| 2009-01-09 14:28:18 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT P-101 THE ENGINEERING FIRM AND THE ARCHITECTURAL |
| | FIRM SHALL INDICATE THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER, (BUSINESS NUMBER), IN THE TITLE BLOCK. FAC |
| | 61G15-23.002(2), 61G1-16.004(2) & FS 471.025, 481.219 & |
| | 481.2055. PLEASE INDICATE BOTH NUMBERS IN TITLE BLOCK. |
| | (SEE ATTACHED SHEETS FROM FLORIDA STATE DBPR WEBSITE |
| | FOR CORRECT NUMBERS). |
| | |
| | 2. SHT P-101 WITH THE LAVS BEING DELETED ON THE VENT |
| | STACK FOR THE WATER CLOSETS, A CLEANOUT IS REQUIRED ON |
| | THE VENT STACK. SECTION 708.3.4. PLEASE INDICATE A |
| | CLEANOUT ON THE VENT PIPE. THE SIZE OF THE CLEANOUT |
| | SHALL BE THE SAME NOMINAL SIZE AS THE PIPE THEY SERVE |
| | PER SECTION 708.7. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |