Plan Review Details - Permit 08120274
Plan Review Stops For Permit 08120274
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-07-24 Cont ID  
Sent By jwitmer Date 2009-07-24 Time 07:59 Rev Time 0.50
Received By jwitmer Date 2009-07-24 Time 07:30 Sent To  
Notes
2009-07-24 07:53:32EXPEDITED PLAN REVIEW
 7:30-8:00 AM
 SHEET A3.1 REVISION# 3

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-21 Cont ID  
Sent By mawillia Date 2009-07-02 Time 12:17 Rev Time 1.11
Received By jwitmer Date 2009-04-21 Time 09:19 Sent To PC
Notes
2009-04-21 09:21:40TO PROCESS PLANS AND BUILDING PROVISO:
 BUILDING PLAN REVIEW
 PERMIT: 08120274
 ADD: 303 BANYAN / 4TH FLOOR
 CONT: LCI CONSTRUCTION
 TEL: (561)578-5930
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
  
 SHEET A3.1 HAS VARIOUS DETAILS INDICATING SOFFITS HUNG
 FROM STRUCTURE ABOVE, PLEASE PROVIDE WHAT TYPE OF
 ATTACHMENT METHOD WILL BE USED. 2506.2 STANDARDS, STEEL
 STUDS NON-LOAD BEARINGASTM C-645-00, TABLE 2508.1,
 GYPSUM BOARD GA 216 & 106.1.2 ADDITIONAL INFORMATION
 REQUIRED. THIS INFORMATION WILL BE REQUIRED BY FRAMING
 INSPECTION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-06 Cont ID  
Sent By jwitmer Date 2009-04-06 Time 07:39 Rev Time 1.00
Received By jwitmer Date 2009-04-06 Time 07:39 Sent To  
Notes
2009-04-06 07:46:38BUILDING PLAN REVIEW
 PERMIT: 08120274
 ADD: 303 BANYAN / 4TH FLOOR
 CONT: LCI CONSTRUCTION
 TEL: (561)578-5930
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
  
 SHEET A3.1 HAS VARIOUS DETAILS INDICATING SOFFITS HUNG
 FROM STRUCTURE ABOVE, PLEASE PROVIDE WHAT TYPE OF
 ATTACHMENT METHOD WILL BE USED. 2506.2 STANDARDS, STEEL
 STUDS NON-LOAD BEARINGASTM C-645-00, TABLE 2508.1,
 GYPSUM BOARD GA 216 & 106.1.2 ADDITIONAL INFORMATION
 REQUIRED. THIS INFORMATION WILL BE REQUIRED BY FRAMING
 INSPECTION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-24 Cont ID  
Sent By jwitmer Date 2008-12-24 Time 15:06 Rev Time 3.33
Received By jwitmer Date 2008-12-24 Time 13:36 Sent To  
Notes
2008-12-24 15:45:56BUILDING PLAN REVIEW
 PERMIT: 08120274
 ADD: 303 BANYAN / 4TH FLOOR
 CONT: LCI CONSTRUCTION
 TEL: (561)578-5930
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B)INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS AND 2004 EXISTING
 BUILDING CODE WITH 2007 SUPPLEMENTS.
  
 2) ENERGY CODE , THE PROJECT SUMMARY INDICATES WHOLE
 METHOD "A" WAS SUBMITTED WHOLE BUILDING PERFORMANCE
 METHOD, THIS IS A 4TH FLOOR TENANT BUILD-OUT NOT A
 WHOLE BUILDING. PLEASE REVIEW 13-101.1.3. RENOVATIONS
 AND 13-202 DEFINITION FOR RENOVATIONS. BY DEFINTION
 THIS IS NOT A RENOVATION.SEE 13-400.0.C.4. EXISTING
 BUILDINGS NOT MEETING THE DEFINTION OFA RENOVATION IN
 WHICH NEW HEATING,COOLING,WATER HEATING, ELECTRICAL OR
 LIGHTING SYSTEMS ARE INSTALLED SHALL MEET THE BASIC
 PRESCRIPTIVE MINIMUM EFFICIENCIES LISTED IN THE CODE
 FOR THE SYSTEMS BEING CHANGED.
  
 3) SHEET A1.1:
  
 3A) DOOR# 45& 6, BOTH ARE INDICATED AS A 2'-6" DOOR ON
 THE DOOR SCHEDULE, 11-4.13.5 MINIMUM CLEAR OPENING IS
 32" , OPENINGS MORE THAN 24 INCHES IN DEPTH SHALL
 COMPLY WITH SECTIONS 11-4.2.1 AND 11-4.3.3.
 3B) DOOR# 42 REQUIRES 1'-6" CLEAR ON THE PULL SIDE,
 PLEASE REVIEW 11-4.13.6. MANEUVERING CLEARENCES AT
 DOORS.
  
 3C) ROOM # 127 THE EMPLOYEE LOUNGE INDICATES A SIDE
 APPROACH, AND SHEET A4.1 DETAIL# 4 ALSO INDICATE DOORS
 ON THE FRONT MAKING IT IMPOSSIBLE FOR A FRONT APPROACH.
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION
  
 4) SHEET A3.1 HAS VARIOUS DETAILS INDICATING SOFFITS
 HUNG FROM STRUCTURE ABOVE, PLEASE PROVIDE WHAT TYPE OF
 ATTACHMENT METHOD WILL BE USED. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 5) SHEET A3.1 DETAIL# 14 INDICATES A FIRESTOPPING AT
 THE 4TH FLOOR MEZZANINE LEVEL, ITHERE ARE NO PLANS OR
 DETAILS FOR WORK TO BE COMPLETED ON THAT LEVEL, OR PART
 OF THIS PERMIT?
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2009-08-05 Cont ID  
Sent By dpalmer Date 2009-08-05 Time 16:58 Rev Time 0.00
Received By dpalmer Date 2009-08-05 Time 16:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2009-07-24 Cont ID  
Sent By dpalmer Date 2009-07-24 Time 20:12 Rev Time 0.00
Received By dpalmer Date 2009-07-24 Time 20:12 Sent To  
Notes
2009-07-24 20:12:21 
 ** DENIED REVISIONS **
  
 1) NOTE: PLEASE SEE THE SUBMITTED SKE ELECTRICAL DETAIL
 SHEETS DO NOT CONTAIN THE RAISED SEAL AS REQUIRED PER
 FAC 61G15-23.002, FS 471.025. IN FACT ONE OF THE THREE
 SUBMITTED IS A PHOTO-COPY.
 PLEASE SUBMIT A MINIMUM OF TWO ORIGINAL SIGNED, DATED
 AND SEALED SHEETS.
  
 2) NOTE: IT WAS NOTED ON PREVIOUS REVIEWS AS A
 *HEADS-UP* ON INFORMATION TO SEE THE NEW FLORIDA
 ASME-17 FOR MINIMUM ELEVATOR CODE REQUIREMENTS.
 THIS OFFICE DOES NOT REVIEW FOR THESE ITEMS FOR MINIMUM
 CODE COMPLIANCE HOWEVER BASED ON THE CODE REQUIREMENTS
 KNOWN TO THIS REVIEWER LIGHTING IN AREAS OF THE
 ELEVATOR LOBBY AS SHOWN WOULD NOT MEET MINIMUM. AN
 INSPECTION BY THE STATE ELEVATOR INSPECTOR WOULD NOT BE
 THE TIME TO FIND OUT ITEMS WHICH WOULD THEN NEED TO BE
 ADDED WHICH WOULD DELAY A TCO OR CO.
 ** SEE LIGHTING LEVELS FOR SILLS AND AT LANDINGS.
  
 ** THIS WILL AFFECT LPC. 13-415.2.ABC.1.1,.1.2,
 13-415.2.
  
 ** THE LIGHTING SHOWN ON THE REFLECTED CEILING PLAN OF
 THE ARCHITECTURAL PLANS DOES NOT COORDINATE WITH THE
 ELECTRICAL PLANS FOR THE ELEVATOR LOBBY.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2009-07-10 Cont ID  
Sent By rregueir Date 2009-07-10 Time 11:49 Rev Time 0.00
Received By rregueir Date 2009-07-10 Time 11:49 Sent To PC
Notes
2009-07-10 11:53:30PAGE SKE-1 DENIED PER DOUG WISE. SKETCH CALLS FOR
 ADDITION OF J BOXES AND SMOKE DETECTOR TO OPERATE AIR
 CURTAINS AT ELEVATOR DOORS. LIFE SAFETY PLAN PAGE A4.1
 CALLS FOR SMOKE GUARD ROLL-DOWN DOORS AT THESE
 LOCATIONS, NOT AIR CURTAINS. PLEASE CORRECT AND
 COORDINATE WITH LIFE SAFETY PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2009-06-29 Cont ID  
Sent By dpalmer Date 2009-06-29 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2009-06-29 Time 13:52 Sent To M
Notes
2009-06-29 13:52:23** NO REVIEW **
  
 ** SUBMITTED REVISIONS/ SKE FOR ADDITION OF SD AND J
 BOX OK WITH ELECTRICAL HOWEVER NEEDS REVIEW FROM
 MECHANICAL AND FIRE BEFORE STAMPING SHEETS.
  
 THERE IS QUESTIONS ON INSTALLATION OF AIR CURTAINS
 OUTSIDE ELEVATOR IN LOBBYS.
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-06-15 Cont ID  
Sent By dpalmer Date 2009-06-15 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2009-06-15 Time 11:36 Sent To PC
Notes
2009-06-15 11:37:35REV E1.2 FOR FLOOR BOXES AND TV OUTLET.
 REDLINED PLANS, ALL LOW VOLTAGE TO BE UNDER SEPARATE
 PERMIT(S).

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-05-26 Cont ID  
Sent By dpalmer Date 2009-05-26 Time 16:31 Rev Time 0.00
Received By dpalmer Date 2009-05-26 Time 16:31 Sent To PC
Notes
2009-05-26 16:31:54REVISIONS FOR RECEPTACLES ONLY.
 REDLINED, ALL LV SYSTEMS SHALL BE UNDER SEPARATE
 PERMITS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-04-16 Cont ID  
Sent By dpalmer Date 2009-04-16 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2009-04-16 Time 17:42 Sent To  
Notes
2009-04-16 17:43:15REDLINED PLANS
 VIF 210.63, 210.8B FOR ROOF TOP GFI REQUIRED FOR CU.
 NEW OR EXISTING.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-04-02 Cont ID  
Sent By dpalmer Date 2009-04-02 Time 19:08 Rev Time 0.00
Received By dpalmer Date 2009-04-02 Time 19:08 Sent To  
Notes
2009-04-02 19:09:021) NOTE: NO MINIMUM CODES STATED ON ELECTRICAL PLANS
 FOR WHICH PROJECT IS UNDER. THE A SHEETS DO NOT CONTAIN
 THE CURRENT MINIMUM REQUIRED CODES AS NEEDED BELOW.
 PLEASE SEE THAT THE FOLLOWING ARE ON PLANS.
  
 2004 FBC W/2007 REVISIONS.
 2003 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE NEC 220.12,220.14, 220.42, 220.44
 ETC LOAD CALCULATIONS FOR PLANS NEED TO MEET THE NEC.
 THE LOAD CALCULATIONS STATE THE MAXIMUM WATTAGE
 ALLOWANCE FOR LIGHTING PER THE FBC. THE SIZING OF
 LIGHTING PANELS FOR FEEDERS, BRANCH CIRCUITS AND
 SERVICE LOAD CALCULATIONS ARE BASE DON THE NEC NOT THE
 FLORIDA BUILDING CODE. THE MINIMUM LIGHTING WATTS PER
 SQUARE FOOT WHEN SIZING THE ABOVE MUST BE PER NEC.
 PLEASE REVISE ALL.
 THIS MAY AFFECT THE SIZE OF THE PANEL.
  
 3) NOTE: AS REQUESTED ON THE PREVIOUS REVIEW THE
 MINIMUM LEVELS, HEIGHTS ETC FOR HORNS, HORN STROBE
 DEVICES SHALL MEET THE FBC CHAPTER 11. 11-4.28.1, .2
 AND .3.
 NO DEVICE LEVELS, HEIGHTS ETC WERE SHOWN ON ANY OF THE
 THREE SHEETS.
  
 4) NOTE: PLEASE SEE THE SUBMITTED FORM B FOR CHAPTER 13
 COMPLIANCE IS FROM THE NEW 2007 FBC. MIXING OF
 CALCULATIONS FROM DIFFERENT CODES IS NOT PERMITTED.
 PLANS SHOW COMPLIANCE WITH THE SPACE BY SPACE METHOD B.
 THIS IS ALL THAT IS NEEDED FOR THIS REVIEWER. PLEASE
 SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY BE NEEDED.
  
 5) NOTE: THE PLANS INDICATE AN IT ROOM WITH A
 DISCONNECT SWITCH FOR AHU, HOWEVER COMPLIANCE WITH NEC
 645, 6.4510 ETC IS NOT MET. THE ROOM MAY NOT BE CALLED
 AND IT ROOM UNLESS MEETING ALL OF THE REQUIREMENTS IN
 NEC 645.4. (1-5)
 WHEN MEETING ALL OF THESE ITEMS AS LISTED THEN THE LESS
 RESTRICTIVE WIRING METHODS PERMITTED IN 645 IS
 PERMITTED. WHEN NOT MEETING THE ABOVE SECTIONS ALL 1-5,
 THEN ALL WIRING METHODS SHALL BE PER CHAPTERS 1-4 OF
 THE NEC. PLEASE KEEP IN MIND THAT COMPANY IT OR LOW
 VOLTAGE PERSONNEL MAY WANT TO USE WIRING METHODS IN
 645, IF SO, THEN THE ROOM SHALL MEET ALL ITEMS IN 645.4
 1-5.
 IF THIS ROOM IS NOT AN IT ROOM, REVISE DESIGNATION AND
 PLEASE PLACE NOTE ON PLANS WHICH STATES * NO WIRING
 METHODS PER NEC 645 PERMITTED* OR WORDS TO THAT AFFECT.
 CALL FOR QUESTIONS.
  
 6) NOTE: THE LIFE SAFETY PLANS DO NOT CORRELATE WITH
 THE ELECTRICAL PLANS FOR EMERGENCY LIGHTING.
 THE LIFE SAFETY SHEETS ALSO STATE TO SEE ELECTRICAL
 PLANS FOR EMERGENCY LIGHTING ABOVE SOFFIT HOWEVER THE
 ELECTRICAL PLANS DO NOT INDICATE ANY EMERGENCY LIGHTING
 ABOVE SOFFIT.
 NFPA-101 7.8, 7.9
 FBC 1006.1.2
  
 7) NOTE: PLEASE KEEP IN MIND ALL OF THE NEW
 REQUIREMENTS OF ASME-17 FOR FLORIDA ELEVATOR CODE
 REQUIREMENTS STILL MUST BE MET. THIS IS ONLY NOTED FOR
 INFORMATIONAL PURPOSE. THIS IS NOT A REVIEW COMMENT FOR
 THIS TRADE. THERE IS ITEMS PER STATE ELEVATOR CODE
 WHICH WOULD NOT MEET CURRENT ELEVATOR CODES.
 SEE REFERENCE FROM FBC CHAPTER 30, NEC FPN TO ASME.
  
 8) NOTE: PANEL SCHEDULE FOR CIRCUITS DOES NOT MEET
 408.4. STATING RECEPTACLES WITHOUT SPECIFIC ROOM AND
 AREAS IS NOT PERMITTED. PLEASE SEE REVISED 2005 NEC AND
 COMMENTARY IN HANDBOOK.
 PLEASE REVISE.
  
 ** KEEP IN MIND FS 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR MINIMUM CODE COMPLIANCE.
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-30 Cont ID  
Sent By dpalmer Date 2008-12-30 Time 09:12 Rev Time 0.00
Received By dpalmer Date 2008-12-30 Time 09:12 Sent To  
Notes
2008-12-30 09:12:38** DENIED REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE FBC
 13-101.1,13-101.1.3,13-400.0.C.4 ETC
 THE SUBMITTED PROPOSED METHOD OF CALCULATIONS WAS FOR
 *WHOLE BUILDING COMPLIANCE* ON METHOD *A*FLA-COM.
 PLEASE EXPLAIN WHERE IN THE CODE DOES IT PERMIT METHOD
 *A* FOR WHOLE BUILDING COMPLIANCE TO BE USED FOR THE
 BUILD OUT OF A SHELL SPACE.
  
 PLANS CONTAIN SPACE BY SPACE FROM TABLE *B*.
 PLEASE SEE 13-415.2.ABC.1. THE CODE DOES NOT PERMIT THE
 USE OF MULTIPLE METHODS.
 IN EITHER CASE THE SUBMITTED INPUT DATA REPORT DOES NOT
 MATCH THE SUBMITTED PLANS. FOR EXAMPLE: PLEASE SEE ZONE
 #1 WHICH ONLY LIST A TOTAL OF FOUR FIXTURES. HOW IS
 THIS POSSIBLE WHEN THE LOBBY ON THE PLANS CLEARLY
 INDICATES SEVERAL MORE FIXTURES? IN THE LOBBY ALONE
 THERE A TOTAL OF 8 *M* FIXTURES ALONE.
  
 ** THIS IS ONE EXAMPLE:
 PLEASE SEE THE TOTAL AMOUNT OF DESIGN WATTAGE SHOWN ON
 SHEET E1.1 IS LESS THAN THE ACTUAL TOTAL WATTAGE OF
 FIXTURES SHOWN ON PLANS. THE TOTAL ON *A* FIXTURES IS
 ABOVE 8300. PLEASE BE SURE TO GO OVER ALL FIXTURES, THE
 WATTAGE OF EACH AND THE NUMBER OF FIXTURES.
  
 2) NOTE: PLEASE PROVIDE INFORMATION ON THE MULTI-GANG
 BATHROOM OCCUPANCY SENSORS. DO THESE CONTAIN DUAL
 TECHNOLOGIES?
 NFPA-101 7.8.
  
 3) NOTE: PLEASE SEE THE LOAD ON PANEL LA EXCEEDS THE
 BREAKER RATING IN PANEL *L* WHICH FEEDS THIS PANEL. THE
 LOAD SHOWN IS 33AMPS YET THERE IS ONLY A 25AMP BREAKER
 FEEDING THIS PANEL.
 240,310,215 ETC
 FBC 106.1.1
  
 4) NOTE: THE WATER HEATER IS SHOWN BEING FED FROM A TWO
 POLE RECEPTACLE WHICH IS NOT PERMITTED. PLEASE SHOW THE
 REQUIRED DISCONNECT. 422.30,422.31
  
 5) NOTE: PLEASE SHOW ALL HORN, HORN/STROBE LOCATIONS,
 HEIGHTS AND LEVELS OF DEVICES TO MEET ADA COMPLIANCE.
 PLEASE SEE FBC 11-4.28.1,.2 AND .3.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-01-16 Cont ID  
Sent By efabian Date 2009-01-16 Time 13:30 Rev Time 0.00
Received By efabian Date 2009-01-16 Time 13:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-08-07 Cont ID  
Sent By mawillia Date 2009-08-07 Time 12:13 Rev Time 0.00
Received By mawillia Date 2009-08-07 Time 11:26 Sent To  
Notes
2009-08-07 11:41:58*****REVISIONS, DATED 7/20/09, APPROVED*****
  
  
 REVISED PLAN SHEETS A3.1, E1.1, AND PAGE SKE-1R WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-07-02 Cont ID  
Sent By mawillia Date 2009-07-02 Time 12:17 Rev Time 0.00
Received By mawillia Date 2009-07-02 Time 11:52 Sent To B
Notes
2009-07-02 12:17:03*****REVISION APPROVED*****
  
 PLAN REVISION (IN PDF FORM) WITH SUBMITTAL REVIEWED AND
 APPROVED; HOWEVER, FIRE-STAMPING NOT NEEDED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-04-20 Cont ID  
Sent By mawillia Date 2009-04-20 Time 11:36 Rev Time 0.00
Received By mawillia Date 2009-04-20 Time 11:02 Sent To  
Notes
2009-04-20 11:36:22*****APPROVED*****
  
 THE COMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN REVIEW
 HAVE BEEN ADDRESSED; PLAN SHEETS A2.1, A4.1, E1.1, AND
 E1.2 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-04-06 Cont ID  
Sent By mawillia Date 2009-04-06 Time 16:26 Rev Time 0.00
Received By mawillia Date 2009-04-06 Time 16:14 Sent To  
Notes
2009-04-06 16:25:27*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW WERE NOT AND STILL NEED TO BE ADDRESED:
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH
 ACCESS TO AND/OR EGRESS FROM THE OTHER FLOORS OF THE
 BUILDING.
  
 3. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED. CHAPTER 38 (NEW BUSINESS OCCUPANCY) OF THIS
 CODE IS APPLICABLE SINCE THE SCOPE WORK IS FOR
 ALTERATIONS, MODERNIZATIONS, OR RENOVATIONS OF AN
 EXISTING BUSINESS OCCUPANCY.
  
 4. PLEASE INDICATE IF THIS FLOOR/BUILDING IS FIRE
 SPRINKLERED. IF SO, PROVIDE A FIRE SPRINKLER LAYOUT FOR
 THE FOURTH FLOOR.
  
 5. SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6. FIRE DOORS SHALL COMPLY WITH NFPA 80.
  
 7. CLARIFYVERIFY VERBAGE ON DRAWING A2.1 DOOR HARDWARE
 NOTE #3, UNDER THE DOOR SCHEDULE. IS THIS WORD "EXIST"
 OR "EXITS" ?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-01-28 Cont ID  
Sent By mawillia Date 2009-01-28 Time 15:26 Rev Time 0.00
Received By mawillia Date 2009-01-28 Time 13:54 Sent To  
Notes
2009-01-28 15:24:41*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH
 ACCESS TO AND/OR EGRESS FROM THE OTHER FLOORS OF THE
 BUILDING.
  
 3. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED. CHAPTER 38 (NEW BUSINESS OCCUPANCY) OF THIS
 CODE IS APPLICABLE SINCE THE SCOPE WORK IS FOR
 ALTERATIONS, MODERNIZATIONS, OR RENOVATIONS OF AN
 EXISTING BUSINESS OCCUPANCY.
  
 4. PLEASE INDICATE IF THIS FLOOR/BUILDING IS FIRE
 SPRINKLERED. IF SO, PROVIDE A FIRE SPRINKLER LAYOUT FOR
 THE FOURTH FLOOR.
  
 5. SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6. FIRE DOORS SHALL COMPLY WITH NFPA 80.
  
 7. CLARIFYVERIFY VERBAGE ON DRAWING A2.1 DOOR HARDWARE
 NOTE #3, UNDER THE DOOR SCHEDULE. IS THIS WORD "EXIST"
 OR "EXITS" ?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-07-21 Cont ID  
Sent By lmartine Date 2009-07-21 Time 13:42 Rev Time 0.00
Received By lmartine Date 2009-07-21 Time 13:42 Sent To  
Notes
2009-07-21 13:56:51*EXPEDITED* B-10

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-06-24 Cont ID  
Sent By shill Date 2009-06-24 Time 14:49 Rev Time 0.00
Received By shill Date 2009-06-24 Time 14:49 Sent To  
Notes
2009-06-24 14:49:43REVISION TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2009-06-04 Time   Rev Time 0.00
Received By rmcdouga Date 2009-06-04 Time 14:07 Sent To  
Notes
2009-06-04 14:06:30REVISION TO DEWEY PALMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-02 Cont ID  
Sent By adarroug Date 2009-04-02 Time 14:58 Rev Time 0.00
Received By adarroug Date 2009-04-02 Time 14:58 Sent To  
Notes
2009-04-02 15:06:01TO "C10"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-29 Cont ID  
Sent By kstevens Date 2009-01-29 Time 15:16 Rev Time 0.00
Received By kstevens Date 2008-12-15 Time 09:01 Sent To  
Notes
2008-12-15 09:05:47TO "COMM" BD#16

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-08-01 Cont ID  
Sent By rregueir Date 2009-08-01 Time 17:43 Rev Time 0.00
Received By rregueir Date 2009-08-01 Time 17:42 Sent To  
Notes
2009-08-01 17:43:00REVISED M1.1 DELTA 6

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-07-10 Cont ID  
Sent By rregueir Date 2009-07-10 Time 14:26 Rev Time 0.00
Received By rregueir Date 2009-07-10 Time 14:25 Sent To PC
Notes
2009-07-10 14:25:57REVISED M1.1 DELTA 5

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-07-10 Cont ID  
Sent By rregueir Date 2009-07-10 Time 11:48 Rev Time 0.00
Received By rregueir Date 2009-07-10 Time 11:43 Sent To  
Notes
2009-07-10 11:48:15SKETCH SKM-1 AND SKM-2 OK PER DOUG WISE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-04-02 Cont ID  
Sent By hmoser Date 2009-04-02 Time 16:05 Rev Time 0.00
Received By hmoser Date 2009-04-02 Time 16:05 Sent To  
Notes
2009-04-02 16:13:24PASS PROVISO
 PLEASE PROVIDE A SEALD LETTER FROM ARNOLD CHANE ON SIZE
 OF HANGER RODS FOR THE AIR-HANDLERS ,AT TIME OF 1ST
 INSPECTION .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732 .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-01-15 Cont ID  
Sent By hmoser Date 2009-01-15 Time 13:57 Rev Time 0.00
Received By hmoser Date 2009-01-15 Time 13:57 Sent To  
Notes
2009-01-15 14:07:2201/15/2009
 PLEASE REFER TO SECTION 607.5.1 2004 FBC (M) FIRE WALLS
 FOR ELECTRICAL ROOM 125 .
 PLEASE REFER TO SECTION 603.5.5 PENETRATIONS PROHIBITED
 2004 FBC (M)
 PLEASE PROVIDE THE SIZE OF HANGER ROD FOR HORIZONTAL
 AHU DETAIL PAGE M2-2 ON MECHANICAL PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-04-17 Cont ID  
Sent By kstevens Date 2009-04-17 Time 17:48 Rev Time 0.00
Received By kstevens Date 2009-04-17 Time 17:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-04-03 Cont ID  
Sent By kstevens Date 2009-04-03 Time 17:33 Rev Time 0.00
Received By kstevens Date 2009-04-03 Time 17:32 Sent To  
Notes
2009-04-03 17:32:51DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A1.1 SHOW ACCESSIBILITY COMPLIANCE WITH THE
 FOLLOWING:
  
 ___W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ___URINAL:
 A. 11-4.18.2 HEIGHT
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 B. 11-4.18.3 CLEAR FLOOR SPACE
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 C. 11-4.18.4 FLUSH CONTROLS
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ___TOILET ROOMS:
 A. 11-4.22.3 THE UNOBSTRUCTED TURNING AREAS ARE NOT
 SHOWN IN THE TOILET ROOMS OF TOILET ROOMS 115 & 116.
 THE TURNING AREA SHALL BE SHOWN IN THE TOILET ROOM, NOT
 THE ACCESSIBLE STALL.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ___SINK:
 A. 11-4.24.2 HEIGHT
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 B. 11-4.24.3 KNEE CLEARANCE
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 C. 11-4.24.5 CLEAR FLOOR SPACE - PARALLEL APPROACH
 SHOWN BUT FORWARD APPROACH REQUIRED. SUBMIT AN
 ELEVATION SHOWING THE REQUIRED OPENING. CABINET DOORS
 ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2. SHT M1.2 PER TABLE 403.1 TWO DRINKING FOUNTAINS ARE
 REQUIRED. THE MODEL INDICATED SHOWS ONE TRAP AND ONE
 SUPPLY TO THE HI/LOW DRINKING FOUNTAIN. EACH FIXTURE
 SHALL HAVE ITS OWN TRAP AND WATER SUPPLY SO THE
 HIGH/LOW INDICATED IS CONSIDERED ONE FIXTURE. PLEASE
 INDICATE THE LOCATION OF THE SECOND DRINKING FOUNTAIN.
 SECTIONS 410.1 & 1002.1. (WATER ISOMETRIC ONLY SHOWS
 ONE SUPPLY ALSO).
 ****NO WRITTEN RESPONSE, BUT THE SANITARY RISER SHOWS 2
 TRAPS, BUT THIS DOES NOT REFLECT THE FLOOR PLAN WHICH
 SHOWS 1 TRAP. THE WATER SUPPLY RISER DIAGRAM ONLY SHOWS
 ONE WATER SUPPLY. TWO DRINKING FOUNTAINS ARE REQUIRED.
  
 3. SHT M1.2 WATER HEATER DETAIL. PLEASE SUBMIT THE
 MANUFACTURE SPECIFICATION AND MODEL FOR THE THERMAL
 EXPANSION TANK. SUBMIT MANUFACTURE CALCULATIONS OR
 SIZING CHART FOR THE SIZING OF THE EXPANSION TANK.
 SECTION 617.3.2.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ****NO RESPONSE, COMMENT NOT ADDRESSED. NO TRANSMITTAL
 LETTER SUBMITTED, NOR WAS ONE SET OF VOIDED SHEETS
 SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-29 Cont ID  
Sent By kstevens Date 2009-01-29 Time 14:50 Rev Time 0.00
Received By kstevens Date 2009-01-28 Time 16:57 Sent To  
Notes
2009-01-29 15:15:08DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A1.1 SHOW ACCESSIBILITY COMPLIANCE WITH THE
 FOLLOWING:
  
 ___W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
  
 ___URINAL:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
  
 ___TOILET ROOMS:
 A. 11-4.22.3 THE UNOBSTRUCTED TURNING AREAS ARE NOT
 SHOWN IN THE TOILET ROOMS OF TOILET ROOMS 115 & 116.
 THE TURNING AREA SHALL BE SHOWN IN THE TOILET ROOM, NOT
 THE ACCESSIBLE STALL.
  
 ___SINK:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.5 CLEAR FLOOR SPACE - PARALLEL APPROACH
 SHOWN BUT FORWARD APPROACH REQUIRED. SUBMIT AN
 ELEVATION SHOWING THE REQUIRED OPENING. CABINET DOORS
 ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
  
 2. SHT M1.2 PER TABLE 403.1 TWO DRINKING FOUNTAINS ARE
 REQUIRED. THE MODEL INDICATED SHOWS ONE TRAP AND ONE
 SUPPLY TO THE HI/LOW DRINKING FOUNTAIN. EACH FIXTURE
 SHALL HAVE ITS OWN TRAP AND WATER SUPPLY SO THE
 HIGH/LOW INDICATED IS CONSIDERED ONE FIXTURE. PLEASE
 INDICATE THE LOCATION OF THE SECOND DRINKING FOUNTAIN.
 SECTIONS 410.1 & 1002.1. (WATER ISOMETRIC ONLY SHOWS
 ONE SUPPLY ALSO).
  
 3. SHT M1.2 WATER HEATER DETAIL. PLEASE SUBMIT THE
 MANUFACTURE SPECIFICATION AND MODEL FOR THE THERMAL
 EXPANSION TANK. SUBMIT MANUFACTURE CALCULATIONS OR
 SIZING CHART FOR THE SIZING OF THE EXPANSION TANK.
 SECTION 617.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-12-22 Cont ID  
Sent By aaponte Date 2008-12-22 Time 13:35 Rev Time 0.00
Received By aaponte Date 2008-12-22 Time 13:35 Sent To  
Notes
***NONE***