Plan Review Details - Permit 08120314
Plan Review Stops For Permit 08120314
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-03-03 Cont ID  
Sent By rmcdouga Date 2009-03-03 Time 14:32 Rev Time 0.00
Received By rmcdouga Date 2009-03-03 Time 14:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-03-03 Cont ID  
Sent By rmcdouga Date 2009-03-03 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2009-03-03 Time 10:40 Sent To  
Notes
2009-03-03 10:42:52OWNER BUILDER SUBMITTED ENERGY CALCS. STATUS WILL BE
 CHANGED TO P WHEN IMPACT FEES ARE PAID AND STAMPED
 PLANS RETURNED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-03-02 Cont ID  
Sent By rmcdouga Date 2009-03-02 Time 11:51 Rev Time 0.00
Received By rmcdouga Date 2009-03-02 Time 11:51 Sent To M
Notes
2009-03-02 11:56:552004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 3) SUBMIT TWO (2) COPIES OF ENERGY CALCULATION FORMS AS
 REQUIRED BY FBC 13-600.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-12 Cont ID  
Sent By btrobaug Date 2009-01-12 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2009-01-12 Time 13:21 Sent To  
Notes
2009-01-12 13:22:222004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 3) SUBMIT TWO (2) COPIES OF ENERGY CALCULATION FORMS AS
 REQUIRED BY FBC 13-600.
  
 4) THE MINIMUM R-VALUE FOR A 2 X 6 FRAME WALL IS R-19
 PER FBC 13-602.1.C.1.1. PLEASE REVISE WALL SECTION ON
 A-2.
  
 5) THE R-30 BATT CEILING INSULATION SPECIFIED ON A-2 IS
 9-1/2" THICK AND WILL NOT ALLOW FOR FREE AIR FLOW
 BETWEEN THE 2 X 8 RAFTERS/JOISTS. THE MINIMUM ALLOWED
 FOR A SINGLE ASSEMBLY ROOF IS R-19 WHICH IS 5-1/2"
 THICK. SEE FBC 13-604.1.ABC.1. PLEASE REVISE.
  
 6) SHOW COMPLIANCE WITH R703.6.3. WHERE CEMENT PLASTER
 (STUCCO) IS TO BE APPLIED TO LATH OVER FRAME
 CONSTRUCTION, MEASURES SHALL BE TAKEN TO PREVENT
 BONDING BETWEEN THE CEMENT PLASTER AND THE
 WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED
 BETWEEN THE WATER-RESISTIVE BARRIER AND THE CEMENT
 PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER
 MATERIAL; OR
 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP; OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 7) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 8) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE ROOF
 COVERING IS FOR UNDERLAYMENT AND IS NOT FOR A FLAT ROOF
 SYSTEM. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 FLAT ROOF SYSTEM THAT WILL BE INSTALLED. SPECIFY WHICH
 ONE OF THE APPROVED ASSEMBLIES LISTED IN THE NOA WILL
 BE USED. SPECIFY THE FASTENING OPTION AND DESIGN
 PRESSURE THAT WILL BE USED. PROVIDE RAS 117 FOR
 ENHANCED FASTENING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY LIMITATION #7 OF THE NOA. DCA RULE 9B-72
  
 9) THE VALUE FOR THE ADDITION SPECIFIED ON THE
 APPLICATION IS LOW. BASED ON THE ICC BUILDING VALUATION
 DATA THE COST FOR 312 SQFT TYPE VI CONSTRUCTION IS
 $30,210.00. THE VALUE HAS BEEN ADJUSTED AND ADDITIONAL
 FEES OF $599.67 ARE DUE. FBC 108.3* CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-02-23 Cont ID  
Sent By btrobaug Date 2009-02-23 Time 11:51 Rev Time 0.00
Received By btrobaug Date 2009-02-23 Time 11:10 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-19 Cont ID  
Sent By btrobaug Date 2008-12-19 Time 14:44 Rev Time 0.00
Received By btrobaug Date 2008-12-19 Time 14:29 Sent To M
Notes
2008-12-19 14:44:22 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 3} A LAUNDRY RECEPTACLE OUTLET(S) IS SUPPLIED BY A
 20-AMPERE BRANCH CIRCUIT. THIS CIRCUIT CAN HAVE NO
 OTHER OUTLETS. SEE 210.11(C)(2) FOR FURTHER
 INFORMATION.*** THE PANEL SCHEDULE INDICATES THE
 EXTERIOR
  
 4} THE DRYER RATED AT 5000 WATTS ON THE PANEL SCHEDULE
 IS SHOWN WITH A 20 MP OVER CURRENT PROTECTION, AND
 SHOWN AS EXISTING. THE DRYER CALCULATION SHOULD BE
 5000/240=20.83 A25 AMP BREAKER (240.6) AND #10
 CONDUCTORS (310.16). ALSO THE FRAME IS REQUIRED TO BE
 GROUNDED WITH AN EQUIPMENT GROUNDING CONDUCTOR PER
 250.140 AND 251.122.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-10 Cont ID  
Sent By adarroug Date 2009-02-10 Time 09:59 Rev Time 0.00
Received By adarroug Date 2009-02-10 Time 09:59 Sent To Z
Notes
2009-02-10 09:59:53TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-12 Cont ID  
Sent By rmcdouga Date 2009-01-12 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2008-12-16 Time 09:25 Sent To  
Notes
2008-12-16 09:29:19TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-03-03 Cont ID  
Sent By rmcdouga Date 2009-03-03 Time 10:51 Rev Time 0.00
Received By rmcdouga Date 2009-03-03 Time 10:51 Sent To  
Notes
2009-03-03 10:53:47MECHANICAL PROVISO
  
 BALANCED RETURN AIR IS REQUIRED PER FBC MECHANICAL
 601.4.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-12-22 Cont ID  
Sent By rregueir Date 2008-12-22 Time 18:37 Rev Time 0.00
Received By rregueir Date 2008-12-22 Time 18:35 Sent To B
Notes
2008-12-22 18:37:03NO INFORMATION PROVIDED ON PLANS FOR VENTILATION, AIR
 CONDITIONING OR DRYER EXHAUST. SEPARATE PLANS AND
 PERMIT APPLICATION REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-02-26 Cont ID  
Sent By kstevens Date 2009-02-26 Time 16:47 Rev Time 0.00
Received By kstevens Date 2009-02-26 Time 16:47 Sent To B1
Notes
2009-02-26 16:48:57PASSED/PROVISO -- 3" REQUIRED TO W/M (406.3) & C/O AT
 W/M TO BE 4' ABOVE THE FLOOR (708.9).

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-18 Cont ID  
Sent By kstevens Date 2008-12-18 Time 16:16 Rev Time 0.00
Received By kstevens Date 2008-12-18 Time 16:16 Sent To E
Notes
2008-12-18 16:20:31DENIED
 REFERENCE:
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-3 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN OF THE PLANS SHALL PRINT THEIR NAME AND AFFIX
 THEIR SIGNATURE ON SAID PLANS. FS 481.029 OR 471.003 OR
 THE EXEMPTIONS TO THOSE STATUTES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-02-23 Cont ID  
Sent By mcruz Date 2009-02-23 Time 08:21 Rev Time 0.00
Received By mcruz Date 2009-02-23 Time 08:19 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-17 Cont ID  
Sent By mcruz Date 2008-12-17 Time 12:08 Rev Time 0.00
Received By mcruz Date 2008-12-17 Time 11:57 Sent To E
Notes
2008-12-17 12:08:03PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE THE SETBACK DIMENSIONS FROM THE PROPSED
 ADDITION TO ALL ADJACENT PROPERTY LINES. NOTE: PURSUANT
 TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZDLR), SECTION 94-75(A)(2):
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 3. INDICATE THE SEPARATION DISTANCE OF THE PROPOSED
 ADDITION TO THE EXISTING WOOD FRAME GARAGE. NOTE:
 PURSUANT TO SECTION 94-304(B)(3) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), ACCESSORY STRUCTURES
 SHALL BE LOCATED NO CLOSER THAN SIX (6) FEET TO THE
 PRINCIPAL STRUCTURE.
  
 4. INDICATE IF ANY TREES WILL BE REMOVED AS A RESULT OF
 THE PROPOSED PROJECT. IF YES, A TREE ALTERATION/REMOVAL
 PERMIT WILL BE REQUIRED. CONTACT ROBERT KUSSNER, CITY
 LANDSCAPE PLANNER, AT (561) 822-1462 FOR THE
 APPLICATION.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  