| Plan Review Stops For Permit 08120274 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-07-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-07-24 |
Time |
07:59 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2009-07-24 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2009-07-24 07:53:32 | EXPEDITED PLAN REVIEW | | | 7:30-8:00 AM | | | SHEET A3.1 REVISION# 3 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-04-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-02 |
Time |
12:17 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2009-04-21 |
Time |
09:19 |
Sent To |
PC |
|
| Notes |
| 2009-04-21 09:21:40 | TO PROCESS PLANS AND BUILDING PROVISO: | | | BUILDING PLAN REVIEW | | | PERMIT: 08120274 | | | ADD: 303 BANYAN / 4TH FLOOR | | | CONT: LCI CONSTRUCTION | | | TEL: (561)578-5930 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | BUILDING PROVISO: | | | | | | SHEET A3.1 HAS VARIOUS DETAILS INDICATING SOFFITS HUNG | | | FROM STRUCTURE ABOVE, PLEASE PROVIDE WHAT TYPE OF | | | ATTACHMENT METHOD WILL BE USED. 2506.2 STANDARDS, STEEL | | | STUDS NON-LOAD BEARINGASTM C-645-00, TABLE 2508.1, | | | GYPSUM BOARD GA 216 & 106.1.2 ADDITIONAL INFORMATION | | | REQUIRED. THIS INFORMATION WILL BE REQUIRED BY FRAMING | | | INSPECTION. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-04-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-04-06 |
Time |
07:39 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2009-04-06 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2009-04-06 07:46:38 | BUILDING PLAN REVIEW | | | PERMIT: 08120274 | | | ADD: 303 BANYAN / 4TH FLOOR | | | CONT: LCI CONSTRUCTION | | | TEL: (561)578-5930 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | BUILDING PROVISO: | | | | | | SHEET A3.1 HAS VARIOUS DETAILS INDICATING SOFFITS HUNG | | | FROM STRUCTURE ABOVE, PLEASE PROVIDE WHAT TYPE OF | | | ATTACHMENT METHOD WILL BE USED. 2506.2 STANDARDS, STEEL | | | STUDS NON-LOAD BEARINGASTM C-645-00, TABLE 2508.1, | | | GYPSUM BOARD GA 216 & 106.1.2 ADDITIONAL INFORMATION | | | REQUIRED. THIS INFORMATION WILL BE REQUIRED BY FRAMING | | | INSPECTION. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-12-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-24 |
Time |
15:06 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2008-12-24 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2008-12-24 15:45:56 | BUILDING PLAN REVIEW | | | PERMIT: 08120274 | | | ADD: 303 BANYAN / 4TH FLOOR | | | CONT: LCI CONSTRUCTION | | | TEL: (561)578-5930 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B)INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, | | | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: | | | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS AND 2004 EXISTING | | | BUILDING CODE WITH 2007 SUPPLEMENTS. | | | | | | 2) ENERGY CODE , THE PROJECT SUMMARY INDICATES WHOLE | | | METHOD "A" WAS SUBMITTED WHOLE BUILDING PERFORMANCE | | | METHOD, THIS IS A 4TH FLOOR TENANT BUILD-OUT NOT A | | | WHOLE BUILDING. PLEASE REVIEW 13-101.1.3. RENOVATIONS | | | AND 13-202 DEFINITION FOR RENOVATIONS. BY DEFINTION | | | THIS IS NOT A RENOVATION.SEE 13-400.0.C.4. EXISTING | | | BUILDINGS NOT MEETING THE DEFINTION OFA RENOVATION IN | | | WHICH NEW HEATING,COOLING,WATER HEATING, ELECTRICAL OR | | | LIGHTING SYSTEMS ARE INSTALLED SHALL MEET THE BASIC | | | PRESCRIPTIVE MINIMUM EFFICIENCIES LISTED IN THE CODE | | | FOR THE SYSTEMS BEING CHANGED. | | | | | | 3) SHEET A1.1: | | | | | | 3A) DOOR# 45& 6, BOTH ARE INDICATED AS A 2'-6" DOOR ON | | | THE DOOR SCHEDULE, 11-4.13.5 MINIMUM CLEAR OPENING IS | | | 32" , OPENINGS MORE THAN 24 INCHES IN DEPTH SHALL | | | COMPLY WITH SECTIONS 11-4.2.1 AND 11-4.3.3. | | | 3B) DOOR# 42 REQUIRES 1'-6" CLEAR ON THE PULL SIDE, | | | PLEASE REVIEW 11-4.13.6. MANEUVERING CLEARENCES AT | | | DOORS. | | | | | | 3C) ROOM # 127 THE EMPLOYEE LOUNGE INDICATES A SIDE | | | APPROACH, AND SHEET A4.1 DETAIL# 4 ALSO INDICATE DOORS | | | ON THE FRONT MAKING IT IMPOSSIBLE FOR A FRONT APPROACH. | | | 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE | | | COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH | | | FLOOR. | | | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" | | | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS | | | 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW | | | FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN | | | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 | | | INCHES (485 MM) UNDERNEATH THE SINK. | | | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT | | | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) | | | COMPLYING WITH SECTION | | | | | | 4) SHEET A3.1 HAS VARIOUS DETAILS INDICATING SOFFITS | | | HUNG FROM STRUCTURE ABOVE, PLEASE PROVIDE WHAT TYPE OF | | | ATTACHMENT METHOD WILL BE USED. 106.1.2 ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | 5) SHEET A3.1 DETAIL# 14 INDICATES A FIRESTOPPING AT | | | THE 4TH FLOOR MEZZANINE LEVEL, ITHERE ARE NO PLANS OR | | | DETAILS FOR WORK TO BE COMPLETED ON THAT LEVEL, OR PART | | | OF THIS PERMIT? | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2009-08-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-08-05 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-08-05 |
Time |
16:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
F |
Date |
2009-07-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-24 |
Time |
20:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-24 |
Time |
20:12 |
Sent To |
|
|
| Notes |
| 2009-07-24 20:12:21 | | | | ** DENIED REVISIONS ** | | | | | | 1) NOTE: PLEASE SEE THE SUBMITTED SKE ELECTRICAL DETAIL | | | SHEETS DO NOT CONTAIN THE RAISED SEAL AS REQUIRED PER | | | FAC 61G15-23.002, FS 471.025. IN FACT ONE OF THE THREE | | | SUBMITTED IS A PHOTO-COPY. | | | PLEASE SUBMIT A MINIMUM OF TWO ORIGINAL SIGNED, DATED | | | AND SEALED SHEETS. | | | | | | 2) NOTE: IT WAS NOTED ON PREVIOUS REVIEWS AS A | | | *HEADS-UP* ON INFORMATION TO SEE THE NEW FLORIDA | | | ASME-17 FOR MINIMUM ELEVATOR CODE REQUIREMENTS. | | | THIS OFFICE DOES NOT REVIEW FOR THESE ITEMS FOR MINIMUM | | | CODE COMPLIANCE HOWEVER BASED ON THE CODE REQUIREMENTS | | | KNOWN TO THIS REVIEWER LIGHTING IN AREAS OF THE | | | ELEVATOR LOBBY AS SHOWN WOULD NOT MEET MINIMUM. AN | | | INSPECTION BY THE STATE ELEVATOR INSPECTOR WOULD NOT BE | | | THE TIME TO FIND OUT ITEMS WHICH WOULD THEN NEED TO BE | | | ADDED WHICH WOULD DELAY A TCO OR CO. | | | ** SEE LIGHTING LEVELS FOR SILLS AND AT LANDINGS. | | | | | | ** THIS WILL AFFECT LPC. 13-415.2.ABC.1.1,.1.2, | | | 13-415.2. | | | | | | ** THE LIGHTING SHOWN ON THE REFLECTED CEILING PLAN OF | | | THE ARCHITECTURAL PLANS DOES NOT COORDINATE WITH THE | | | ELECTRICAL PLANS FOR THE ELEVATOR LOBBY. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2009-07-10 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-10 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-10 |
Time |
11:49 |
Sent To |
PC |
|
| Notes |
| 2009-07-10 11:53:30 | PAGE SKE-1 DENIED PER DOUG WISE. SKETCH CALLS FOR | | | ADDITION OF J BOXES AND SMOKE DETECTOR TO OPERATE AIR | | | CURTAINS AT ELEVATOR DOORS. LIFE SAFETY PLAN PAGE A4.1 | | | CALLS FOR SMOKE GUARD ROLL-DOWN DOORS AT THESE | | | LOCATIONS, NOT AIR CURTAINS. PLEASE CORRECT AND | | | COORDINATE WITH LIFE SAFETY PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
N |
Date |
2009-06-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-06-29 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-06-29 |
Time |
13:52 |
Sent To |
M |
|
| Notes |
| 2009-06-29 13:52:23 | ** NO REVIEW ** | | | | | | ** SUBMITTED REVISIONS/ SKE FOR ADDITION OF SD AND J | | | BOX OK WITH ELECTRICAL HOWEVER NEEDS REVIEW FROM | | | MECHANICAL AND FIRE BEFORE STAMPING SHEETS. | | | | | | THERE IS QUESTIONS ON INSTALLATION OF AIR CURTAINS | | | OUTSIDE ELEVATOR IN LOBBYS. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2009-06-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-06-15 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-06-15 |
Time |
11:36 |
Sent To |
PC |
|
| Notes |
| 2009-06-15 11:37:35 | REV E1.2 FOR FLOOR BOXES AND TV OUTLET. | | | REDLINED PLANS, ALL LOW VOLTAGE TO BE UNDER SEPARATE | | | PERMIT(S). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-05-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-05-26 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-05-26 |
Time |
16:31 |
Sent To |
PC |
|
| Notes |
| 2009-05-26 16:31:54 | REVISIONS FOR RECEPTACLES ONLY. | | | REDLINED, ALL LV SYSTEMS SHALL BE UNDER SEPARATE | | | PERMITS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-04-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-16 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-16 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2009-04-16 17:43:15 | REDLINED PLANS | | | VIF 210.63, 210.8B FOR ROOF TOP GFI REQUIRED FOR CU. | | | NEW OR EXISTING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-04-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-02 |
Time |
19:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-02 |
Time |
19:08 |
Sent To |
|
|
| Notes |
| 2009-04-02 19:09:02 | 1) NOTE: NO MINIMUM CODES STATED ON ELECTRICAL PLANS | | | FOR WHICH PROJECT IS UNDER. THE A SHEETS DO NOT CONTAIN | | | THE CURRENT MINIMUM REQUIRED CODES AS NEEDED BELOW. | | | PLEASE SEE THAT THE FOLLOWING ARE ON PLANS. | | | | | | 2004 FBC W/2007 REVISIONS. | | | 2003 NFPA-101 | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | | | | 2) NOTE: PLEASE SEE NEC 220.12,220.14, 220.42, 220.44 | | | ETC LOAD CALCULATIONS FOR PLANS NEED TO MEET THE NEC. | | | THE LOAD CALCULATIONS STATE THE MAXIMUM WATTAGE | | | ALLOWANCE FOR LIGHTING PER THE FBC. THE SIZING OF | | | LIGHTING PANELS FOR FEEDERS, BRANCH CIRCUITS AND | | | SERVICE LOAD CALCULATIONS ARE BASE DON THE NEC NOT THE | | | FLORIDA BUILDING CODE. THE MINIMUM LIGHTING WATTS PER | | | SQUARE FOOT WHEN SIZING THE ABOVE MUST BE PER NEC. | | | PLEASE REVISE ALL. | | | THIS MAY AFFECT THE SIZE OF THE PANEL. | | | | | | 3) NOTE: AS REQUESTED ON THE PREVIOUS REVIEW THE | | | MINIMUM LEVELS, HEIGHTS ETC FOR HORNS, HORN STROBE | | | DEVICES SHALL MEET THE FBC CHAPTER 11. 11-4.28.1, .2 | | | AND .3. | | | NO DEVICE LEVELS, HEIGHTS ETC WERE SHOWN ON ANY OF THE | | | THREE SHEETS. | | | | | | 4) NOTE: PLEASE SEE THE SUBMITTED FORM B FOR CHAPTER 13 | | | COMPLIANCE IS FROM THE NEW 2007 FBC. MIXING OF | | | CALCULATIONS FROM DIFFERENT CODES IS NOT PERMITTED. | | | PLANS SHOW COMPLIANCE WITH THE SPACE BY SPACE METHOD B. | | | THIS IS ALL THAT IS NEEDED FOR THIS REVIEWER. PLEASE | | | SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY BE NEEDED. | | | | | | 5) NOTE: THE PLANS INDICATE AN IT ROOM WITH A | | | DISCONNECT SWITCH FOR AHU, HOWEVER COMPLIANCE WITH NEC | | | 645, 6.4510 ETC IS NOT MET. THE ROOM MAY NOT BE CALLED | | | AND IT ROOM UNLESS MEETING ALL OF THE REQUIREMENTS IN | | | NEC 645.4. (1-5) | | | WHEN MEETING ALL OF THESE ITEMS AS LISTED THEN THE LESS | | | RESTRICTIVE WIRING METHODS PERMITTED IN 645 IS | | | PERMITTED. WHEN NOT MEETING THE ABOVE SECTIONS ALL 1-5, | | | THEN ALL WIRING METHODS SHALL BE PER CHAPTERS 1-4 OF | | | THE NEC. PLEASE KEEP IN MIND THAT COMPANY IT OR LOW | | | VOLTAGE PERSONNEL MAY WANT TO USE WIRING METHODS IN | | | 645, IF SO, THEN THE ROOM SHALL MEET ALL ITEMS IN 645.4 | | | 1-5. | | | IF THIS ROOM IS NOT AN IT ROOM, REVISE DESIGNATION AND | | | PLEASE PLACE NOTE ON PLANS WHICH STATES * NO WIRING | | | METHODS PER NEC 645 PERMITTED* OR WORDS TO THAT AFFECT. | | | CALL FOR QUESTIONS. | | | | | | 6) NOTE: THE LIFE SAFETY PLANS DO NOT CORRELATE WITH | | | THE ELECTRICAL PLANS FOR EMERGENCY LIGHTING. | | | THE LIFE SAFETY SHEETS ALSO STATE TO SEE ELECTRICAL | | | PLANS FOR EMERGENCY LIGHTING ABOVE SOFFIT HOWEVER THE | | | ELECTRICAL PLANS DO NOT INDICATE ANY EMERGENCY LIGHTING | | | ABOVE SOFFIT. | | | NFPA-101 7.8, 7.9 | | | FBC 1006.1.2 | | | | | | 7) NOTE: PLEASE KEEP IN MIND ALL OF THE NEW | | | REQUIREMENTS OF ASME-17 FOR FLORIDA ELEVATOR CODE | | | REQUIREMENTS STILL MUST BE MET. THIS IS ONLY NOTED FOR | | | INFORMATIONAL PURPOSE. THIS IS NOT A REVIEW COMMENT FOR | | | THIS TRADE. THERE IS ITEMS PER STATE ELEVATOR CODE | | | WHICH WOULD NOT MEET CURRENT ELEVATOR CODES. | | | SEE REFERENCE FROM FBC CHAPTER 30, NEC FPN TO ASME. | | | | | | 8) NOTE: PANEL SCHEDULE FOR CIRCUITS DOES NOT MEET | | | 408.4. STATING RECEPTACLES WITHOUT SPECIFIC ROOM AND | | | AREAS IS NOT PERMITTED. PLEASE SEE REVISED 2005 NEC AND | | | COMMENTARY IN HANDBOOK. | | | PLEASE REVISE. | | | | | | ** KEEP IN MIND FS 553.80(2)(B) WITH RESPECT TO REPEAT | | | COMMENTS FOR MINIMUM CODE COMPLIANCE. | | | | | | | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-12-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-30 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-30 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2008-12-30 09:12:38 | ** DENIED REVIEW ** | | | | | | | | | | | | | | | 1) NOTE: PLEASE SEE FBC | | | 13-101.1,13-101.1.3,13-400.0.C.4 ETC | | | THE SUBMITTED PROPOSED METHOD OF CALCULATIONS WAS FOR | | | *WHOLE BUILDING COMPLIANCE* ON METHOD *A*FLA-COM. | | | PLEASE EXPLAIN WHERE IN THE CODE DOES IT PERMIT METHOD | | | *A* FOR WHOLE BUILDING COMPLIANCE TO BE USED FOR THE | | | BUILD OUT OF A SHELL SPACE. | | | | | | PLANS CONTAIN SPACE BY SPACE FROM TABLE *B*. | | | PLEASE SEE 13-415.2.ABC.1. THE CODE DOES NOT PERMIT THE | | | USE OF MULTIPLE METHODS. | | | IN EITHER CASE THE SUBMITTED INPUT DATA REPORT DOES NOT | | | MATCH THE SUBMITTED PLANS. FOR EXAMPLE: PLEASE SEE ZONE | | | #1 WHICH ONLY LIST A TOTAL OF FOUR FIXTURES. HOW IS | | | THIS POSSIBLE WHEN THE LOBBY ON THE PLANS CLEARLY | | | INDICATES SEVERAL MORE FIXTURES? IN THE LOBBY ALONE | | | THERE A TOTAL OF 8 *M* FIXTURES ALONE. | | | | | | ** THIS IS ONE EXAMPLE: | | | PLEASE SEE THE TOTAL AMOUNT OF DESIGN WATTAGE SHOWN ON | | | SHEET E1.1 IS LESS THAN THE ACTUAL TOTAL WATTAGE OF | | | FIXTURES SHOWN ON PLANS. THE TOTAL ON *A* FIXTURES IS | | | ABOVE 8300. PLEASE BE SURE TO GO OVER ALL FIXTURES, THE | | | WATTAGE OF EACH AND THE NUMBER OF FIXTURES. | | | | | | 2) NOTE: PLEASE PROVIDE INFORMATION ON THE MULTI-GANG | | | BATHROOM OCCUPANCY SENSORS. DO THESE CONTAIN DUAL | | | TECHNOLOGIES? | | | NFPA-101 7.8. | | | | | | 3) NOTE: PLEASE SEE THE LOAD ON PANEL LA EXCEEDS THE | | | BREAKER RATING IN PANEL *L* WHICH FEEDS THIS PANEL. THE | | | LOAD SHOWN IS 33AMPS YET THERE IS ONLY A 25AMP BREAKER | | | FEEDING THIS PANEL. | | | 240,310,215 ETC | | | FBC 106.1.1 | | | | | | 4) NOTE: THE WATER HEATER IS SHOWN BEING FED FROM A TWO | | | POLE RECEPTACLE WHICH IS NOT PERMITTED. PLEASE SHOW THE | | | REQUIRED DISCONNECT. 422.30,422.31 | | | | | | 5) NOTE: PLEASE SHOW ALL HORN, HORN/STROBE LOCATIONS, | | | HEIGHTS AND LEVELS OF DEVICES TO MEET ADA COMPLIANCE. | | | PLEASE SEE FBC 11-4.28.1,.2 AND .3. | | | | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2009-01-16 |
|
|
Cont ID |
|
| Sent By |
efabian |
Date |
2009-01-16 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
efabian |
Date |
2009-01-16 |
Time |
13:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2009-08-07 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-08-07 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-08-07 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2009-08-07 11:41:58 | *****REVISIONS, DATED 7/20/09, APPROVED***** | | | | | | | | | REVISED PLAN SHEETS A3.1, E1.1, AND PAGE SKE-1R WERE | | | STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-07-02 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-02 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-07-02 |
Time |
11:52 |
Sent To |
B |
|
| Notes |
| 2009-07-02 12:17:03 | *****REVISION APPROVED***** | | | | | | PLAN REVISION (IN PDF FORM) WITH SUBMITTAL REVIEWED AND | | | APPROVED; HOWEVER, FIRE-STAMPING NOT NEEDED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-04-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-04-20 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-20 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2009-04-20 11:36:22 | *****APPROVED***** | | | | | | THE COMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN REVIEW | | | HAVE BEEN ADDRESSED; PLAN SHEETS A2.1, A4.1, E1.1, AND | | | E1.2 WERE STAMPED, INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2009-04-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-04-06 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-06 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2009-04-06 16:25:27 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW WERE NOT AND STILL NEED TO BE ADDRESED: | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH | | | ACCESS TO AND/OR EGRESS FROM THE OTHER FLOORS OF THE | | | BUILDING. | | | | | | 3. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. CHAPTER 38 (NEW BUSINESS OCCUPANCY) OF THIS | | | CODE IS APPLICABLE SINCE THE SCOPE WORK IS FOR | | | ALTERATIONS, MODERNIZATIONS, OR RENOVATIONS OF AN | | | EXISTING BUSINESS OCCUPANCY. | | | | | | 4. PLEASE INDICATE IF THIS FLOOR/BUILDING IS FIRE | | | SPRINKLERED. IF SO, PROVIDE A FIRE SPRINKLER LAYOUT FOR | | | THE FOURTH FLOOR. | | | | | | 5. SPECIFY THE WALL AND CEILING FINISH MATERIALS IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 6. FIRE DOORS SHALL COMPLY WITH NFPA 80. | | | | | | 7. CLARIFYVERIFY VERBAGE ON DRAWING A2.1 DOOR HARDWARE | | | NOTE #3, UNDER THE DOOR SCHEDULE. IS THIS WORD "EXIST" | | | OR "EXITS" ? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-01-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-01-28 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-01-28 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2009-01-28 15:24:41 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH | | | ACCESS TO AND/OR EGRESS FROM THE OTHER FLOORS OF THE | | | BUILDING. | | | | | | 3. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. CHAPTER 38 (NEW BUSINESS OCCUPANCY) OF THIS | | | CODE IS APPLICABLE SINCE THE SCOPE WORK IS FOR | | | ALTERATIONS, MODERNIZATIONS, OR RENOVATIONS OF AN | | | EXISTING BUSINESS OCCUPANCY. | | | | | | 4. PLEASE INDICATE IF THIS FLOOR/BUILDING IS FIRE | | | SPRINKLERED. IF SO, PROVIDE A FIRE SPRINKLER LAYOUT FOR | | | THE FOURTH FLOOR. | | | | | | 5. SPECIFY THE WALL AND CEILING FINISH MATERIALS IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 6. FIRE DOORS SHALL COMPLY WITH NFPA 80. | | | | | | 7. CLARIFYVERIFY VERBAGE ON DRAWING A2.1 DOOR HARDWARE | | | NOTE #3, UNDER THE DOOR SCHEDULE. IS THIS WORD "EXIST" | | | OR "EXITS" ? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-07-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-07-21 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-07-21 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2009-07-21 13:56:51 | *EXPEDITED* B-10 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-06-24 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-06-24 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2009-06-24 14:49:43 | REVISION TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2009-06-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-06-04 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2009-06-04 14:06:30 | REVISION TO DEWEY PALMER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-04-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-04-02 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-04-02 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2009-04-02 15:06:01 | TO "C10" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-29 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-15 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2008-12-15 09:05:47 | TO "COMM" BD#16 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2009-08-01 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-08-01 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-08-01 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2009-08-01 17:43:00 | REVISED M1.1 DELTA 6 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2009-07-10 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-10 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-10 |
Time |
14:25 |
Sent To |
PC |
|
| Notes |
| 2009-07-10 14:25:57 | REVISED M1.1 DELTA 5 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-07-10 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-10 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-10 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2009-07-10 11:48:15 | SKETCH SKM-1 AND SKM-2 OK PER DOUG WISE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-04-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2009-04-02 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2009-04-02 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2009-04-02 16:13:24 | PASS PROVISO | | | PLEASE PROVIDE A SEALD LETTER FROM ARNOLD CHANE ON SIZE | | | OF HANGER RODS FOR THE AIR-HANDLERS ,AT TIME OF 1ST | | | INSPECTION . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-01-15 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2009-01-15 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2009-01-15 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2009-01-15 14:07:22 | 01/15/2009 | | | PLEASE REFER TO SECTION 607.5.1 2004 FBC (M) FIRE WALLS | | | FOR ELECTRICAL ROOM 125 . | | | PLEASE REFER TO SECTION 603.5.5 PENETRATIONS PROHIBITED | | | 2004 FBC (M) | | | PLEASE PROVIDE THE SIZE OF HANGER ROD FOR HORIZONTAL | | | AHU DETAIL PAGE M2-2 ON MECHANICAL PLANS . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-04-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-17 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-17 |
Time |
17:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-04-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-03 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-03 |
Time |
17:32 |
Sent To |
|
|
| Notes |
| 2009-04-03 17:32:51 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. SHT A1.1 SHOW ACCESSIBILITY COMPLIANCE WITH THE | | | FOLLOWING: | | | | | | ___W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | ___URINAL: | | | A. 11-4.18.2 HEIGHT | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | B. 11-4.18.3 CLEAR FLOOR SPACE | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | C. 11-4.18.4 FLUSH CONTROLS | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | ___TOILET ROOMS: | | | A. 11-4.22.3 THE UNOBSTRUCTED TURNING AREAS ARE NOT | | | SHOWN IN THE TOILET ROOMS OF TOILET ROOMS 115 & 116. | | | THE TURNING AREA SHALL BE SHOWN IN THE TOILET ROOM, NOT | | | THE ACCESSIBLE STALL. | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | ___SINK: | | | A. 11-4.24.2 HEIGHT | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | B. 11-4.24.3 KNEE CLEARANCE | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | C. 11-4.24.5 CLEAR FLOOR SPACE - PARALLEL APPROACH | | | SHOWN BUT FORWARD APPROACH REQUIRED. SUBMIT AN | | | ELEVATION SHOWING THE REQUIRED OPENING. CABINET DOORS | | | ARE NOT APPROVED IN THE CLEAR FLOOR SPACE. | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | 2. SHT M1.2 PER TABLE 403.1 TWO DRINKING FOUNTAINS ARE | | | REQUIRED. THE MODEL INDICATED SHOWS ONE TRAP AND ONE | | | SUPPLY TO THE HI/LOW DRINKING FOUNTAIN. EACH FIXTURE | | | SHALL HAVE ITS OWN TRAP AND WATER SUPPLY SO THE | | | HIGH/LOW INDICATED IS CONSIDERED ONE FIXTURE. PLEASE | | | INDICATE THE LOCATION OF THE SECOND DRINKING FOUNTAIN. | | | SECTIONS 410.1 & 1002.1. (WATER ISOMETRIC ONLY SHOWS | | | ONE SUPPLY ALSO). | | | ****NO WRITTEN RESPONSE, BUT THE SANITARY RISER SHOWS 2 | | | TRAPS, BUT THIS DOES NOT REFLECT THE FLOOR PLAN WHICH | | | SHOWS 1 TRAP. THE WATER SUPPLY RISER DIAGRAM ONLY SHOWS | | | ONE WATER SUPPLY. TWO DRINKING FOUNTAINS ARE REQUIRED. | | | | | | 3. SHT M1.2 WATER HEATER DETAIL. PLEASE SUBMIT THE | | | MANUFACTURE SPECIFICATION AND MODEL FOR THE THERMAL | | | EXPANSION TANK. SUBMIT MANUFACTURE CALCULATIONS OR | | | SIZING CHART FOR THE SIZING OF THE EXPANSION TANK. | | | SECTION 617.3.2. | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. NO TRANSMITTAL | | | LETTER SUBMITTED, NOR WAS ONE SET OF VOIDED SHEETS | | | SUBMITTED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-29 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-28 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2009-01-29 15:15:08 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SHT A1.1 SHOW ACCESSIBILITY COMPLIANCE WITH THE | | | FOLLOWING: | | | | | | ___W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | | | | ___URINAL: | | | A. 11-4.18.2 HEIGHT | | | B. 11-4.18.3 CLEAR FLOOR SPACE | | | C. 11-4.18.4 FLUSH CONTROLS | | | | | | ___TOILET ROOMS: | | | A. 11-4.22.3 THE UNOBSTRUCTED TURNING AREAS ARE NOT | | | SHOWN IN THE TOILET ROOMS OF TOILET ROOMS 115 & 116. | | | THE TURNING AREA SHALL BE SHOWN IN THE TOILET ROOM, NOT | | | THE ACCESSIBLE STALL. | | | | | | ___SINK: | | | A. 11-4.24.2 HEIGHT | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.5 CLEAR FLOOR SPACE - PARALLEL APPROACH | | | SHOWN BUT FORWARD APPROACH REQUIRED. SUBMIT AN | | | ELEVATION SHOWING THE REQUIRED OPENING. CABINET DOORS | | | ARE NOT APPROVED IN THE CLEAR FLOOR SPACE. | | | | | | 2. SHT M1.2 PER TABLE 403.1 TWO DRINKING FOUNTAINS ARE | | | REQUIRED. THE MODEL INDICATED SHOWS ONE TRAP AND ONE | | | SUPPLY TO THE HI/LOW DRINKING FOUNTAIN. EACH FIXTURE | | | SHALL HAVE ITS OWN TRAP AND WATER SUPPLY SO THE | | | HIGH/LOW INDICATED IS CONSIDERED ONE FIXTURE. PLEASE | | | INDICATE THE LOCATION OF THE SECOND DRINKING FOUNTAIN. | | | SECTIONS 410.1 & 1002.1. (WATER ISOMETRIC ONLY SHOWS | | | ONE SUPPLY ALSO). | | | | | | 3. SHT M1.2 WATER HEATER DETAIL. PLEASE SUBMIT THE | | | MANUFACTURE SPECIFICATION AND MODEL FOR THE THERMAL | | | EXPANSION TANK. SUBMIT MANUFACTURE CALCULATIONS OR | | | SIZING CHART FOR THE SIZING OF THE EXPANSION TANK. | | | SECTION 617.3.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-12-22 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2008-12-22 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2008-12-22 |
Time |
13:35 |
Sent To |
|
|
| Notes |
|
|