Plan Review Details - Permit 08120285
Plan Review Stops For Permit 08120285
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-08-03 Cont ID  
Sent By jwitmer Date 2009-08-03 Time 17:59 Rev Time 1.00
Received By jwitmer Date 2009-08-03 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-08 Cont ID  
Sent By mjacobs Date 2009-04-08 Time 15:43 Rev Time 0.00
Received By mjacobs Date 2009-04-07 Time 15:43 Sent To PC
Notes
2009-04-07 15:43:21WAITING FOR ADDITIONAL INFORMATION FROM ENGINEER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-02-24 Cont ID  
Sent By mjacobs Date 2009-02-24 Time 12:08 Rev Time 0.00
Received By mjacobs Date 2009-02-23 Time 16:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-23 Cont ID  
Sent By mjacobs Date 2008-12-23 Time 13:43 Rev Time 0.00
Received By mjacobs Date 2008-12-23 Time 16:52 Sent To  
Notes
2008-12-23 13:43:01BUILDING PLAN REVIEW
 PERMIT: 08120285
 ADD: 1919 NORTH FLAGLER DR.
 CONT: ANDERSON MOORE CONST.
 TEL: (561)753-7400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12/23/08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET T: PLANS SUBMITTED FOR PERMIT (FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) THE DRAWINGS NEED TO STATE THE TYPE, HEIGHT AND
 NUMBER OF STORIES OF BUILDING PER TABLE 601 AND 503 AND
 THE OCCUPANT LOAD PER TABLE 1004.1.2.
  
 5) IF THERE IS A FIRE SPRINKLER SYSTEM IN THE BUILDING
 PLEASE STATE THIS INFORMATION ON THE DRAWINGS. NOW THE
 SPACE IS BEING ALTERED, THE DRAWINGS NEED TO SHOW THE
 LOCATIONS OF THE SPRINKLER HEADS IN RELATION TO THE NEW
 CONSTRUCTED ROOMS. THE SPRINKLER HEADS CAN BE SHOWN ON
 THE REFLECTED CEILING PLANS. FBC 106.3.5.1.1(5) FS
 553.79 (2).
  
 6) SHEET A1.2 DETAIL D9 BREAK SINKS: 11-4.24.2 SINKS,
 HEIGHT. SINKS SHALL BE MOUNTED WITH THE COUNTER NO
 HIGHER THAN 34" ABOVE THE FINISH FLOOR. 11-4.24.3 KNEE
 CLEARANCE THAT IS AT LEAST 27" HIGH 30" WIDE, AND 19"
 DEEP SHALL BE PROVIDED UNDERNEATH SINKS. 11-4.24.5
 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT LEAST 30
 INCHES BY 48 INCHES COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES UNDERNEATH THE SINK TYPE OF FAUCETS 11-4.24.7
 ETC. THE MICROWAVE SHALL MEET THE REQUIREMENTS OF
 11-4.27: THE CLEAR FLOOR SPACE 11-4.27.2: THE HEIGHT OF
 THE EQUIPMENT 11-4.27.3 AND THE OPERATION CONTROLS
 11-4.27.4. SHOW COMPLIANCE.
  
 7) SHEET A2.2 FLOOR TRANSITION. 11-4.5.2 CHANGES IN
 LEVEL GREATER THAN 1/2 INCH SHALL BE ACCOMPLISHED BY
 MEANS OF A RAMP THAT COMPLIES WITH 11-4.7 OR 11-4.8.
 CHANGES IN LEVEL BETWEEN 1/4 INCH AND 1/2 INCH SHALL BE
 BEVELED WITH A SLOPE NO GREATER THAN 1:2[SEE FIGURE
 7(D)]. IF CARPET OR TILE IS USED ON A GROUND OR FLOOR
 SURFACE, THE MAXIMUM PILE THICKNESS SHALL BE 1/2 INCH.
 11-4.5.3. THE 9/16 INCH TRANSITION STRIP IS GREATER
 THAN 1/2 INCH.
  
 8) SHEET A2.1: 715.3 THE DOOR SCHEDULE NEED TO STATE
 THE PROTECTION RATING OF NUMBER 2 IN ACCORDANCE WITH
 TABLE 715.3. THE GLAZING LOCATED BETWEEN ROOMS 300 AND
 301 SHALL BE TESTED IN ACCORDANCE WITH NFPA 257,
 INCLUDING, THE HOSE STREAM TEST, IN ACCORDANCE WITH
 715.4. PROVIDE THE MANUFACTURE INFORMATION FOR THE
 GLAZING IN THE FIRE WALL. FIRE-PROTECTION-RATED GLAZING
 SHALL BEAR A LABEL OR OTHER IDENTIFICATION SHOWING THE
 NAME OF THE MANUFACTURE, THE TEST STANDARD AND THE FIRE
 PROTECTION RATING. THIS INFORMATION SHALL BE
 PERMANENTLY AFFIXED: SECTION 715.3.6.3.
 FIRE-PROTECTION-RATED GLAZING INSTALLED IN FIRE
 ASSEMBLIES IN AREAS SUBJECT TO HUMAN IMPACT IN
 HAZARDOUS LOCATIONS SHALL COMPLY WITH CH. 24.
  
 9) PROVIDE DETAIL INFORMATION FOR THE STRUCTURAL
 FRAMING OF THE SOFFITS IN THE LOBBY AND ENTRY AREAS.
 ADDITIONAL INFORMATION REQUIRED. 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-08-21 Cont ID  
Sent By dpalmer Date 2009-08-21 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2009-08-21 Time 08:59 Sent To PC
Notes
2009-08-21 09:00:37REV E-1, E-2 ALSO ADDED MTS FOR FUTURE PORTABLE
 GENERATOR.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-08-05 Cont ID  
Sent By dpalmer Date 2009-08-05 Time 17:39 Rev Time 0.00
Received By dpalmer Date 2009-08-05 Time 17:39 Sent To  
Notes
2009-08-05 17:39:31 
 ** DENIED REVIEW OF REVISIONS **
  
 1) NOTE: PLANS HAVE BEEN REVISED TO NOW INCLUDE MANUAL
 TRANSFER SWITCH FOR TENANT SPACE. HOW WILL FEED COME
 INTO BUILDING FOR TRANSFER SWITCH?
 PLEASE SHOW HOW THIS WILL TAKE PLACE.
 PLEASE EXPLAIN HOWEVER AND WHERE THE DISCONNECT MEANS
 WILL BE PROVIDED FOR POWER FROM GENERATOR.
 PLEASE SEE 225.34, 225.31-225.39, ALSO 702.11.
  
 2) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED MTS. 90.7,110.3, 702.6.
  
 3) NOTE: PANEL SCHEDULES AND LOAD CALCULATIONS HAVE
 REVISED ITEMS SHOWN IN REV #4 HOWEVER NO OTHER
 ELECTRICAL PLANS FOR LAYOUT OF ELECTRICAL EQUIPMENT WAS
 SUBMITTED TO REVISE THE ACTUAL ITEMS ON PLANS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-04-03 Cont ID  
Sent By dpalmer Date 2009-04-03 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2009-04-03 Time 12:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-03-04 Cont ID  
Sent By dpalmer Date 2009-03-04 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2009-03-04 Time 14:38 Sent To  
Notes
2009-03-05 09:45:28NOTE ADDED 3/5/08
  
 THE LIFE SAFETY CODE NOTED ON PLANS STATES THE 2005
 EDITION. HOWEVER THERE IS A 2003 OR 2006. THERE IS NO
 2005. THIS PROJECT AS APPLIED FOR PERMIT IS UNDER THE
 2003 NFPA-101. PLEASE ADJUST NOTES WHEN MAKING CHANGES
 TO PLANS.
2009-03-04 14:38:19** DENIED 2ND REVIEW **
  
 ** SOME ITEMS REQUESTED TO SHOW MINIMUM CODE COMPLIANCE
 IS NOW ON PLANS FOR FIRST REVIEW.
  
 1) NOTE: A COMMENT PREVIOUSLY MADE BY THE FIRE MARSHAL
 REVIEWER WITH RESPECT TO CO2 DETECTORS WAS ANSWERED
 WITH A STATEMENT THAT THE OVEN HAS NOW BEEN REMOVED.
 HOWEVER THE FACT IS PER THE ELECTRICAL PLANS THE OVEN
 AS WELL AS THE COOK-TOP STILL EXISTS.
 ** THIS IS NOTED FOR INFORMATION AND WILL BE FORWARDED
 TO THE FIRE REVIEWER. THIS MAY ELECTRICAL PLANS
 DEPENDING ON COMMENTS AND TYPE OF EQUIPMENT BEING
 INSTALLED..
  
 2) NOTE: ON PREVIOUS REVIEW THE CODE SECTION WAS GIVEN
 WITH RESPECT TO THE STORAGE TYPE WATER HEATERS NEEDING
 TO HAVE LOAD FIGURED AS A CONTINUOUS LOAD. THE RESPONSE
 MENTIONS REVISED LOADS ARE NOW SHOWN. HOWEVER THE WATER
 HEATER STATES IT IS SHOWN AT 125% WHICH IS 3KW. IF THE
 UNIT IS 3KW, THEN THE 125% REQUIRED WOULD BE ABOVE
 THIS. THE UNIT ON THE PLANS AS WELL AS THE PLUMBING
 PLANS INDICATES THE BASE KW AT 3KW.
 PLEASE ADJUST. 422.13, 220.
  
 3) NOTE: PREVIOUS REVIEW REQUESTED TO SUBMIT AND SHOW
 LIGHTING PERFORMANCE CALCULATIONS/LIGHTING DENSITIES
 PER 13-415.2,13-415.2.ABC.1.1 AND .1.2.
 THE PLANS HAVE NOW BEEN REVISED TO INCLUDE CALCULATIONS
 HOWEVER CODE COMPLIANCE DOES NOT APPEAR TO BE CORRECT.
 FOR EXAMPLE:
 ROOM #305 DOES NOT INCLUDE ANY OF THE *K* FIXTURES ON
 THE CALCULATIONS. THE BD FIXTURES ARE ALSO SHOWN AT A
 MUCH LOWER WATTAGE ON THE TABLE ALONG WITH A NUMBER OF
 FIXTURES LOWER THEN WHAT IS SHOWN ON PLANS.
 ANOTHER ROOM WOULD BE #307.
  
 FOR EXAMPLE: THE NOTES AT THE BOTTOM OF THE
 CALCULATIONS ALSO STATES THERE ARE LIGHTS EXEMPT PER
 13-415.2.ABC.1.1. PLEASE SEE THIS SECTION OF THE CODE
 WHICH ONLY EXEMPTS LIGHT IN ANY ONE ARE FROM BEING
 FIGURED IN THE CALCULATIONS IF THE OTHER LIGHTING IN
 THE AREA WHICH IS CONTROLLED COMPLETELY SEPARATELY IS
 THE GREATER OF THE TWO. IN ORDER TO USE THIS EXEMPTION,
 THERE MUST BE ALIGHTING SYSTEM OR CONTROLS IN PLACE
 WHICH DOES NOT PERMIT BOTH POSSIBLE AREAS/ZONES ETC
 FROM BEING *ON* AT THE SAME TIME. BASED ON THE LIGHTING
 CONTROLS SHOWN IT IS POSSIBLE FOR ALL LIGHTS TO BE ON
 AT THE SAME TIME.
 IF SUCH SYSTEM EXISTS PLEASE PROVIDE WIRING DETAILS OR
 SYSTEM ON PLANS.
  
 FOR EXAMPLE: THE ARCHITECTURAL PLANS SHOW THE LIGHTING
 FIXTURES AND LAYOUTS WHICH ARE NOT THE SAME ON THE
 ELECTRICAL PLANS. ONE LOCATION WOULD BE ROOM 310.
  
 *** PLEASE BE SIRE TO GO OVER THE REST OF THE
 CALCULATIONS AS THERE ARE OTHER AREAS IN WHICH THE
 LIGHTING CALCULATIONS DO NOT INDICATE THE WATTAGES
 SHOWN ON THE FIXTURE LEGEND. PLEASE KEEP IN MIND THE
 WATTAGES ARE BASED ON THE RATINGS OF THE FIXTURES NOT
 THE BULBS INCLUDING THE POWER FACTORS OF BALLAST ON
 HID/FLUORESCENT FIXTURES.
  
 ** THE ABOVE ARE ONLY A FEW EXAMPLES GIVEN AS A BENEFIT
 TO THE DESIGN TEAM. THESE EXAMPLES MAY NOT BE AN
 EXHAUSTED LIST.
  
 4) NOTE: PLEASE IDENTIFY THE ROOF TOP GFI FOR THE
 CONDENSING UNITS. PER 210.63,210.8B3 NEW COMMENT
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-01-06 Cont ID  
Sent By dpalmer Date 2009-01-06 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2009-01-06 Time 11:48 Sent To  
Notes
2009-01-06 15:59:14NOTE ADDED 1/6/08 3:58PM
  
 IF BUILDIGN CONTAINS NEW OR EXISTING FIRE ALARM SYSTEM,
 PLEASE INCLUDE ALL LOCATIONS, DEVICE HIGGHTS AND LEVELS
 TO MEET THE ADA SECTION OF THE FBC. SEE 11-4.28.1,.2
 AND .3.
2009-01-06 11:48:50** DENIED REVIEW **
  
  
  
 1) NOTE: PLEASE SUBMIT THE REQUIRED LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2,
 13-415.2.ABC.1.1, .1.2.
 PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND WITH
 SPECIFIC FIXTURES. CODE COMPLIANCE CAN NOT BE
 DETERMINED OF LIGHTING LEVELS AND FOR ITEMS SUCH AS
 TANDEM WIRING PER 13-415.1.ABC.3 NEEDS TO BE CONFIRMED.
  
 2) NOTE: PLEASE SEE NEC 645.4 FOR REQUIREMENTS OF AN IT
 ROOM. THE PLANS INDICATE AN IT ROOM HOWEVER ALL ITEMS
 LISTED IN 645.4 ARE NOT SHOWN ON PLANS.
 NO DISCONNECTING MEANS SHOWN FOR PANEL OR A/C
 EQUIPMENT.
 IF THIS IS NOT AN IT ROOM BECAUSE IT DOES NOT MEET ALL
 ITEMS IN THE SECTION ABOVE THEN *NO* WIRING METHODS AS
 PERMITTED IN 645 IS PERMITTED. THE FACT IS ALL WIRING
 SHALL COMPLY WITH CHAPTERS 1-4.
 PLEASE VERIFY WIRING METHODS, PLEASE VERIFY WHAT THE
 ACTUAL ROOM DESIGNATION IS GOING TO BE AND PLEASE
 ADJUST ALL AS REQUIRED.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2 FOR LIGHTING
 CONTROLS. SOME LOCATIONS ON PLANS ONLY INDICATE WHAT
 APPEAR TO BE A SINGLE POLE SWITCH AND NOT AN OCCUPANCY
 SENSOR TYPE OF DEVICE.
 (IT ROOM ETC).
  
 4) NOTE: PANEL *D* SHOWS HOW THE LOADS WERE DETERMINED
 PER 220.56 FOR APPLIANCES IN OTHER THAN DWELLING UNITS
 HOWEVER HOW ARE THE OTHER LOADS SHOWN ON PANEL DERIVED.
 RECEPTACLES, LIGHTING, CONTINUOUS LOADS?
 220.12, 220.14, 220.42, 220.44 ETC. CONTINUOUS LOADS,
 215.3,230.42 ETC.
 WATER HEATER CONTINUOUS LOAD AT 125%.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-08-04 Cont ID  
Sent By mawillia Date 2009-08-04 Time 12:53 Rev Time 0.00
Received By mawillia Date 2009-08-04 Time 12:30 Sent To  
Notes
2009-08-04 12:47:09*****REVISION, DATED 7/01/09, APPROVED
  
 OF THE 6 REVISED SHEETS THAT WERE SUBMITTED, PLAN SHEET
 A1.1 WAS STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-03-09 Cont ID  
Sent By mwennerg Date 2009-03-09 Time 11:26 Rev Time 0.00
Received By mwennerg Date 2009-03-09 Time 11:26 Sent To  
Notes
2009-03-09 12:23:14MECHANICAL SHEETS ARE STILL SHOWING CO2 DETECTION
 DEVICES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-01-06 Cont ID  
Sent By mwennerg Date 2009-01-06 Time 14:29 Rev Time 0.00
Received By mwennerg Date 2009-01-06 Time 14:29 Sent To  
Notes
2009-01-06 14:44:46PLANS APPREAR TO BE FIRE CODE COMPLIANT. PLANS WILL BE
 STAMPED WHEN RETURNED WITH THESE AND OTHER REVIEW
 COMMENT CORRECTS/CLARRIFICATION
  
 1) PLEASE SHOW THE PROPOSED FIRE SPRINKLER LAYOUT WHICH
 MAY BE SHOWN ON THE REFLECTED CEILING PLAN. IN
 ADDITION, SEPARET SHOP DRAWINGS AND PERMITS WILL BE
 REQUIRED PRIOR TO EQUIPMENT INSTALLATION.
  
 2) PLEASE CLARIFY THAT CO2 SENSORS ARE FOR THE
 DETECTION OF CARBON DIOXIDE.
  
 3) PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING THAT IS SPECIFIC
 TO THIS PROJECT.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-08-20 Cont ID  
Sent By lmartine Date 2009-08-20 Time 17:26 Rev Time 0.00
Received By lmartine Date 2009-08-20 Time 17:26 Sent To  
Notes
2009-08-20 17:28:53GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-07-31 Cont ID  
Sent By lmartine Date 2009-07-31 Time 13:20 Rev Time 0.00
Received By lmartine Date 2009-07-31 Time 13:11 Sent To  
Notes
2009-07-31 13:16:52B-12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-31 Cont ID  
Sent By adarroug Date 2009-03-31 Time 13:57 Rev Time 0.00
Received By adarroug Date 2009-03-31 Time 13:57 Sent To  
Notes
2009-03-31 13:57:36TO "B10"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-18 Cont ID  
Sent By adarroug Date 2009-02-18 Time 12:57 Rev Time 0.00
Received By adarroug Date 2009-02-18 Time 12:57 Sent To  
Notes
2009-02-18 12:58:00TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-09 Cont ID  
Sent By rregueir Date 2009-01-09 Time 12:04 Rev Time 0.00
Received By rregueir Date 2008-12-15 Time 15:47 Sent To PC
Notes
2008-12-15 15:50:22TO "BOB"#1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-08-05 Cont ID  
Sent By rregueir Date 2009-08-05 Time 18:22 Rev Time 0.00
Received By rregueir Date 2009-08-05 Time 18:21 Sent To PC
Notes
2009-08-05 18:22:09REVISED M1 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-03-24 Cont ID  
Sent By rregueir Date 2009-03-24 Time 11:27 Rev Time 0.00
Received By rregueir Date 2009-03-24 Time 11:27 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-01-09 Cont ID  
Sent By rregueir Date 2009-01-09 Time 12:02 Rev Time 0.00
Received By rregueir Date 2009-01-09 Time 12:02 Sent To PC
Notes
2009-01-09 12:04:11REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE WOLF VENTLESS HOOD INSTALLED ABOVE THE COOKTOP
 SHALL BE TESTED IN ACCORDANCE WITH UL 197 FOR
 COMMERCIAL KITCHEN RECIRCULATING SYSTEMS PER FBCM
 507.1(2). PROVIDE SUPPORTING DOCUMENTATION.
  
 2. OTHER HEAT PRODUCING APPLIANCES IN THE KITCHEN (SUCH
 AS THE OVEN) SHALL BE PROVIDED WITH A TYPE II HOOD IN
 ACCORDANCE WITH FBCM 507.2.2.
  
 3. AHU HANGING DETAIL CALLS FOR AN AUXILIARY PAN DRAIN
 FROM AN AUXILIARY DRAIN PAN. THE AUXILIARY PAN DRAIN
 SHALL DISCHARGE TO A CONSPICUOUS POINT OF DISPOSAL TO
 ALERT OCCUPANTS IN THE EVENT OF A STOPPAGE OF THE
 PRIMARY DRAIN IN ACCORDANCE WITH FBCM 307.2.3(1).
 PLEASE SHOW THE LOCATION OF THE AUXILIARY DRAIN
 DISCHARGE TO DEMONSTRATE COMPLIANCE WITH THIS SECTION.
 NOTE: ANY OF THE METHODS OF AUXILIARY/SECONDARY DRAIN
 PROTECTION LISTED UNDER FBCM 307.2.3 MAY BE EMPLOYED
 AND SHOWN ON PLANS TO DEMONSTRATE COMPLIANCE.
  
 4. ALUMINUM ROOF STAND APPEARS TO BE OF THE
 PRE-ENGINEERED TYPE. PRE-ENGINEERED A/C STANDS ARE
 DEFINED AS STRUCTURAL COMPONENTS IN ACCORDANCE WITH FAC
 RULE 9B-72. PLEASE PROVIDE PRODUCT APPROVAL FOR THE
 STAND TO BE USED, REVIEWED AND APPROVED BY THE DESIGNER
 OF RECORD IN ACCORDANCE WITH FBCB 106.3.3.
  
 5. PLANS CALL FOR AN 18? ELEVATION FROM THE FOOT OF THE
 A/C STAND TO THE BOTTOM OF THE BEAM. THE ELEVATION OF
 THE STAND SHALL BE DETERMINED IN ACCORDANCE WITH FBCB
 TABLE 1509.7 BASED ON THE WIDTH OF THE ELEVATED
 APPLIANCE. THIS MEASUREMENT SHALL BE FROM ABOVE THE
 ROOF SURFACE. PROVIDE DIMENSIONS OF THE CONDENSERS TO
 CONFIRM REQUIRED HEIGHT OF STANDS AND THE SIZE OF
 CONDENSER ALLOWED ON THE STAND PER THE PRODUCT APPROVAL
 DOCUMENTATION.
  
 6. MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES IN ACCORDANCE WITH FBCM
 301.13. PROVIDE INFORMATION SHOWING OUTDOOR APPLIANCES,
 SUCH AS CONDENSING UNITS, ARE DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH THIS SECTION.
  
 7. DETAIL CALLS FOR RUSKIN FIRE/SMOKE DAMPER TO BE
 INSTALLED AT RATED WALL ASSEMBLIES. PLEASE SHOW HOW
 SMOKE DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH
 FBCM 607.3.2.1.
 ALSO, ELECTRICAL PLANS SHOW NO PROVISIONS FOR POWER TO
 THE SMOKE DAMPER ACTUATING MOTORS. PLEASE COORDINATE
 MECHANICAL AND ELECTRICAL PLANS IN ACCORDANCE WITH FBCB
 106.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-08-06 Cont ID  
Sent By kstevens Date 2009-08-06 Time 17:36 Rev Time 0.00
Received By kstevens Date 2009-08-06 Time 08:05 Sent To  
Notes
2009-08-06 17:37:21REVISION OK -- SHTS P1 & P2.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-04-01 Cont ID  
Sent By kstevens Date 2009-04-01 Time 13:53 Rev Time 0.00
Received By kstevens Date 2009-04-01 Time 13:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-02-27 Cont ID  
Sent By kstevens Date 2009-02-27 Time 17:40 Rev Time 0.00
Received By kstevens Date 2009-02-27 Time 17:40 Sent To  
Notes
2009-02-27 17:48:35DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. SHT P1 SHOWS THE DISH WASHER DRAINING THROUGH THE
 GREASE TRAP. PER ARTICLE III SECTION 90-124(7)(B)
 GREASE TRAPS ARE TO BE INSTALLED OUTSIDE THE FLLD
 PREPARATION AREA WITH THE DISH WASHER DISCHARGING VIA A
 SEPARATE LINE.
 ****RESPONSE NOTED, BUT THE DISHWASHER IS STILL
 DISCHARGING THRU THE GREAS TRAP. THE DISH WASHER SHALL
 DISCHARGE DOWNSTREAM OF THE GREASE TRAP.
  
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. SHT P2 WATER HEATER PIPING DETAIL SHOWS THE P&T
 DISCHARGE LINE TO THE EXTERIOR AND ALSO TO THE
 EMERGENCY WATER HEATER PAN. THE DETAIL ALSO SHOWS AN
 EXPANSION TANK AND A WATTS MODEL 530 VALVE FOR
 EXPANSION RELIEF. PLEASE CLARIFY. SECTIONS 106.1.1,
 504.6.1 & 607.3.1/607.3.2.
 ****RESPONSE NOTED, BUT THE P/T AND PAN DRAIN ARE NOW
 INDICATING AS BEING RUN TO THE MECHANICAL ROOM. PLEASE
 CLARIFY. PLEASE INDICATE THE "SAFE PLACE OF DISPOSAL"
 FOR THE P/T VALVE AS REQUIRED IN SECTION 504.6.1. ALSO
 THE PAN DRAIN SHALL TERMINATE OVER A SUITABLY LOCATED
 INDIRECT WAST RECEPTOR OR FLOOR DRAIN OR EXTEND TO THE
 EXTERIOR OF THE BUILDING. SECTION 504.7.2. PLEASE
 INDICATE THE TERMINATION POINT FOR THE PAN DRAIN. --
 DETAIL NOW SHOWS THE DRAIN LINE FROM THE WATTS MODEL
 530C THERMAL EXPANSION VALVE DRAINING INTO THE PAN. THE
 WATER HEATER SHALL BE RAISED IN THE PAN TO KEEP IT FROM
 SITTING IN WATER DISCHARGE FROM THE VALVE. SECTION
 303.2.
  
 12. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-05 Cont ID  
Sent By kstevens Date 2009-01-05 Time 11:55 Rev Time 0.00
Received By kstevens Date 2009-01-05 Time 11:55 Sent To  
Notes
2009-01-05 12:20:35DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
  
 1. SHT T CODE CRITERIA TO INCLUDE THE 2007 AMENDMENTS
 TO THE FBC-2004. SECTION 106.1.1.
  
 2. SHT A1.2 DETAIL G1(3)(4) SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.6 DISPENSERS
 ___FOR LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 3. SHT A1.2 DETAIL D1 SHOW THE BACKING REQUIRED FOR THE
 GRAB BARS AT THE W/C FOR ADAPTABILITY. SECTIONS
 11-4.1.3(11) & 11-4.1.6(1)(B).
  
 4. SHT A1.2 DETAIL 9(2) CABINET DOOR ARE NOT APPROVED
 IN THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 SECTION 11-4.22.2(1). PLEASE DELETE CABINET DOORS.
  
 5. SHT A2.1 SHOW COMPLIANCE FOR THE FOLLOWING:
 ___FOR SINK:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (SHOW ON FLOOR PLAN SHT
 A1.1).
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 6. SHT P1 SHOWS THE DISH WASHER DRAINING THROUGH THE
 GREASE TRAP. PER ARTICLE III SECTION 90-124(7)(B)
 GREASE TRAPS ARE TO BE INSTALLED OUTSIDE THE FLLD
 PREPARATION AREA WITH THE DISH WASHER DISCHARGING VIA A
 SEPARATE LINE.
  
 7. SHT P1 PER SECTION 1003.3.2 WHERE FOOD WASTE
 GRINDERS CONNECT TO GREASE TRAPS, A SOLIDS INTERCEPTOR
 SHALL SEPARATE THE DISCHARGE BEFORE CONNECTING TO THE
 GREASE TRAP. PLEASE INDICATE IF THERE WILL BE A FOOD
 WASTE GRINDER OR NOT ON PLANS.
  
 8. ALL GREASE INTERCEPTORS AND TRAPS SHALL BE SIZED BY
 THE UTILITY DEPARTMENT, ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT HOLLY MCGRATH BY PHONE AT (561)
 822-2200, OR BY FAX AT (561) 822-2279, OR BY E-MAIL AT
 [email protected]. A WRITTEN DETERMINATION IS REQUIRED
 FOR PERMIT APPROVAL. SECTION 90-124(7).
  
 9. SHT P1 FLOOR PLAN AND P2 SANITARY ISOMETRIC RISER
 DIAGRAM. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE
 RECEPTORS. A FLOOR SINK OR HUB DRAIN IS APPROVED.
 SECTIONS 802.3 & 802.3.2.
  
 10. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM. SHOW
 ALL PIPE SIZES, TRAPS & VENTS. SECTION 106.2.5.1.3.
  
 11. SHT P2 WATER HEATER PIPING DETAIL SHOWS THE P&T
 DISCHARGE LINE TO THE EXTERIOR AND ALSO TO THE
 EMERGENCY WATER HEATER PAN. THE DETAIL ALSO SHOWS AN
 EXPANSION TANK AND A WATTS MODEL 530 VALVE FOR
 EXPANSION RELIEF. PLEASE CLARIFY. SECTIONS 106.1.1,
 504.6.1 & 607.3.1/607.3.2.
  
 12. SHT P3 SAFE WASTE DETAIL SHOWS THE SAFE WASTE
 DOUBLE TRAPPED. THIS IS NOT APPROVED. SECTION 1002.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved