM C-1063). (REPEAT | | | COMMENT). EXTERIOR ELEVATIONS ON SHEET A-1 SPECIFIES | | | 5/8" STUCCO THICKNESS. REVISE AS REQUIRED. | | | | | | 8- SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS | | | REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL | | | CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF | | | BATHROOM ADDITION. (REPEAT COMMENT). SPECIFY SIZE OF | | | EXISTING EGRESS WINDOW THAT IS SHOWN NOW AND SIZE OF | | | EXISTING WINDOW TO BE BLOCKED WITH NEW BATHROOM TO | | | VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-04-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-04-08 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-04-08 |
Time |
16:42 |
Sent To |
PC |
|
| Notes |
| 2009-04-08 16:49:06 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND | | | CHECKLIST. | | | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 | | | REVISIONS. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | | UP. | | | | | | 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY (2300 N. JOG RD (561)233-5120) TO CHECK IF | | | IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY | | | OF PAID RECEIPT. (REPEAT COMMENT. NOT ADDRESSED AT | | | ALL). | | | | | | 3- DIMENSIONS SHOWN ON FLOOR PLANS ARE NOT LEGIBLE. | | | THEY ARE EXTREMELY LIGHT TO READ. REVISE AS REQUIRED. | | | SEC. 106.1.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 4- SPECIFY CURRENT CODE 2004 FLORIDA RESIDENTIAL CODE | | | WITH 2007 REVISIONS. CODE TABULATION INFORMATION ON | | | SHEET A-1 IS REFERRING TO 2007 FBC. THIS PERMIT | | | APPLICATION WAS SUBMITTED UNDER THE 2004 FLORIDA | | | RESIDENTIAL CODE WITH 2007 REVISIONS. REVISE AS | | | REQUIRED. | | | | | | 5- PROVIDE COMPLETE GABLE END DETAIL THAT SHOWS | | | COMPLIANCE WITH SEC. R609.4 OF 2004 FLORIDA RESIDENTIAL | | | CODE. (REPEAT COMMENT). DETAIL SHOWN ON SHEET A-3 IS | | | FOR WOOD FRAMED WALL. NEED DETAIL FOR MASONRY | | | CONSTRUCTION AS SHOWN ON FLOOR PLANS. PROVIDE COMPLETE | | | SPECIFICATIONS FOR SIZE AND FASTENING OF BOTTOM SILL | | | PLATE, GABLE END FASTENING TO THE BOTTOM SILL AND GABLE | | | END OUTLOOKERS (ROOF RAFTERS) TO GABLE END TRUSS TO | | | SHOW COMPLIANCE WITH SEC. R601.2 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 6- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | 13-600 OF 2004 FBC. | | | A) PLEASE MAKE SURE CORRECT 2004 REVISED FORM IS USED. | | | (REPEAT COMMENT). FORM SUBMITTED WAS FORM 600A-2001. | | | THIS FORM IS NOT ONLY THE OLD CODE, BUT IS NOT THE | | | REVISED FORM EITHER. NEED TO USE FORM 600A-2004R. | | | | | | B) OVERHANG HEIGHT SHOWN ON PAGE TWO IS INCORRECT. SEE | | | SEC. 13-601.2.A.3 AND FIGURE 6.1 OF 2004 FBC TO SEE HOW | | | THE DIMENSIONS FOR THE OVERHANG HEIGHT AND LENGTH ARE | | | TAKEN AND REVISE AS REQUIRED. | | | | | | C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. (REPEAT | | | COMMENT). | | | | | | D) COMPLETE ALL INFORMATION ON TOP OF FORM. | | | | | | 7- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY | | | DCA RULE 9B-72 FOR: | | | A) ROOF SHINGLES. (REPEAT COMMENT. NOT ADDRESSED AT | | | ALL). | | | | | | B) HURRICANE SHUTTERS. AND, PROVIDE COMPLETE | | | INSTALLATION SCHEDULE. SEE ATTACHED COPY. ALSO, CLEARLY | | | MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS | | | (EG: WALL MOUNTED, BUILD OUT, ETC.) AND SPECIFIC ANCHOR | | | TYPE AND SPACING TO BE USED. (REPEAT COMMENT. NOT | | | ADDRESSED AT ALL). | | | ***NOTE: ENGINEER'S WINDOW SCHEDULE ON SHEET A-1 | | | SPECIFIES IMPACT GLASS, WHILE PRODUCT APPROVAL | | | SUBMITTED IS FOR NON-IMPACT GLASS. COORDINATE | | | INFORMATION AS REQUIRED TO MATCH. | | | | | | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | (REPEAT COMMENT. NOT ADDRESSED AT ALL). | | | | | | 9- MIN. THICKNESS OF STUCCO ON FRAME CONSTRUCTION IS | | | 7/8" AS REQUIRED BY SEC. R703.6.4.3 OF 2004 FLORIDA | | | RESIDENTIAL CODE ( ASTM C926 AND ASTM C-1063). (REPEAT | | | COMMENT). EXTERIOR ELEVATIONS ON SHEET A-1 AND BUILDING | | | SECTION ON SHEET A-2 SPECIFY 5/8" STUCCO THICKNESS. | | | REVISE AS REQUIRED. | | | | | | 10- SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS | | | REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL | | | CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF | | | BATHROOM ADDITION. (REPEAT COMMENT. NOT ADDRESSED AT | | | ALL). | | | | | | 11- SPECIFY SAFETY GLASS FOR WINDOW BY TUB AREA AS | | | REQUIRED BY SEC. R308.4 OF 2004 FLORIDA RESIDENTIAL | | | CODE. (REPEAT COMMENT). WINDOW SCHEDULE CALLS FOR | | | IMPACT GLASS, BUT PRODUCT APPROVAL SUBMITTED IS FOR | | | NON-IMPACT GLASS. COORDINATE INFORMATION AS REQUIRED TO | | | MATCH. | | | | | | 12- RETURN REVIEWED SET AFTER CORRECTIONS ARE DONE TO | | | ORIGINAL DRAWINGS TO EXPEDITE REVIEW PROCESS. | | | | | | 13- SURVEY CAN'T BE COPIED BECAUSE OF COPYRIGHT ISSUES. | | | REMOVE SURVEY INFORMATION ON SHEET A-1. DRAWINGS TO | | | SHOW SITE PLAN, NOT COPY OF SURVEY. BESIDES THIS SURVEY | | | CAN'T BE USED FOR CONSTRUCTION. SEE NOTE #5 ON SURVEY. | | | (REPEAT COMMENT. NOT ADDRESSED AT ALL). | | | | | | 14- CLARIFY WHY KNEE WALL SHOWS ONLY ONE TOP PLATE IF | | | THIS IS A BEARING WALL?. SEE CHAPTER 6 OF 2004 FLORIDA | | | RESIDENTIAL CODE. (REPEAT COMMENT). PLANS SUBMITTED NOW | | | SPECIFY ROOF TRUSS, BUT DRAWING STILL SHOWS KNEE WALL. | | | REVISE AS REQUIRED. | | | | | | 15- SPECIFY R-VALUES ON CEILING AND WALLS. COORDINATE | | | WITH THE ENERGY CALCULATIONS. (REPEAT COMMENT). MISSING | | | INFORMATION FOR WALLS. | | | | | | 16- SPECIFY HOW LONG ARE THE BOLTS SPECIFIED TO HOLD | | | THE 2X8 WOOD PLATE SHOWN ON BUILDING SECTION A/2. | | | (REPEAT COMMENT. NOT ADDRESSED AT ALL). | | | | | | 17- SPECIFY ROOF VENTILATION TO COMPLY WITH SEC. R806 | | | OF 2004 FLORIDA RESIDENTIAL CODE. PLANS AND SECTIONS | | | SUBMITTED DON'T PROVIDE ANY INFORMATION. | | | | | | 18- SPECIFY FIREBLOCKING MATERIAL AND LOCATION IN WALL | | | SECTION TO VERIFY COMPLIANCE WITH SEC. R602.1.2 OF 2004 | | | FLORIDA RESIDENTIAL CODE. BUILDING SECTION DOESN'T | | | PROVIDE ANY INFORMATION. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-01-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-01-15 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-01-15 |
Time |
13:02 |
Sent To |
PC |
|
| Notes |
| 2009-01-15 15:55:32 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | | UP. | | | | | | 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY (2300 N. JOG RD (561)233-5120) TO CHECK IF | | | IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY | | | OF PAID RECEIPT IF FEES ARE DUE. | | | | | | 3- DIMENSIONS SHOWN ON FLOOR PLAN AND FOUNDATION PLAN | | | DON'T MATCH DIMENSIONS SHOWN ON SURVEY. REVISE AS | | | REQUIRED. | | | | | | 4- SURVEY SUBMITTED: | | | A) ADDITION DIMENSIONS DON'T MATCH PLANS. REVISE AS | | | REQUIRED. | | | | | | B) PROPERTY IS LOCATED ON FLOOD ZONE "C", NOT "X". | | | REVISE AS REQUIRED. FLOOD ZONE STILL IS BASED ON FLOOD | | | INSURANCE RATE MAP (FIRM) DATED MARCH 1ST OF 1979. | | | | | | C) SURVEY NEED ORIGINAL SIGNATURE, NOT COPY AS REQUIRED | | | BY SEC. 61G17-7.0025 OF FLORIDA ADMINISTRATIVE CODE AND | | | CHAPTER 472 FLORIDA STATUTE. | | | | | | D) GENERAL NOTE #5 STATES THAT THIS SURVEY IS NOT TO BE | | | USED FOR CONSTRUCTION. NEED TO PROVIDE SURVEY THAT IS | | | SUITABLE FOR CONSTRUCTION. | | | | | | 5- PROVIDE COMPLETE DESIGN CRITERIA. SPECIFY CURRENT | | | CODE 2004 FLORIDA RESIDENTIAL CODE WITH 2007 REVISIONS. | | | SPECIFY ALL LIVE, DEAD, AND WIND LOADS AS REQUIRED BY | | | SEC. R301 AND R301.2.1.1 OF 2004 FLORIDA RESIDENTIAL | | | CODE. | | | | | | 6- NAME AND SIGNATURE OF PERSON RESPONSIBLE FOR THE | | | DESIGN NEED TO BE ON ALL DRAWINGS. | | | | | | 7- PLANS TO SPECIFY LOCATION OF VERTICAL REINFORCEMENT | | | IN FILLED CELLS. SHOW ON PLANS LOCATION OF VERTICAL | | | REINFORCEMENT INCLUDING THE CORNERS AND AT BOTH ENDS OF | | | OPENINGS AS REQUIRED BY SECTIONS R606 AND R609 OF 2004 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 8- PROVIDE COMPLETE GABLE END DETAIL THAT SHOWS | | | COMPLIANCE WITH SEC. R609.4 OF 2004 FLORIDA RESIDENTIAL | | | CODE. PROVIDE FULL HEIGHT WALL WITH RAKE BEAM OR | | | PROVIDE COMPLETE DETAIL THAT PROVIDES CONTINUOUS | | | STRUCTURAL SUPPORT AND BRACING TO COMPLY WITH THIS CODE | | | SECTION. SPECIFY EVERY FRAMING MEMBER AND CONNECTIONS. | | | | | | 9- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | 13-600 OF 2004 FBC. | | | ***NOTE: PLEASE MAKE SURE CORRECT 2004 REVISED FORM IS | | | USED. ALSO, COMPLETE ALL INFORMATION AND MAKE SURE ALL | | | CORRESPONDING PARTIES SIGN AND DATE BOTTOM OF FORM. | | | | | | 10- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED | | | BY DCA RULE 9B-72 FOR: | | | A) ROOF SHINGLES. | | | | | | B) HURRICANE SHUTTERS. AND, PROVIDE COMPLETE | | | INSTALLATION SCHEDULE. SEE ATTACHED COPY. ALSO, CLEARLY | | | MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS | | | (EG: WALL MOUNTED, BUILD OUT, ETC.) AND SPECIFIC ANCHOR | | | TYPE AND SPACING TO BE USED. | | | | | | C) ALL SIMPSON OR USP STRUCTURAL CONNECTORS SPECIFIED | | | ON PLANS AND DETAILS. | | | NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND | | | PAGE SHOWING THE CONNECTOR. | | | | | | 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 12- OWES $1.30 FOR RADON FEES AS REQUIRED BY CHAPTER | | | 10D-91 OF FLORIDA ADMINISTRATIVE CODE SUBPART B. | | | | | | 13- SHEET 1: | | | A) *SPECIFY 2 LAYERS OF WATER RESISTANT BARRIER OVER | | | FRAME CONSTRUCTION AS REQUIRED BY SEC. R703.6.3 OF 2004 | | | FLORIDA RESIDENTIAL CODE. | | | **CLARIFY HOW IS THE 5/8" STUCCO ON SELF FURRING PAPER | | | BACKED LATH ATTACHED TO THE CONCRETE BLOCK. | | | ***MIN. THICKNESS OF STUCCO ON FRAME CONSTRUCTION IS | | | 7/8" AS REQUIRED BY ASTM C926 AND ASTM C-1063. REVISE | | | AS REQUIRED. | | | | | | B) SPECIFY CALCULATED OPENINGS DESIGN PRESSURES AS | | | REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. | | | | | | C) SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS | | | REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL | | | CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF | | | BATHROOM ADDITION. | | | | | | D) SPECIFY SAFETY GLASS FOR WINDOW BY TUB AREA AS | | | REQUIRED BY SEC. R308.4 OF 2004 FLORIDA RESIDENTIAL | | | CODE. | | | | | | E) SEE COMMENTS ON PLANS AND RETURN REVIEWED SET OF | | | PLANS AFTER CORRECTIONS ARE DONE TO ORIGINAL DRAWINGS. | | | | | | F) SURVEY CAN'T BE COPIED BECAUSE OF COPYRIGHT ISSUES. | | | REMOVE SURVEY INFORMATION. DRAWINGS TO SHOW SITE PLAN, | | | NOT COPY OF SURVEY. BESIDES THIS SURVEY CAN'T BE USED | | | FOR CONSTRUCTION. SEE NOTE #5 ON SURVEY. | | | | | | G) ROOF FRAMING PLAN: SPECIFY THE CALCULATED UPLIFT | | | LOADS AND SPECIFIC CONNECTORS AS REQUIRED TO VERIFY | | | COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA RESIDENTIAL | | | CODE. | | | | | | H) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS SHOWING | | | HOW JOINING THE NEW ADDITION TO THE EXISTING BUILDING | | | AT ROOF AREA AND WALL AREA. | | | ALSO, FOUNDATION PLAN TO SPECIFY HOW LONG AND HOW MUCH | | | EMBEDMENT IS REQUIRED FOR #5 DOWELS SPECIFIED TO | | | CONNECT NEW CONCRETE SLAB TO EXISTING. | | | | | | 14- SHEET 2: | | | A) BUILDING SECTION: | | | *SPECIFY TWO LAYERS OF VAPOR BARRIER ON FRAMED | | | CONSTRUCTION. SEC. R703.6.3 OF 2004 FLORIDA RESIDENTIAL | | | CODE. | | | | | | **CLARIFY WHY KNEE WALL SHOWS ONLY ONE TOP PLATE IF | | | THIS IS A BEARING WALL?. SEE CHAPTER 6 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | ***SPECIFY ALL STRUCTURAL CONNECTORS TO SHOW COMPLIANCE | | | WITH THE CONTINUOUS LOAD PATH OF SEC. R601.2 OF 2004 | | | FLORIDA RESIDENTIAL CODE. | | | | | | ****SPECIFY R-VALUES ON CEILING AND WALLS. COORDINATE | | | WITH THE ENERGY CALCULATIONS. | | | | | | *****SPECIFY HOW LON ARE THE BOLTS SPECIFIED TO HOLD | | | THE 2X8 WOOD PLATE. | | | | | | ******SPECIFY HOW ARE THE 2X8 ROOF RAFTERS JOINED TO | | | THE 2X6 CEILING JOISTS. | | | | | | 15- DESIGNER TO REVIEW COMMENTS SHOWN ON REVIEWED SET | | | OF PLANS AND RETURN REVIEWED SET AFTER CORRECTIONS ARE | | | DONE TO THE ORIGINAL DRAWINGS TO EXPEDITE REVIEW | | | PROCESS AND MAKE SURE ALL COMMENTS ARE ADDRESSED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-10-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-10-28 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-10-28 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2009-10-28 15:52:43 | ** REDLINED PLANS. ** | | | | | | 1) 2005 NEC | | | | | | 2) BATH CIRCUIT PER 210.52D, 210.11.C.3 | | | | | | 3) LOAD CALCULATIONS STATE ONLY ONE SMALL APPLIANCE | | | CIRCUIT YET SHOWN IN CALCS. 220.53,210.11.C.1 | | | | | | 4) WATER HEATER INDICATES 40AMP OCP ON #10 AWG WHICH IS | | | TOO HIGH. VIF THE KW RATING OF WATER HEATER AND CORRECT | | | BRANCH CIRCUIT SIZING PER 422.13, 310.16, 240.4 | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2009-06-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-06-01 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-06-01 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2009-06-01 10:10:20 | *** DENIED PLANS **** | | | | | | ** PLANS ARE COMING BACK FOR COMMENTS FROM OTHER | | | TRADES. ALSO PLANS HAVE ITEMS TAPED/ATTACHED TO SIGNED | | | AND SEALED PLANS WHICH IS NOT PERMITTED. | | | PLANS COULD HAVE BEEN REDLINED HOWEVER SOME ITEMS NOW | | | NEED TO BE CORRECTED WHICH ARE NEW. | | | | | | 1) NOTE: PLEASE BE SURE THE 2005 NEC IS NOTED ON PLANS. | | | | | | 2) NOTE: PLEASE SEE FBC R313.2.1. PLEASE PROVIDE A | | | LAYOUT FOR EXISTING DWELLING SHOWING EXISTING OR NEW | | | SMOKE ALARMS MEETING CURRENT NFPA-72 2002. | | | | | | 3) NOTE: DEDICATED CIRCUIT FOR BATH SHALL MEET | | | 210.11C3. 20AMP AND #12. PANEL SCHEDULE DOES NOT LIST. | | | PLEASE SEE THAT THE PANEL SCHEDULE ONLY LIST ONE SMALL | | | APPLIANCE CIRCUIT. IS THIS CORRECT? 210.11C1, 220.52. | | | | | | 4) NOTE: ON PLANS OTHER THAN ELECTRICAL THE NEW A/C | | | SYSTEM IS GOING IN AT THIS TIME OF THE ADDITION. | | | PLEASE SHOW THE REQUIRED DISCONNECT PER 441.11, 440.12. | | | PLEASE ALSO SHOW THE NEW OR EXISTING GFI PER | | | 210.63,210.8A3 FOR A/C EQUIPMENT | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-04-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-01 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-01 |
Time |
11:37 |
Sent To |
P |
|
| Notes |
| 2009-04-01 12:05:18 | REDLINED PLAN, DEDICATED CIRCUIT REQUIRED PER 210.11C3, | | | MUST BE 20AMP AND #12, | | | NO A/C WORK BEING DONE AT THIS TIME. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-12-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-31 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-31 |
Time |
10:41 |
Sent To |
M |
|
| Notes |
| 2008-12-31 10:41:39 | ** DENIED REVIEW ** | | | | | | | | | 1) NOTE: PLEASE SEE FS 481.229, 471.003. WHEN MEETING | | | EXCEPTIONS IN THE STATUTES AS MENTIONED PLANS ARE STILL | | | REQUIRED TO BE DONE BY THE DESIGN PROFESSIONAL AS | | | LISTED. | | | THE PLANS SUBMITTED DO NOT CONTAIN ANY TITLE BLOCKS, | | | PRINTED NAME, SIGNATURE, OR SIGNED AND SEALED. | | | | | | 2) NOTE: PLANS MENTIONS USE OF POSSIBLE EXISTING | | | LAUNDRY CIRCUIT OR RECEPTACLE CIRCUIT. IT IS NOT | | | PERMISSIBLE TO USE THE LAUNDRY CIRCUIT. PLEASE SEE | | | 210.52D, 210.11C2 AND 210.11C3. | | | THE LAUNDRY CIRCUIT MUST BE SEPARATE AND BE AVAILABLE | | | FOR LAUNDRY. | | | THE BATH SHALL BE DEDICATED AS LISTED IN THE ABOVE | | | SECTIONS. THERE IS TWO SEPARATE WAYS TO WIRE THE | | | BATHROOMS HOWEVER THE PLANS DO NOT INDICATE COMPLIANCE | | | WITH EITHER. | | | MUST BE 20AMP AND #12 WHEN WIRING FOR GFI. | | | | | | 2) NOTE: PLANS DO NOT INDICATE ANY NEW ELECTRICAL FOR | | | PROPOSED A/C SYSTEM. | | | PLEASE SEE 210.63, 210.8A, 440.11 FOR MISSING GFI | | | RECEPTACLES, DISCONNECTS ETC | | | | | | 3) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR | | | THE EXISTING ELECTRICAL SERVICE WITH NEW PROPOSED A/C | | | LOADS. | | | PLEASE SEE NEC 220.83. | | | PLEASE INDICATE THE SIZE OF THE ELECTRICAL SERVICE IN | | | ORDER TO DETERMINE IF THE EXISTING IS ADEQUATE FOR NEW | | | LOADS. | | | 215.5,230.2 | | | | | | 4) NOTE: PLEASE SEE FBC 108.3 WHICH REQUIRES THE | | | APPLIED VALUE TO INCLUDE ALL LABOR, DESIGN COST, | | | MATERIALS ETC EVEN IF ANY OF THESE ARE OWNER SUPPLIED. | | | PLEASE SEE VALUATIONS BASED ON THE ADOPTED ICC | | | STANDARDS APPEARS THIS WILL CHANGE THE VALUE AS | | | APPLIED. | | | THE APPLIED SQ FT NOTES 100 SQ FT YET BASED ON THE | | | PLANS THE SQ FT IS HIGHER. | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-12-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-12-01 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-12-01 |
Time |
09:19 |
Sent To |
B |
|
| Notes |
| 2009-12-01 09:20:10 | TO JULIO./WRT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-10-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-28 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-10-27 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2009-10-28 10:24:14 | SENT TO R-21 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-05-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-05-22 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-05-22 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2009-05-22 15:17:22 | TO R-18 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-03-27 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-03-27 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-03-25 |
Time |
10:10 |
Sent To |
Z |
|
| Notes |
| 2009-03-27 10:10:33 | PLACED IN Z BOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-12-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-30 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-30 |
Time |
15:15 |
Sent To |
E |
|
| Notes |
| 2008-12-30 15:15:28 | TO "SFR" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-01-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-01-15 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-12-23 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2008-12-23 15:12:09 | TO "SFR" "Z" |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2009-11-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-11-05 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-11-05 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2009-11-05 15:00:48 | PAID PR# 09019590. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2009-07-24 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-24 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-24 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2009-07-24 13:28:49 | NO ENERGY CALCULATIONS SUBMITTED, NO MECHANICAL PERMIT | | | APPLIED FOR. SEPARATE PLANS AND PERMIT REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-04-08 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2009-04-08 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2009-04-08 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-01-12 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2009-01-12 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2009-01-12 |
Time |
14:54 |
Sent To |
P |
|
| Notes |
| 2009-01-12 15:01:22 | 01/12/2009 | | | PLEASE PROVIDE DUCT SIZE FOR NEW BATHROOM DUCT . PLEASE | | | SEE SECTION M1602 PROHIBITED SOURCES #4 . 2004 FBCR | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2009-10-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-10-29 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-10-29 |
Time |
11:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-06-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-06-01 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-06-01 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-04-08 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2009-04-08 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2009-04-08 |
Time |
09:08 |
Sent To |
M |
|
| Notes |
| 2009-04-08 09:42:44 | *******NOTE********* | | | SHEET A-1 STATES 2007 CODE. PERMIT # 08120504 WOULD BE | | | FBC 2004. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-01-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-13 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-12 |
Time |
16:53 |
Sent To |
B |
|
| Notes |
| 2009-01-13 08:43:50 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. INDICATE CODE CRITERIA. PERSENT CODE ADOPTED IS | | | FBC-2004 WITH 2007 AMENDMENTS. SECTION 106.1.1 | | | | | | 2. BOTH SHEETS. NOTE: ALL PLANS, SPECIFICATIONS, AND | | | ACCOMPANYING DATA BEING FILED FOR PUBLIC RECORD SHALL | | | CONTAIN THE PRINTED NAME OF THE RESPONSIBLE PERSON WITH | | | THE ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. | | | PER SECTION *106.3.4.3. | | | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, | | | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, | | | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA | | | STATUTES 481 AND 471 RESPECTIVELY AND SHOW THE REQUIRED | | | TITLE BLOCK INFORMATION AS REQUIRED IN FAC | | | 61G1-15.23002(2) AND 61G1-16.004. | | | | | | 3. SHT 2 SANITARY RISER DIAGRAM. THE LAVS ARE NOT | | | VENTED AS SHOWN AND THE VENT PAST THE LAVS IS A | | | HORIZONTAL DRY VENT WHICH IS PROHIBITED PER | | | FBC-2004,PLUMBING, SECTION 905.3. VENT CONNECTIONS TO | | | DRAINAGE SYSTEM. EVERY DRY VENT CONNECTING TO A | | | HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF | | | THE HORIZONTAL DRAIN PIPE. SHOW VENT STACK AS A | | | CONTINUATION OF THE WASTE STACK FOR THE LAVS. | | | | | | 4. SHT 2 WATER RISER DIAGRAM. FIXTURE FITTINGS, FAUCETS | | | AND DIVERTERS SHALL BE INSTALLED AND ADJUSTED SO THAT | | | THE FLOW OF HOT WATER FROM THE FITTINGS CORRESPONDS TO | | | THE LEFT-HAND SIDE OF THE FIXTURE FITTING. SECTION | | | 607.4. RISER SHOWS THE HOT WATER TO THE RIGHT SIDE OF | | | THE FIXTURES. PLEASE CORRECT RISER. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2009-11-24 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2009-11-24 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2009-11-24 |
Time |
17:36 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2009-05-31 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-05-31 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-05-31 |
Time |
15:24 |
Sent To |
E |
|
| Notes |
| 2009-05-31 15:28:56 | PLANNING AND ZONING DEPT: ***ZONING FAILED*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | | | | | 3. THE SITE PLAN INDICATES A SLIGHT INCREASE IN THE | | | DIMENSIONS OF THE PROPOSED BATHROOM ADDITION. PLEASE | | | INDICATE ON THE SURVEY THE SETBACK DIMENSIONS FROM THE | | | PROPOSED ADDITION TO ALL ADJACENT PROPERTY LINES. | | | PURSUANT TO THE ZLDR, SECTION 94-72(A)(2): | | | SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT - | | | MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS: | | | | | | A. FRONT: 25 FEET; | | | | | | B. CORNER: 12.5 FEET; | | | | | | C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER | | | IS LESS; | | | | | | D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | | | | ADDITIONALLY, PLEASE ENSURE THAT THE PERMIT DESCRIPTION | | | IS REVISED ACCORDING TO THE PROPOSED REVISED SITE PLAN. | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2009-03-27 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-03-27 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-03-27 |
Time |
15:30 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-12-30 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-12-30 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-12-30 |
Time |
12:27 |
Sent To |
I |
|
| Notes |
| 2008-12-30 12:30:36 | PLANNING AND ZONING DEPT: ***ZONING FAILED*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. THE PERMIT APPLICATION INDICATES THE PROPOSED | | | ADDITION IS 10X12 IN SIZE, BUT THE SURVEY INDICATES | | | THAT THE PROPOSED ADDITION IS 10X5.9. PLEASE CLARIFY. | | | | | | 3. INDICATE THE SEPARATION DISTANCE OF THE PROPOSED | | | ADDITION TO THE EXISTING SHED. NOTE: PURSUANT TO | | | SECTION 94-304(B)(3) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), ACCESSORY STRUCTURES SHALL BE | | | LOCATED NO CLOSER THAN SIX (6) FEET TO THE PRINCIPAL | | | STRUCTURE. | | | | | | 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED/RELOCATED | | | A/C EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR, | | | SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|