Plan Review Details - Permit 08120259
Plan Review Stops For Permit 08120259
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-29 Cont ID  
Sent By mjacobs Date 2009-01-29 Time 07:45 Rev Time 0.00
Received By mjacobs Date 2009-01-29 Time 07:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-15 Cont ID  
Sent By mjacobs Date 2008-12-15 Time 15:42 Rev Time 0.00
Received By mjacobs Date 2008-12-15 Time 15:42 Sent To  
Notes
2008-12-15 15:42:27BUILDING PLAN REVIEW
 PERMIT: 08120259
 ADD: 4225 45TH STREET.
 CONT: NEWCO CONSTRUCTION OF AMERICA, INC.
 TEL: (561)735-3877
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12-15-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE PLANS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. STATE THE LEVEL OF ALTERATION ON THE
 DRAWINGS PER THE SECTIONS INDICATED ABOVE.
  
 5) 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
 6) 481.219 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561)805-6676
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-09 Cont ID  
Sent By dpalmer Date 2009-02-09 Time 10:48 Rev Time 0.00
Received By dpalmer Date 2009-02-09 Time 10:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-01-30 Cont ID  
Sent By dpalmer Date 2009-01-30 Time 13:00 Rev Time 0.00
Received By dpalmer Date 2009-01-30 Time 12:59 Sent To  
Notes
2009-01-30 13:01:10** DENIED **
  
 1) NOTE: THE BASE BUILDING DOES NOT HAVE A CERTIFICATE
 OF OCCUPANCY. NEW APPLIED SCOPE OF WORK IN THIS
 BUILDING IS BEING APPLIED FOR FROM A SEPARATE
 CONTRACTOR OTHER THAN THE BASE BUILDING CONTRACTOR.
 THIS REQUIRES A LETTER OF UNDERSTANDING FROM THE BASE
 BUILDING AND NEW CONTRACTOR AS RELATED WORK IN THE SAME
 SPACE AND BUILDING WILL BE TAKING PLACE.
 PLEASE KEEP IN MIND THAT THIS WOULD ALSO BE REQUIRED
 FOR ANY OTHER CONTRACTORS UNDER THE PERMIT WHO MAY NOT
 BE THE BASE BUILDING SUB CONTRACTOR. AN EXAMPLE WOULD
 BE THE ELECTRICAL CONTRACTOR.
 IF THE ELECTRICAL SCOPE OF WORK AS SUBMITTED UNDER THIS
 PERMIT IS DONE BY AN ELECTRICAL CONTRACTOR OTHER THAN
 THE ELECTRICAL CONTRACTOR FOR THE BASE BUILDING THEN
 THIS WOULD ALSO REQUIRE A LETTER.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-24 Cont ID  
Sent By dpalmer Date 2008-12-24 Time 10:47 Rev Time 0.00
Received By dpalmer Date 2008-12-24 Time 10:47 Sent To  
Notes
2008-12-24 10:48:24** DENIED REVIEW**
  
  
 1) NOTE: PLEASE SUBMIT A LETTER OF UNDERSTANDING
 BETWEEN BASE BUILDING CONTRACTOR AND SUB CONTRACTOR AS
 THE BASE BUILDING DOES NOT CONTAIN A CERTIFICATE OF
 OCCUPANCY.
  
 2) NOTE: MISSING LICENSING INFORMATION AND OTHER
 INFORMATION ON TITLE BLOCKS PER FAC 61G1-16.004 FOR
 ARCHITECTURAL FIRM.
  
 3) NOTE: PLEASE SEE FS 553.73 AS THE ADOPTED CODES BY
 THE STATE OF FLORIDA IS NOT SHOWN ON PLANS. THE STATE
 OF FLORIDA IS UNDER THE 2004 FBC WITH 2007 REVISIONS
 AND ALSO UNDER THE 2005 NFPA-70 (NATIONAL ELECTRICAL
 CODE).
 PLEASE LIST ON PLANS AS FOLLOWS FOR THIS REVIEWER AND
 SEE POSSIBLE COMMENTS FROM OTHER TRADES.
  
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 4) NOTE: PLEASE SHOW NEW OR EXISTING HORN, STROBE AND
 PULL STATION LOCATIONS IN COMPLIANCE WITH NFPA-72 AND
 ALSO CHAPTER 11 OF THE FBC FOR ADA COMPLIANCE.
 PLEASE SEE FBC 11-4.28.1,.2, AND .3.
  
 5) NOTE: PLEASE SHOW NEW OR EXISTING LIGHTING IN
 COMPLIANCE FOR EGRESS UNDER NORMAL AND EMERGENCY
 CONDITIONS.
 NFPA-101 7.8,7.9
  
 6) NOTE: PLEASE SHOW NEW OR EXISTING LIGHTING CONTROLS
 IN COMPLIANCE WITH FBC 13-415.1.ABC.1.1,.1.2, .1.3.
  
 7) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,.1.2
 FOR INTERIOR LIGHTING PERFORMANCE LEVELS FOR NEW BEING
 INSTALLED. AS THE PLANS DO NOT INDICATE ANY LIGHTING,
 THE LIGHTING DENSITY LEVELS CAN NOT BE DETERMINED FOR
 CODE COMPLIANCE AT THIS TIME.
  
 8) NOTE: COLOR CODING SHALL BE BROWN, PURPLE, YELLOW
 FOR 277/480V AS ON BASE BUILDING. ORANGE IS THE COLOR
 BY THE NEC WHICH IS SET ASIDE FOR DELTA HIGH LEG
 SYSTEMS. THIS IS NOT SUCH A SYSTEM.
 PLEASE REVISE TO MATCH EXISTING.
 90.4
  
  
 ** THE PLANS ARE MISSING INFORMATION NEEDED TO SHOW
 MINIMUM CODE COMPLIANCE FOR SEVERAL ITEMS AS LISTED
 ABOVE. EACH RECORD SET OF PLANS FOR PERMITTED WORK
 NEEDS TO SHOW THIS AS THEY DO NOT CONTAIN BASE BUILDING
 INFORMATION.
 ** AS SOME INFORMATION IS MISSING THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT
 BE MADE AT THIS TIME.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-02-02 Cont ID  
Sent By mawillia Date 2009-02-02 Time 12:41 Rev Time 0.00
Received By mawillia Date 2009-02-02 Time 12:16 Sent To  
Notes
2009-02-02 12:32:44*****APPROVED*****
  
  
 PLAN SHEET A1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-24 Cont ID  
Sent By mwennerg Date 2008-12-24 Time 11:07 Rev Time 0.00
Received By mwennerg Date 2008-12-24 Time 11:07 Sent To  
Notes
2008-12-24 11:14:32***DENIED***
  
 1) PLEASE SHOW EXISTING FIRE PROTECTION EQUIPMENT.
  
 2) REMOVAL/REINSTALLATION OF ANY EXISTING FIRE
 PROTECTION EQUIPMENT WILL REQUIRE TESTING, INSPECTION
 AND APPROVAL FROM THIS OFFICE.
  
 3) PLEASE SEE ELECTRICAL COMMENT #5 REGARDING MEANS OF
 EGRESS LIGHTING.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 08:24 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 08:24 Sent To E
Notes
2009-02-09 08:25:20TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-27 Cont ID  
Sent By adarroug Date 2009-01-27 Time 09:12 Rev Time 0.00
Received By adarroug Date 2009-01-27 Time 09:12 Sent To  
Notes
2009-01-27 09:15:03TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-24 Cont ID  
Sent By mwennerg Date 2008-12-24 Time 11:18 Rev Time 0.00
Received By mwennerg Date 2008-12-12 Time 10:50 Sent To  
Notes
2008-12-12 10:50:19TO "BOB"#9


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved