Plan Review Details - Permit 08120454
Plan Review Stops For Permit 08120454
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-28 Cont ID  
Sent By shill Date 2009-05-28 Time 11:20 Rev Time 0.00
Received By shill Date 2009-05-28 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-26 Cont ID  
Sent By mjacobs Date 2008-12-26 Time 07:45 Rev Time 0.00
Received By mjacobs Date 2008-12-24 Time 16:39 Sent To  
Notes
2008-12-24 16:39:15BUILDING PLAN REVIEW
 PERMIT: 08110316
 ADD: 501 27TH STREET
 CONT: CHILD KAREN
 TEL: (561)310-8207
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12-24-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE PLANS.
  
  
 4) SHEET M3 AND M4: 1609.6.2 WIND DESIGN PROCEDURES
 SHALL BE INDICATED ON THE DRAWINGS FOR THE CONCRETE
 PAD.
 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 5) SHEET E-1: THE FIRE/SMOKE RATED WALL DETAILS: TREMCO
 DETAIL AT THE BOTTOM LEFT CORNER IS MISSING THE UL#
  
 6) 2004 FBC EXISTING: 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE
 PLANS.
  
 7) 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED.
 THE NEW CONCRETE PADS AT BOTH LOCATIONS FAIL TO
 INDICATE THEIR LENGTH AND WIDTH.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561)805-6676
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-05-06 Cont ID  
Sent By dpalmer Date 2009-05-06 Time 16:58 Rev Time 0.00
Received By dpalmer Date 2009-05-06 Time 16:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-26 Cont ID  
Sent By dpalmer Date 2008-12-26 Time 16:21 Rev Time 0.00
Received By dpalmer Date 2008-12-26 Time 16:21 Sent To  
Notes
2008-12-26 16:23:23** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW AND EXISTING. BEFORE GRANTING
 ADDITIONAL LIGHTING , THE EXISTING NEEDS TO BE
 VERIFIED.
  
 2) NOTE: PLEASE ELABORATE NOTE ON PLANS WITH RESPECT TO
 IT/TELCO ROOM DESIGNATION. IF THIS IS NOT AN IT ROOM AS
 DEFINED IN NEC 645.2. PLEASE BE SURE TO ADD TO NOTE
 WHICH WILL STATE *** NO WIRING METHODS IN NEC 645 IS
 PERMITTED**.
 CONFIRMATION OF COUNTY IT/MIS STAFF MAY BE NEEDED TO
 CONFIRM NO WIRING METHODS PERMITTED IN 645 IS DESIRED.
 IF THIS IS NOT AN IT ROOM, ALL WIRING SHALL BE IN
 ACCORDANCE WITH CHAPTERS 1-4.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-05-08 Cont ID  
Sent By mawillia Date 2009-05-08 Time 14:02 Rev Time 0.00
Received By mawillia Date 2009-05-08 Time 13:48 Sent To  
Notes
2009-05-08 14:02:49*****APPROVED*****
  
 THE COMMENT FROM THE PREVIOUS FIRE PLAN REVIEW HAS BEEN
 ADDRESSED; PLAN SHEETS M3 AND FA-1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-01-15 Cont ID  
Sent By mwennerg Date 2009-01-15 Time 10:12 Rev Time 0.00
Received By mwennerg Date 2009-01-15 Time 10:12 Sent To  
Notes
2009-01-15 10:16:19***DENIED***
  
 1) PLANS INDICATE THE INSTALLATION OF A NEW DUCT SMOKE
 DETECTOR. DETAILS HAVE NOT BEEN PROVIDED TO EXPLAIN THE
 SEQUENCE OF OPERATION, BUT ONLY THAT THE DEVICE WILL BE
 TIED INTO THE BUILDING FIRE ALARM SYSTEM. PLEASE NOTE
 THAT THE ACTIVATION OF A DUCT SMOKE DETECTOR SHALL
 INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS. PLEASE ADD NOTE TO THE PLANS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-17 Cont ID  
Sent By btrobaug Date 2009-11-17 Time 14:49 Rev Time 0.00
Received By btrobaug Date 2009-11-17 Time 14:49 Sent To M
Notes
2009-11-17 14:49:37TO RON'S DESK./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-28 Cont ID  
Sent By dpalmer Date 2009-04-28 Time 15:18 Rev Time 0.00
Received By dpalmer Date 2009-04-28 Time 15:18 Sent To  
Notes
2009-04-28 15:18:50TO C-10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-24 Cont ID  
Sent By rregueir Date 2009-01-24 Time 17:42 Rev Time 0.00
Received By rregueir Date 2008-12-22 Time 10:38 Sent To PC
Notes
2008-12-22 10:38:33TO "COMM" BD#23

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-05-13 Cont ID  
Sent By rkussner Date 2009-05-12 Time 15:39 Rev Time 0.00
Received By rkussner Date 2009-05-12 Time 15:39 Sent To  
Notes
2009-05-12 15:41:50***LANDSCAPE REVIEW PASSED WITH PROVISO***
  
 1. COCOPLUM SHALL BE 3- GALLON SIZE MATERIAL 24 INCHES
 IN HEIGHT AND SPACED 24 INCHES ON CENTER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-11-24 Cont ID  
Sent By rregueir Date 2009-11-24 Time 14:01 Rev Time 0.00
Received By rregueir Date 2009-11-24 Time 14:00 Sent To  
Notes
2009-11-24 14:01:00REVISED M3 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-04-30 Cont ID  
Sent By rregueir Date 2009-04-30 Time 13:36 Rev Time 0.00
Received By rregueir Date 2009-04-30 Time 12:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-01-24 Cont ID  
Sent By rregueir Date 2009-01-24 Time 17:42 Rev Time 0.00
Received By rregueir Date 2009-01-24 Time 17:32 Sent To PC
Notes
2009-01-24 17:42:17REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NEW MECHANICAL ROOM WILL SERVE AS A RETURN AIR
 PLENUM. SHOW TYPE OF FINISH ON INTERIOR SIDE OF
 EXTERIOR WALLS TO SHOW COMPLIANCE WITH FBCM 603.8 AND
 FBCM 603.9.
  
 2. WHAT TYPE OF DOOR IS LOCATED AT THE ENTRANCE TO THE
 MECHANICAL ROOM? A WOOD DOOR AT THIS LOCATION IS NOT
 PERMISSABLE. MATERIALS EXPOSED WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84
 PER FBCM 602.2.1. ENSURE DOOR AND ALL OTHER MATERIALS
 EXPOSED IN THIS ROOM MEET THIS REQUIREMENT. EXAMPLE:
 DETAIL ON M4 CALLS FOR PVC TO BE USED FOR CONDENSATE
 PIPING. PVC MAY NOT BE LOCATED IN THE PLENUM.
  
 3. PROVIDE AUXILIARY OR SECONDARY DRAIN PROTECTION IN
 ACCORDANCE WITH FBCM 307.2.3.
  
 4. FOR THE OUTDOOR CONDENSING UNIT: MECHANICAL
 APPLIANCES AND THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST WIND PRESSURES AS
 DETERMINED IN ACCORDANCE WITH FBCM 301.13. PROVIDE
 MANUFACTURER'S DATA SHOWING THIS APPLIANCE IS DESIGNED
 FOR WIND RESISTANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2009-05-13 Cont ID  
Sent By lfranco Date 2009-05-13 Time 16:22 Rev Time 0.00
Received By lfranco Date 2009-05-13 Time 16:22 Sent To B
Notes
2009-05-13 16:24:48PLANNING AND ZONING: **** PASSED WITH PROVISO ****
  
 1. PLEASE REFER TO LANDSCAPE PROVISO COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER, LANDSCAPE PLANNER @ 822-1435.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-01-05 Cont ID  
Sent By lfranco Date 2009-01-05 Time 17:21 Rev Time 0.00
Received By lfranco Date 2009-01-05 Time 17:21 Sent To  
Notes
2009-01-05 17:26:19PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. MECHANICAL EQUIPMENT IS REQUIRED TO BE SCREENED, THE
 SITE PLAN SHALL INCLUDE THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF WALL/HEDGES AROUND THE
 MECHANICAL EQUIPMENT/A/C UNIT, PROVIDE SETBACK DISTANCE
 FROM PROPERTY LINE.
  
 3. PURSUANT TO SECTION 94-444(B) OPEN SPACE
 STANDARDS:
  
 (B) FUEL OR OIL OR PROPANE TANKS, GENERATORS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND
 STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]