Plan Review Details - Permit 08120272
Plan Review Stops For Permit 08120272
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-03-13 Cont ID  
Sent By shill Date 2009-03-13 Time 08:48 Rev Time 0.00
Received By shill Date 2009-03-13 Time 08:48 Sent To  
Notes
2009-03-13 08:49:34HAD TELEPHONE CONVERSATION W/ENGINEER & OWNER
 ENGINEER CONFIRMED STRAP CAPACITY OK
 ENGINEER AGREED TO PROVIDE REVISION CORRECTING BUILDING
 TYPE, LEVEL OF ALTERATION BEFORE FINAL
 ISSUED W/PROVISO
 AT CONTRACTOR'S RISK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-03-04 Cont ID  
Sent By shill Date 2009-03-04 Time 16:10 Rev Time 0.00
Received By shill Date 2009-03-04 Time 16:10 Sent To  
Notes
2009-03-04 16:16:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1-10. ADDRESSED.
  
 11. SPECIFY ROOF DESIGN PRESSURE, FBC R301.
  
 2ND REVIEW, NOT ADDRESSED. SEE FBC1609. PLEASE SPECIFY
 PRESSURES AS REQUESTED.
  
 3RD REVIEW, NOT ADDRESSED.
  
 NEW COMMENTS:
  
 PLEASE CHECK ALL INFORMATION ON A1. LEVEL 1 ALTERATION
 DECLARED; THIS IS AN ADDITION, HOW CAN THIS BE A LEVEL
 I? BUILDING TYPE III V DECLARED; PLEASE GIVE CODE
 SECTION WHERE III V IS A BUILDING TYPE. .18 PRESSURE
 COEFFICIENT STATED; THIS IS A PORCH OPEN ON TWO SIDES.
 SHOULDN'T YOU BE DESIGNING TO A PARTIALLY ENCLOSED
 CONDITION? HOW HAVE "ACTUAL LOADS' ON THE TRUSS
 ANCHORAGE SCHEDULE BEEN DETERMINED?
  
 SHUTTER PRODUCT APPRPOVALS SUBMITTED; WHY ARE THEY IN
 THIS PACKAGE? PLEASE REMOVE; IT APPEARS THEY BELONG TO
 A DIFFERENT PERMIT.
  
 A SET HAS BEEN RETAINED. WHEN RESUBMITTING, PROVIDE TWO
 COMPLETE ORIGINAL SETS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-29 Cont ID  
Sent By shill Date 2009-01-29 Time 11:33 Rev Time 0.00
Received By shill Date 2009-01-29 Time 11:33 Sent To  
Notes
2009-01-29 11:35:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. INFORMATIONAL ONLY - SEPARATE PERMIT REQUIRED, ROOF.
 PLEASE NOTE THAT INFORMATION REGARDING ROOF TILE
 ATTACHMENT WILL BE REQUIRED WITH THE ROOF PERMIT
 APPLICATION. NOA 06-0526.09 SUBMITTED.
  
 2. PLEASE CLARIFY USE OF EXPOSURE B, FBC R301.
  
 2ND REVIEW, NOT ADDRESSED. ENGINEER IS TO PROVIDE
 RATIONALE, NOT CLEAR WHY ENGINEER HAS DECLARED EXPOSURE
 B.
  
 3-10. ADDRESSED.
  
 11. SPECIFY ROOF DESIGN PRESSURE, FBC R301.
  
 2ND REVIEW, NOT ADDRESSED. SEE FBC1609. PLEASE SPECIFY
 PRESSURES AS REQUESTED.
  
 A SET HAS BEEN RETAINED. WHEN RESUBMITTING, PROVIDE TWO
 COMPLETE ORIGINAL SETS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-29 Cont ID  
Sent By shill Date 2008-12-29 Time 10:21 Rev Time 0.00
Received By shill Date 2008-12-29 Time 10:21 Sent To  
Notes
2008-12-29 10:37:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. INFORMATIONAL ONLY - SEPARATE PERMIT REQUIRED, ROOF.
 PLEASE NOTE THAT INFORMATION REGARDING ROOF TILE
 ATTACHMENT WILL BE REQUIRED WITH THE ROOF PERMIT
 APPLICATION. NOA 06-0526.09 SUBMITTED.
  
 2. PLEASE CLARIFY USE OF EXPOSURE B, FBC R301.
  
 3. GOVERNING CODE IS TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS.
  
 4. PLEASE EXPLAIN LEVEL OF ALTERATION 3, FBC EB CHAPTER
 3.
  
 5. PLEASE EXPLAIN CONSTRUCTION TYPE II AND CONSTRUCTION
 TYPE IIIB (BOTH DECLARED IN DIFFERENT PLACES). NOTE
 THAT TYPE IIIB HAS A 2 HOUR EXTERIOR BEARING WALL
 REQUIREMENT. THIS BUILDING IS TWO STORY; ARE ALL
 BEARING WALLS 2 HOUR INCLUDING SECOND FLOOR?
  
 6. HOW WILL TRUSSES CONNECT TO THE LEDGER? NOTHING
 SPECIFIFED. FBC*106, FBC R301.
  
 7. WHAT IS 3" A.B., ROOF FRAMING PLAN?
  
 8. SPECIFY ROOF PITCH, FBC R301. PLANS STATE THAT IT IS
 TO MATCH EXISTING, NOTHING SPECIFIED FOR EXISTING.
  
 9. SPECIFY BEAM CONSTRUCTION. NO INFORMATION PROVIDED.
  
 10. PLANS DO NOT CLEARLY REFLECT SCOPE OF WORK. SITE
 PLAN APPEARS TO SHOW THE SLAB ADJACENT TO HOUSE AS
 EXISTING, AS IT IS NOT INCLUDED WITH THE LABEL "NEW
 CONC SLAB" AS THE OTHER SECTION. BUT THE FOUNDATION
 PLAN SHOWS THIS AREA AS "TYPICAL" WITH A SPEC AND
 FOOTING. PLEASE CORRELATE, FBC*106.
  
 11. SPECIFY ROOF DESIGN PRESSURE, FBC R301.
  
 A SET HAS BEEN RETAINED. WHEN RESUBMITTING, PROVIDE TWO
 COMPLETE ORIGINAL SETS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-02-26 Cont ID  
Sent By btrobaug Date 2009-02-26 Time 16:13 Rev Time 0.00
Received By btrobaug Date 2009-02-26 Time 16:02 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-12-19 Cont ID  
Sent By btrobaug Date 2008-12-19 Time 13:52 Rev Time 0.00
Received By btrobaug Date 2008-12-19 Time 13:46 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-17 Cont ID  
Sent By adarroug Date 2009-02-17 Time 11:39 Rev Time 0.00
Received By adarroug Date 2009-02-17 Time 11:39 Sent To Z
Notes
2009-02-17 11:40:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 13:50 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 13:50 Sent To Z
Notes
2009-01-20 13:51:01TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-17 Cont ID  
Sent By adarroug Date 2008-12-17 Time 10:55 Rev Time 0.00
Received By adarroug Date 2008-12-17 Time 10:55 Sent To E
Notes
2008-12-17 10:56:17TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-29 Cont ID  
Sent By shill Date 2008-12-29 Time 10:37 Rev Time 0.00
Received By shill Date 2008-12-12 Time 16:33 Sent To  
Notes
2008-12-12 16:34:00TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2009-02-25 Cont ID  
Sent By mcruz Date 2009-02-25 Time 08:54 Rev Time 0.00
Received By mcruz Date 2009-02-25 Time 08:43 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-01-28 Cont ID  
Sent By mcruz Date 2009-01-28 Time 13:26 Rev Time 0.00
Received By mcruz Date 2009-01-28 Time 13:20 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-16 Cont ID  
Sent By mcruz Date 2008-12-16 Time 08:25 Rev Time 0.00
Received By mcruz Date 2008-12-15 Time 12:56 Sent To I
Notes
2008-12-16 08:25:00PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE ON SURVEY AND SITE THE SETBACK DIMENSIONS
 FROM THE PROPOSED ENCLODURE TO ALL ADJACENT PROPERTY
 LINES.
  
 4. INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION. PURSUANT TO THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B): OVERHANGS SHALL NOT PROJECT MORE THAN THREE
 (3) FEET INTO A REQUIRED SETBACK.
  
 5. IS THE PROPOSED CONCRETE SLAB EXTENDING TO THE
 PROPERTY LINE? IF YES, AN APPROVED EASEMENT CONSENT
 FORM FROM THE CITY OF WEST PALM BEACH DEPARTMENT OF
 PUBLIC UTILITIES (1ST FLOOR, CITY HALL) SHALL BE
 REQUIRED.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  