| 2008-12-23 09:09:15 | PROJECT: 2800 GEORGIA AVENUE/GREEN TERRACE APARTMENTS |
| | |
| | PROJECT DETAIL: REPAIR/REBUILD BALCONIES |
| | |
| | CODE REVIEW: |
| | |
| | 2004 FLORIDA RESIDENTIAL BUILDING CODE |
| | 2004 FLORIDA EXISTING BUILDING CODE |
| | 2004 FLORIDA BUILDING CODE |
| | |
| | STATUS: FAILED |
| | |
| | PLAN REVIEW COMMENTS: |
| | |
| | |
| | PERFORMED A PRELIMINARY INSPECTION OF SOME OF THE |
| | RE-BUILT BALCONIES. |
| | |
| | 1) PLEASE INDICATE THE BUILDING AND UNIT NUMBERS OF THE |
| | BALCONIES THAT ARE TO BE REPAIRED/RE-BUILT. |
| | |
| | 2) PLEASE SUBMIT WIND, LIVE, AND DEAD LOAD CALCULATIONS |
| | FOR THE RE-CONSTRUCTION OF THE APPLICABLE BALCONIES: |
| | |
| | 407.3.1 NEW STRUCTURAL FRAME MEMBERS. |
| | |
| | NEW STRUCTURAL FRAME MEMBERS USED IN THE REPAIR OF |
| | DAMAGED BUILDINGS, INCLUDING ANCHORAGE AND CONNECTIONS, |
| | SHALL COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1603.1 GENERAL. |
| | CONSTRUCTION DOCUMENTS SHALL SHOW THE SIZE, SECTION AND |
| | RELATIVE LOCATIONS OF STRUCTURAL MEMBERS WITH FLOOR |
| | LEVELS, COLUMN CENTERS AND OFFSETS FULLY DIMENSIONED. |
| | THE DESIGN LOADS AND OTHER INFORMATION PERTINENT TO THE |
| | STRUCTURAL DESIGN REQUIRED BY SECTIONS 1603.1.1 THROUGH |
| | 1603.1.8 SHALL BE CLEARLY INDICATED ON THE CONSTRUCTION |
| | DOCUMENTS FOR PARTS OF THE BUILDING OR STRUCTURE. |
| | |
| | 1603.1.1 FLOOR LIVE LOAD. |
| | THE UNIFORMLY DISTRIBUTED, CONCENTRATED AND IMPACT |
| | FLOOR LIVE LOAD USED IN THE DESIGN SHALL BE INDICATED |
| | FOR FLOOR AREAS. LIVE LOAD REDUCTION OF THE UNIFORMLY |
| | DISTRIBUTED FLOOR LIVE LOADS, IF USED IN THE DESIGN, |
| | SHALL BE INDICATED. |
| | |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | 2. WIND IMPORTANCE FACTOR, IW, AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M2) TO BE USED FOR THE SELECTION OF |
| | EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 1609.1 APPLICATIONS. |
| | BUILDINGS, STRUCTURES AND PARTS THEREOF SHALL BE |
| | DESIGNED TO WITHSTAND THE MINIMUM WIND LOADS PRESCRIBED |
| | HEREIN. DECREASES IN WIND LOADS SHALL NOT BE MADE FOR |
| | THE EFFECT OF SHIELDING BY OTHER STRUCTURES. |
| | |
| | |
| | 3) PLEASE SUBMIT PRODUCT APPROVALS FOR THE INDICATED |
| | SIMPSON HANGERS: |
| | |
| | 9B-72.005 SCOPE. |
| | (1) PRODUCTS IN THE FOLLOWING CATEGORIES AS DEFINED BY |
| | SUBCATEGORIES OF SUBSECTION 9B-72.010(31), F.A.C., |
| | SHALL BE AVAILABLE FOR |
| | APPROVAL BY THE COMMISSION PURSUANT TO RULE 9B-72.090, |
| | F.A.C., FOR USE IN THE STATE: |
| | (A) PANEL WALLS; |
| | (B) EXTERIOR DOORS; |
| | (C) ROOFING PRODUCTS; |
| | (D) SKYLIGHTS; |
| | (E) WINDOWS; |
| | (F) SHUTTERS; AND |
| | (G) STRUCTURAL COMPONENTS. |
| | (2) THIS RULE APPLIES TO APPROVAL OF PRODUCTS AND |
| | SYSTEMS, WHICH COMPRISE THE BUILDING ENVELOPE AND |
| | STRUCTURAL FRAME, FOR |
| | COMPLIANCE WITH THE STRUCTURAL REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE. |
| | SPECIFIC AUTHORITY 553.842(1) FS. LAW IMPLEMENTED |
| | 553.842(5) FS. HISTORY?NEW 11-22-06. |
| | |
| | 4.) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE |
| | FOLLOWING: |
| | |
| | FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED WITH |
| | THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE WORK |
| | DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) THE POSTING |
| | OF THE NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE |
| | BEFORE THE FIRST INSPECTION. |
| | |
| | |
| | |
| | PLAN REVIEW: KEN CONRAD |