Plan Review Details - Permit 08120329
| Plan Review Stops For Permit 08120329 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-08-07 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-08-07 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-08-07 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2009-08-07 15:05:58 | *****REVISION, DATED 7/17/09, APPROVED***** | | | | | | THE COMMENT FROM THE PREVIOUS REVIEW HAS BEEN | | | ADDRESSED; REVISED PLAN SHEETS FP-4A AND FP-7 WERE | | | STAMPED, INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2009-08-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-08-04 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-08-04 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2009-08-04 10:51:45 | *****REVISION, DATED 7/17/09, DENIED***** | | | | | | THE SUBMITTED PLAN SHEETS FP-4A AND FP-7 HAVE NOT BEEN | | | SIGNED AND SEALED BY THE ENGINEER OF RECORD. BE ADVISED | | | THAT THE CITY OF WEST PALM BEACH'S FILE SET HAS JAMES | | | M. CURTIS' STAMP. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-05-13 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-05-13 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-05-13 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2009-05-13 10:00:44 | REVISED SHEETS FP-1, FP-3 FP-4 DATED 4/20/09 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2008-12-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-23 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-23 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2008-12-23 15:32:10 | PLANS APPROVED AND STAMPED ON THIS DATE. | | | | | | 1) TWO (2) HOUR HYDROSTATIC TEST REQUIRED PER NFPA 13, | | | 2002. | | | | | | 2) FIRE SPRINKLER PIPE INSPECTION REQUIRED. CODE 603 | | | | | | 3) FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED WITH | | | KNOX LOCKING CAPS PRIOR TO FINAL INSPECTION. | | | | | | 4) IN ADDITION TO ELECTRONIC SUPERVISION, DOUBLE CHECK | | | DETECTOR ASSEMBLY TO BE SECURED WITH CHAIN AND LOCK IN | | | ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 5) FIRE PUMP INSTALLATION TO COMPLY WITH THE | | | REQUIREMENTS OF NFPA 20, 2003. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-05-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-04-30 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-04-30 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2009-04-30 16:25:44 | TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-12-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-23 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-17 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2008-12-17 10:58:49 | TO "F" BOX |
|
|
|