Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-06 Cont ID  
Sent By mjacobs Date 2009-04-06 Time 13:49 Rev Time 0.00
Received By mjacobs Date 2009-04-06 Time 13:49 Sent To PC
Notes
2009-04-06 13:49:22REVISION SHEET A-2

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-02-04 Cont ID  
Sent By mjacobs Date 2009-02-04 Time 11:03 Rev Time 0.00
Received By mjacobs Date 2009-02-04 Time 11:03 Sent To  
Notes
2009-02-04 11:03:06PROVISOR: 11-4.28.1 ALARM SYSTEMS SHALL COMPLY WITH
 SECTION 11-4.28.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-19 Cont ID  
Sent By mjacobs Date 2008-12-19 Time 14:32 Rev Time 0.00
Received By mjacobs Date 2008-12-19 Time 14:32 Sent To  
Notes
2008-12-19 14:32:03BUILDING PLAN REVIEW
 PERMIT: 08120283
 ADD: 550 SOUTH QUADRILLE BLVD. #100
 CONT: DANNER CONSTRUCTION COMPANY, INC.
 TEL: (561)986-2343
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12-19-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) THE PLANS FAIL TO INDICATE THE CONSTRUCTION TYPE OF
 THE BUILDING IN ACCORDANCE WITH CHAPTER 6; TABLE 601
 AND TABLE 503. PLEASE INDICATE THE NUMBER OF STORIES
 AND HEIGHT OF THE BUILDING.
  
 4) SHEET CS: THE DRAWINGS STATE LEVEL 3 ALTERATION.
 ALTERATION LEVEL 3 OCCURS WHEN THE WORK AREA EXCEEDS 50
 PERCENT OF THE AGGREGATE AREA OF THE BUILDING WITHIN A
 TWELVE MONTH PERIOD. DOES THE WORK MEET THE
 REQUIREMENTS OF FBC (EXISTING) 305.1?
  
 5) A SPRINKLER HEAD LAYOUT SHALL BE SUBMITTED WITH THE
 PLANS TO SHOW THE NEW LOCATION OF THE NEW AND OLD
 SPRINKLER HEADS IN RELATION TO THE NEW CONSTRUCTED
 WALLS.106.3.5.1.1(5) AND FS 553.79(2). THIS INFORMATION
 CAN BE INDICATED ON THE CEILING PLANS.
  
 6) SHEET A-2 MAKES REFERENCE TO DETAIL # ON SHEET A-2
 WHICH DOES NOT CORRESPOND WITH ANY OF THE DETAILS SHOWN
 ON THAT SAID SHEET. CLARIFY.
  
 7) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-04-03 Cont ID  
Sent By dpalmer Date 2009-04-03 Time 12:15 Rev Time 0.00
Received By dpalmer Date 2009-04-02 Time 21:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-23 Cont ID  
Sent By dpalmer Date 2009-02-23 Time 10:23 Rev Time 0.00
Received By dpalmer Date 2009-02-23 Time 10:23 Sent To  
Notes
2009-02-23 10:25:28REDLINED PLANS.
 THE DATE NOTED AS BEING SIGNED AND SEALED IS 1/16/09
 ALTHOUGH THE REVISIONS ARE 2/13/09.
 THE ACTUAL DATE CONFIRMED BY MR. ARNOLD CHANE WAS
 2/16/09 THIS IS NOTED ON ELECTRICLA PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-02-02 Cont ID  
Sent By dpalmer Date 2009-02-02 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2009-02-02 Time 12:08 Sent To  
Notes
2009-02-02 12:09:15** DENIED **
  
 ** PLEASE SEE SOME ITEMS FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING. A CALL WAS PLACED TO THE
 ENGINEER OF RECORD TO GO OVER SOME OF THESE ITEMS. THE
 ENGINEER WILL LOOK INTO THE PLANS.
  
  
 1) NOTE: PLEASE SEE 13-415.2, 13-415.2.B.2,
 13-415.2.ABC.1.1, .1.2 FOR REQUIRED LIGHTING
 PERFORMANCE CALCULATIONS.
 THE FOLLOWING ARE SOME ITEMS WHICH IS NOT CONSISTENT
 WITH NOTES ON PLANS AND WHAT NEEDS TO BE SHOWN. THIS
 ALSO AFFECT THE LIGHTING CONTROLS WHICH WILL BE NOTED
 BELOW IN NOTE #2.
  
 FOR EXAMPLE: THE TOTAL DESIGN WATTAGE LISTED IN NOTE #1
 IS 15,016. THIS MUST BE A MISPRINT. THE TOTAL LISTED
 ABOVE IS 1545.
  
 FOR EXAMPLE: THE NOTES MENTIONS THE ACCENT AND DISPLAY
 LIGHTING IS NOT INCLUDED PER 13-415.B.2(1). THIS IS NOT
 A SECTION IN THE FBC. IF THIS NOTE IS MEANT TO
 REFERENCE 13-415.2.ABC.1 FOR DISPLAY AND ACCENT
 LIGHTING WHICH IS NOTED AS EXEMPT IN THE ENERGY CODE.
 PLEASE SEE THE LAST SENTENCE IN THE FIRST LINE IS THIS
 EXEMPTION IS ONLY FOR GALLERIES, MUSEUMS AND MONUMENTS.
 AS THIS OCCUPANCY IS NOT EITHER OF THESE THIS EXEMPTION
 MAY NOT BE USED. PLEASE RE-CONFIGURE AND SHOW WITH
 LIGHTING FIGURED INTO THE OVER ALL BASED ON SQ FT OF
 THOSE SPACES. SEE 13-415.2.B.2 FOR THE ADDITIONAL
 ALLOWANCE
  
 FOR EXAMPLE: PLEASE SEE THE TABLE OF CALCULATIONS WHICH
 LIST A SPACE AS RETAIL. BASED ON CHAPTER 3 OF THE FBC
 THIS IS A BUSINESS OCCUPANCY WHICH WILL ALLOW 1.1 AND
 NOT 1.7. PLEASE RE-CONFIGURE.
  
 FOR EXAMPLE: THE PLANS SHOW TRACK LIGHTING AND FIXTURES
 HOWEVER THEY ARE NOT IDENTIFIED OR SPECIFIED. UPON
 CONVERSATION WITH ENGINEER IT WAS BROUGHT UP THAT A
 FIXTURE WAS NOT KNOWN AT THIS TIME. PLEASE COME UP WITH
 SOME SORT OF FIXTURE TO SHOW MINIMUM COMPLIANCE AT THIS
 TIME. THE FIXTURE TYPE MAY ALWAYS BE REVISED AT A LATER
 DATE. THIS WILL ALLOW PERMIT ISSUANCE AND THE PROJECT
 TO MOVE FORWARD.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.3 FOR THE REQUIRED
 CONTROLS WHEN USING DISPLAY OR ACCENT LIGHTING OR TASK
 LIGHTING. MOST OF THE TASK FIXTURES DO HAVE THE
 SEPARATE REQUIRED CONTROLS ALREADY SHOWN ON THE PLANS.
 ( THIS IS NOTED AS OCCUPANCY IN SOME AREAS IS STATE AS
 RETAIL.
  
 3) NOTE: A COMMENT NOT MADE ON PREVIOUS REVIEW. PLEASE
 BE SURE THE PLANS STATE THE MINIMUM CODE PER 2005
 NFPA-70 (NEC). NO EDITION OF THE NEC IS NOTED.
 THE PLANS ALSO STATE PALM BEACH COUNTY FOR AMENDED
 CODES.
  
 4) NOTE: A COMMENT NOT MADE ON THE PREVIOUS REVIEW.
 PLEASE BE SURE TO LIST THE HORN, STROBE LEVELS FOR ADA
 COMPLIANCE. 11-4.28.1, .2, .3(4).
 THIS IS BUILDING CODE REQUIREMENT WHICH DOES AFFECT THE
 ELECTRICAL PLANS. PLEASE ADJUST EVEN IF COMMENT IS NOT
 MADE OTHER TRADES.
  
 5) NOTE: THE LOAD CALCULATIONS HAVE BEEN REVISED. IT IS
 NOT CLEAR WHAT CONTINUOUS LOADS ARE BEING FIGURED.
 PLEASE INDICATE. LIGHTING AND STORAGE TYPE WATER HEATER
 IS CONSIDERED CONTINUOUS LOADS.
 215.3,230.42,220,422.13
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-24 Cont ID  
Sent By dpalmer Date 2008-12-24 Time 13:30 Rev Time 0.00
Received By dpalmer Date 2008-12-24 Time 13:30 Sent To  
Notes
2008-12-24 13:30:17** DENIED REVIEW**
  
  
 1) NOTE: LIGHTING CONTROLS FOR NEW INSTALLED SHALL
 COMPLY WITH FBC 13-415.1.ABC.1.1, .1.2 AND .1.3.
 SOME SHOWN IS OK FOR COMPLIANCE HOWEVER SOME OTHER NEW
 DEVICES SHOWN ARE NOT.
 PLEASE
  
 2) NOTE: THE LIGHTING PERFORMANCE CALCULATIONS AS
 SUBMITTED ARE NOT CODE COMPLIANT AND/OR CAN NOT BE
 DETERMINED AS COMPLAINT UNTIL MORE INFORMATION IS
 PROVIDED. THE PROPOSED NEW ADDITIONAL LIGHTING AS
 PROPOSED IS NOT PERMITTED AT THIS TIME. INFORMATION IS
 NEEDED ON ALL EXISTING LIGHTING BEFORE AN ALLOWANCE OF
 PROPOSED NEW LIGHTING MAY BE INSTALLED
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1 AND .1.2.
 PLANS AS SUBMITTED INDICATE A BUILDING AREA METHOD FOR
 ALLOWANCE AND DESIGN. YOU MUST SHOW ALL EXISTING
 LIGHTING INFORMATION TO DETERMINE IF THE ADDITION OF
 NEW LIGHTING IS PERMITTED.
 ** PLEASE CALL TO GO OVER IF THERE ARE ANY QUESTIONS.
  
 3) NOTE: PLEASE COMPLETE PANELS/CIRCUITS ETC ON PLANS
 AND COORDINATE. AN EXAMPLE OF THIS IS THE SIGN CIRCUIT
 WHICH IS NOTED ON THE LIGHTING PLANS AS EXISTING
 CIRCUIT L-36 HOWEVER CIRCUIT 36 ON THE L PANEL IS
 BLANK. NO CIRCUIT, NO LOAD, NO OVER CURRENT PROTECTION
 ETC.
 PLEASE SEE 600.5 FOR MINIMUM LOADS AND CIRCUIT SIZE FOR
 SIGNS.
 PLEASE SEE 408.4 FOR PANEL SCHEDULE REQUIRED TO BE
 ACCURATE.
 PLEASE SEE FBC 106.1.1 FOR CLARITY OF PLANS AND
 COORDINATION.
 ** THIS IS ONE EXAMPLE GIVEN ONLY.
  
  
 4) NOTE: PLEASE SEE NEC 517 FOR REQUIREMENTS OF WIRING
 OF RECEPTACLE CIRCUITS FOR REDUNDANT GROUNDING. PLEASE
 SEE 517.10 (PART II).
 PLEASE ALSO SEE THE OCCUPANCY SHALL COMPLY WITH ALL OF
 NEC 517 AS THE LOCATION ON TITLE BLOCKS CLEARLY STATE
 ** PLASTIC SURGERY**.
  
  
  
 ** AS THERE IS SOME INFORMATION NOT YET SUBMITTED OR
 SHOWN, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NTO BE MADE AT THIS TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-04-03 Cont ID  
Sent By mwennerg Date 2009-04-03 Time 15:32 Rev Time 0.00
Received By mwennerg Date 2009-04-03 Time 15:31 Sent To  
Notes
2009-04-03 15:32:23REVISION DATED 3/12/09

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-02-05 Cont ID  
Sent By mwennerg Date 2009-02-05 Time 11:03 Rev Time 0.00
Received By mwennerg Date 2009-02-05 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-12-26 Cont ID  
Sent By mwennerg Date 2008-12-26 Time 10:45 Rev Time 0.00
Received By mwennerg Date 2008-12-26 Time 10:45 Sent To  
Notes
2008-12-26 10:54:54***PROVISO***
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH
 CORRECTIONS/CLARRIFICATION FOR THESE AND OTHER REVIEW
 COMMENTS.
  
 1) PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING THAT IS SPECIFIC
 TO THIS PROJECT. SHEET A3
  
 2) PROVIDE FIRE SPRINKLER HEAD LAYOUT THAT MAY BE SHOWN
 ON THE REFLECTED CEILING PLAN. IN ADDITION, SEPARATE
 SHOP DRAWINGS AND PERMIT ALONG WITH MANUFACTURER
 SPECIFICATIONS ARE REQUIRED PRIOR TO EQUIPMENT
 INSTALLATION.
  
 3) SHEET E1 INDICATES (1) NEW HORN STROBE INSIDE
 PATIENT BATHROOM 115 AND EXISTING EQUIPMENT NEXT TO THE
 RECEPTION EXIT DOOR. ARE THERE ANY OTHER DEVICES
 PROPOSED FOR COMMON AREAS OR HALLWAYS?
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-13 Cont ID  
Sent By adarroug Date 2009-03-13 Time 15:42 Rev Time 0.00
Received By adarroug Date 2009-03-13 Time 15:42 Sent To  
Notes
2009-03-13 15:43:13TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-02-18 Cont ID  
Sent By adarroug Date 2009-02-18 Time 13:07 Rev Time 0.00
Received By adarroug Date 2009-02-18 Time 13:07 Sent To E
Notes
2009-02-18 13:07:25TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-26 Cont ID  
Sent By adarroug Date 2009-01-26 Time 16:58 Rev Time 0.00
Received By adarroug Date 2009-01-26 Time 16:58 Sent To  
Notes
2009-01-26 16:58:37TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 15:18 Rev Time 0.00
Received By rregueir Date 2008-12-15 Time 11:43 Sent To PC
Notes
2008-12-15 11:47:38TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-04-02 Cont ID  
Sent By rregueir Date 2009-04-02 Time 10:22 Rev Time 0.00
Received By rregueir Date 2009-04-02 Time 10:09 Sent To  
Notes
2009-04-02 10:22:40REVISED M-1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-02-09 Cont ID  
Sent By hmoser Date 2009-02-09 Time 14:22 Rev Time 0.00
Received By hmoser Date 2009-02-09 Time 14:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 15:18 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 15:06 Sent To PC
Notes
2009-01-10 15:18:11REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. FLEX HANGER DETAIL INDICATES 1" HANGER STRAP USED
 FOR SUPPORT OF FLEX DUCT. IN NO CASE SHALL THE MATERIAL
 SUPPORTING FLEXIBLE DUCT THAT IS IN DIRECT CONTACT WITH
 IT BE LESS THAN 1 1/2 INCHES WIDE IN ACCORDANCE WITH
 FBCM 603.5.6.6(6).
  
 2. PLEASE PROVIDE DETAILED OUTSIDE AIR CALCULATIONS
 WITH OCCUPANCY CLASSIFICATIONS INDICATED AND BROKEN
 DOWN BY SPACES SERVED. ALSO, PLEASE INDICATE THE
 VENTILATION BASIS FOR DESIGN. INDICATE IETHER FBCM
 403.3 OR AHSRAE 62.1-2004.
  
 3. NOTE ON PAGE A2 REFLECTIVE CEILING PLAN INDICATES
 EXPOSED CEILING AREAS RE TO BE PAINTED. ANY DUCT
 INSULATION IN THIS AREA, EITHER RIGID OR FLEX, SHALL
 NOT BE PAINTED AS THIS WILL NEGATE THE REQUIRED UL 181
 LISTING OF THESE PRODUCTS RELATED TO FLAME SPREAD AND
 SMOKE DEVELOPMENT RATING. THIS APPLIES TO NEW AND
 EXISTING DUCTS. FBCM 603.4.
 NOTE: ANY EXPOSED METALLIC DUCTS IN THIS AREA IS NOT
 REQUIRED TO BE INSULATED AND MAY BE PAINTED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-02-05 Cont ID  
Sent By kstevens Date 2009-02-05 Time 08:39 Rev Time 0.00
Received By kstevens Date 2009-02-05 Time 08:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-24 Cont ID  
Sent By kstevens Date 2008-12-24 Time 15:56 Rev Time 0.00
Received By kstevens Date 2008-12-24 Time 15:56 Sent To  
Notes
2008-12-24 16:00:00DENIED
 REFERENCE:
 FBC-2004 BUILDING
  
 1. SHT A-3 FINISH SCHEDULE INDICATES PAINTED WALLS FOR
 THE TOILE ROOMS. PER SECTION 1210.2 WALLS WITHIN 2 FEET
 OF WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE. PAINTED WALLS DOES NOT COMPLY
 WITH THE "HARD" PORTION OF THIS REQUIREMENT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-12-24 Cont ID  
Sent By aaponte Date 2008-12-24 Time 10:11 Rev Time 0.00
Received By aaponte Date 2008-12-24 Time 10:11 Sent To  
Notes
***NONE***