| Plan Review Stops For Permit 08120208 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2009-05-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-05-06 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-05-06 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2009-05-06 10:23:43 | LETTER OK PER RB - LETTER PUT ON FILE (NOTHING GIVEN | | | BACK TO CONTRACTOR AS ONLY 1 LETTER SUBMITTED) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2009-05-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-05-01 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-05-01 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2009-05-01 16:22:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. LETTER STATES THAT THAT BLOCK MAY PROTRUDE A MINIMUM | | | OF 1"; PLEASE REVISE TO STATE "MAXIMUM" OR EXPLAIN | | | RATIONALE. | | | | | | 2. PLEASE PROVIDE JUSTIFICATION FOR THE STATEMENT THAT | | | THIS IS "WITHOUT STRUCTURAL COMPROMISE." CALCULATIONS | | | WERE PROVIDED FOR THE FOUNDATION SIZE; AREN'T THOSE | | | CALCULATIONS BASED ON THE BLOCK BEARING ON THE CENTER | | | OF THE FOUNDATION? PLEASE PROVIDE MORE INFORMATION | | | REGARDING HOW THIS CHANGE IN DESIGN WILL AFFECT THE | | | STRUCTURAL INTEGRITY. THIS MAY BE ACCOMPLISHED IN PART | | | BY TELEPHONING ROBERT BROWN, ASSISTANT BUILDING | | | OFFICIAL, 561-805-6652. | | | | | | 3. ONE COMMENT FROM THE HOUSE (09020075) PLAN REVIEW | | | WAS NOT ADDRESSED: | | | | | | PROVIDE FOUNDATION VENTING SPECIFICATION FBC R408.1. | | | | | | THE HYDROVENT CALCULATIONS WERE PROVIDED, BUT UNDER | | | FLOOR VENTILATION WAS NOT ADDRESSED. THE PLAN PROVIDED | | | DOES NOT SHOW DIMENSIONED LOCATIONS AND, WHEN SCALED, | | | DO NOT COMPLY WITH FBC R408.1. PLEASE CLARIFY LOCATION | | | FOR VENTILATION IN THE REVISED LETTER. | | | | | | | | | . |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-03-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-03-03 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-03-03 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2009-03-03 15:28:25 | REVISED SURVEY SHOWING FLOOD ZONE LINE | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-01-29 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-01-29 |
Time |
17:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-01-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-01-27 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-01-27 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2009-01-27 16:35:34 | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY BEFORE | | | A PERMIT TO CONSTRUCT CAN BE ISSUED. 561-233-5025. | | | | | | PLEASE ADVISE WHEN PLANS ARE RESUBMITTED. THE PLANS ARE | | | TO BE STAMPED BY PALM BEACH COUNTY AND THE RECEIPT | | | INCLUDED IN THE RESUBMITTAL. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-12-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-12-18 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-12-18 |
Time |
09:46 |
Sent To |
E |
|
| Notes |
| 2008-12-18 10:27:43 | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY BEFORE | | | A PERMIT TO CONSTRUCT CAN BE ISSUED. 561-233-5025. | | | | | | 2. GOVERNING CODE IS TO INCLUDE 2007 | | | REVISONS/SUPPLEMENTS. PLEASE REVISE PLAN. | | | | | | 3. MAXIMUM RISER HEIGHT IS TO BE 7 3/4", FBC R311.5.3. | | | PLEASE REVISE SECTION D-D AND ANY OTHER AFFECTED | | | DETAILS. | | | | | | 4. TREAD DIMENSION IS TO COMPLY WITH FBC R311.5.3.2. | | | PLEASE REVISE SECTION D-D AND ANY OTHER AFFECTED | | | DETAILS. | | | | | | 5. SEE FBC312.2, GUARDS WHEN PROVIDED ARE TO REJECT A | | | 4" OBJECT. PLANS SPECIFY "4" MINIMUM", THIS DOES NOT | | | COMPLY (4 INCHES OR LARGER). THIS MUST BE LESS THAN 4" | | | TO REJECT A 4" OBJECT. PLEASE REVISE. | | | | | | 6. ISOMETRIC DETAIL, PLEASE CLARIFY, ARE THE BUILDING | | | DETAILS SHOWN A PART OF THE MODULAR HOME? NOTHING ON | | | THE DETAIL STATES THAT; PLEASE REVISE. THIS DETAIL | | | SHOWING WALL CONSTRUCTION IS IN CONFLICT WITH OTHER | | | DETAILS ON THE PLAN AND THE APPLICAITON WHICH INDICATES | | | THAT A MODULAR HOME WILL BE INSTALLED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-01-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-01-23 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-01-23 |
Time |
12:34 |
Sent To |
B |
|
| Notes |
| 2009-01-23 12:44:41 | | | | | | | | | | PROVISO | | | | | | ELECTRICAL PERMIT REQUIRED TO INSTALL THE GROUNDING | | | ELECTRODE CONDUCTOR |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-12-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-12-18 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-12-18 |
Time |
15:35 |
Sent To |
PC |
|
| Notes |
| 2008-12-18 15:51:07 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | REQUIREMENT FOR THE GROUNDING ELECTRODE SYSTEM: | | | | | | 250.52(A)(3) CONCRETE-ENCASED ELECTRODE -AN ELECTRODE | | | ENCASED BY AT LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED | | | WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR | | | FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH, | | | CONSISTING OF AT LEAST 6.0 M (20 FT) OF ONE OR MORE | | | BARE OR ZINC GALVANIZED OR OTHER ELECTRICALLY | | | CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS OF NOT | | | LESS THAN 13 MM ( 1/ 2 IN.) IN DIAMETER, OR CONSISTING | | | OF AT LEAST 6.0 M (20 FT) OF BARE COPPER CONDUCTOR NOT | | | SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED | | | TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR | | | OTHER EFFECTIVE MEANS. | | | | | | GIVEN THAT THE FOOTER MAY BE POURED WITHOUT THE | | | ELECTRICAL CONTRACTORS KNOWLEDGE, THIS GROUNDING | | | ELECTRODE CONDUCTOR, INSTALLED AND SIZED PER 250.66, | | | MUST BE INSTALLED AT THIS STAGE OF THE WORK. INDICATE | | | SIZE AND LOCATION ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-03-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-03-31 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-03-31 |
Time |
11:51 |
Sent To |
B |
|
| Notes |
| 2009-03-31 11:52:26 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-01-29 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-01-29 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-01-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-21 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-21 |
Time |
10:41 |
Sent To |
E |
|
| Notes |
| 2009-01-21 10:41:27 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-12-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-16 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-16 |
Time |
10:23 |
Sent To |
B |
|
| Notes |
| 2008-12-16 10:27:29 | TO "MISC" BOX#2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-12-18 |
Time |
15:56 |
Rev Time |
|
| Received By |
btrobaug |
Date |
2008-12-10 |
Time |
16:34 |
Sent To |
PC |
|
| Notes |
| 2008-12-10 16:35:00 | TO "Z" BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2008-12-15 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-12-15 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-12-15 |
Time |
10:26 |