Plan Review Details - Permit 08120332
Plan Review Stops For Permit 08120332
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2008-12-17 Cont ID  
Sent By kstevens Date 2008-12-17 Time 19:02 Rev Time 0.00
Received By kstevens Date 2008-12-17 Time 19:02 Sent To  
Notes
2008-12-18 07:17:45 
  
  
 PASSED/PROVISO
  
 REVISION REQUIRED
  
 THE PIPING SHALL BE A MINIMUM 2-1/2" FOR THE SECTIONS
 OF PIPE BETWEEN P24G AND P23G ON LINE 1 AND THE
 STUB-OUT AND SHUT OFF VALVE SHALL BE 1" FOR THE FIRST
 P17G ON LINE ONE PER TABLE 402.4(1). -- MANUF. ITEM 24
 ANETS GOLDEN GRILL CHROME GAS GRILLS DOES NOT REFLECT
 THE BTU LOAD INDICATED ON THE RISER DIAGRAM. THE 72,000
 BTU IS INDICATED AS "LP" BTUH ON THE MANUF.
 SPECIFICATION SHEETS. (MANUF. ITEM 24.1 IS APPROVED FOR
 THE IMPERIAL SNAP ACTION GRIDDLES AS P24G). PLEASE
 CLARIFY.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-17 Cont ID  
Sent By kstevens Date 2008-12-17 Time 19:04 Rev Time 0.00
Received By kstevens Date 2008-12-16 Time 15:59 Sent To  
Notes
2008-12-16 15:59:22TO "G" BOX