Plan Review Details - Permit 08120208
Plan Review Stops For Permit 08120208
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-05-06 Cont ID  
Sent By shill Date 2009-05-06 Time 10:23 Rev Time 0.00
Received By shill Date 2009-05-06 Time 10:23 Sent To  
Notes
2009-05-06 10:23:43LETTER OK PER RB - LETTER PUT ON FILE (NOTHING GIVEN
 BACK TO CONTRACTOR AS ONLY 1 LETTER SUBMITTED)

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2009-05-01 Cont ID  
Sent By shill Date 2009-05-01 Time 16:00 Rev Time 0.00
Received By shill Date 2009-05-01 Time 16:00 Sent To  
Notes
2009-05-01 16:22:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. LETTER STATES THAT THAT BLOCK MAY PROTRUDE A MINIMUM
 OF 1"; PLEASE REVISE TO STATE "MAXIMUM" OR EXPLAIN
 RATIONALE.
  
 2. PLEASE PROVIDE JUSTIFICATION FOR THE STATEMENT THAT
 THIS IS "WITHOUT STRUCTURAL COMPROMISE." CALCULATIONS
 WERE PROVIDED FOR THE FOUNDATION SIZE; AREN'T THOSE
 CALCULATIONS BASED ON THE BLOCK BEARING ON THE CENTER
 OF THE FOUNDATION? PLEASE PROVIDE MORE INFORMATION
 REGARDING HOW THIS CHANGE IN DESIGN WILL AFFECT THE
 STRUCTURAL INTEGRITY. THIS MAY BE ACCOMPLISHED IN PART
 BY TELEPHONING ROBERT BROWN, ASSISTANT BUILDING
 OFFICIAL, 561-805-6652.
  
 3. ONE COMMENT FROM THE HOUSE (09020075) PLAN REVIEW
 WAS NOT ADDRESSED:
  
 PROVIDE FOUNDATION VENTING SPECIFICATION FBC R408.1.
  
 THE HYDROVENT CALCULATIONS WERE PROVIDED, BUT UNDER
 FLOOR VENTILATION WAS NOT ADDRESSED. THE PLAN PROVIDED
 DOES NOT SHOW DIMENSIONED LOCATIONS AND, WHEN SCALED,
 DO NOT COMPLY WITH FBC R408.1. PLEASE CLARIFY LOCATION
 FOR VENTILATION IN THE REVISED LETTER.
  
  
 .

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-03-03 Cont ID  
Sent By shill Date 2009-03-03 Time 15:28 Rev Time 0.00
Received By shill Date 2009-03-03 Time 15:28 Sent To  
Notes
2009-03-03 15:28:25REVISED SURVEY SHOWING FLOOD ZONE LINE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-01-29 Cont ID  
Sent By shill Date 2009-01-29 Time 17:12 Rev Time 0.00
Received By shill Date 2009-01-29 Time 17:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-27 Cont ID  
Sent By shill Date 2009-01-27 Time 16:34 Rev Time 0.00
Received By shill Date 2009-01-27 Time 16:34 Sent To  
Notes
2009-01-27 16:35:34SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY BEFORE
 A PERMIT TO CONSTRUCT CAN BE ISSUED. 561-233-5025.
  
 PLEASE ADVISE WHEN PLANS ARE RESUBMITTED. THE PLANS ARE
 TO BE STAMPED BY PALM BEACH COUNTY AND THE RECEIPT
 INCLUDED IN THE RESUBMITTAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-18 Cont ID  
Sent By btrobaug Date 2008-12-18 Time 15:51 Rev Time 0.00
Received By shill Date 2008-12-18 Time 09:46 Sent To E
Notes
2008-12-18 10:27:43SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY BEFORE
 A PERMIT TO CONSTRUCT CAN BE ISSUED. 561-233-5025.
  
 2. GOVERNING CODE IS TO INCLUDE 2007
 REVISONS/SUPPLEMENTS. PLEASE REVISE PLAN.
  
 3. MAXIMUM RISER HEIGHT IS TO BE 7 3/4", FBC R311.5.3.
 PLEASE REVISE SECTION D-D AND ANY OTHER AFFECTED
 DETAILS.
  
 4. TREAD DIMENSION IS TO COMPLY WITH FBC R311.5.3.2.
 PLEASE REVISE SECTION D-D AND ANY OTHER AFFECTED
 DETAILS.
  
 5. SEE FBC312.2, GUARDS WHEN PROVIDED ARE TO REJECT A
 4" OBJECT. PLANS SPECIFY "4" MINIMUM", THIS DOES NOT
 COMPLY (4 INCHES OR LARGER). THIS MUST BE LESS THAN 4"
 TO REJECT A 4" OBJECT. PLEASE REVISE.
  
 6. ISOMETRIC DETAIL, PLEASE CLARIFY, ARE THE BUILDING
 DETAILS SHOWN A PART OF THE MODULAR HOME? NOTHING ON
 THE DETAIL STATES THAT; PLEASE REVISE. THIS DETAIL
 SHOWING WALL CONSTRUCTION IS IN CONFLICT WITH OTHER
 DETAILS ON THE PLAN AND THE APPLICAITON WHICH INDICATES
 THAT A MODULAR HOME WILL BE INSTALLED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-01-23 Cont ID  
Sent By btrobaug Date 2009-01-23 Time 12:42 Rev Time 0.00
Received By btrobaug Date 2009-01-23 Time 12:34 Sent To B
Notes
2009-01-23 12:44:41 
  
  
 PROVISO
  
 ELECTRICAL PERMIT REQUIRED TO INSTALL THE GROUNDING
 ELECTRODE CONDUCTOR

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-18 Cont ID  
Sent By btrobaug Date 2008-12-18 Time 15:51 Rev Time 0.00
Received By btrobaug Date 2008-12-18 Time 15:35 Sent To PC
Notes
2008-12-18 15:51:07 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 REQUIREMENT FOR THE GROUNDING ELECTRODE SYSTEM:
  
 250.52(A)(3) CONCRETE-ENCASED ELECTRODE -AN ELECTRODE
 ENCASED BY AT LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED
 WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR
 FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH,
 CONSISTING OF AT LEAST 6.0 M (20 FT) OF ONE OR MORE
 BARE OR ZINC GALVANIZED OR OTHER ELECTRICALLY
 CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS OF NOT
 LESS THAN 13 MM ( 1/ 2 IN.) IN DIAMETER, OR CONSISTING
 OF AT LEAST 6.0 M (20 FT) OF BARE COPPER CONDUCTOR NOT
 SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED
 TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR
 OTHER EFFECTIVE MEANS.
  
 GIVEN THAT THE FOOTER MAY BE POURED WITHOUT THE
 ELECTRICAL CONTRACTORS KNOWLEDGE, THIS GROUNDING
 ELECTRODE CONDUCTOR, INSTALLED AND SIZED PER 250.66,
 MUST BE INSTALLED AT THIS STAGE OF THE WORK. INDICATE
 SIZE AND LOCATION ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-03-31 Cont ID  
Sent By adarroug Date 2009-03-31 Time 11:51 Rev Time 0.00
Received By adarroug Date 2009-03-31 Time 11:51 Sent To B
Notes
2009-03-31 11:52:26TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-29 Cont ID  
Sent By shill Date 2009-01-29 Time 09:02 Rev Time 0.00
Received By shill Date 2009-01-29 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-21 Cont ID  
Sent By adarroug Date 2009-01-21 Time 10:41 Rev Time 0.00
Received By adarroug Date 2009-01-21 Time 10:41 Sent To E
Notes
2009-01-21 10:41:27TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-16 Cont ID  
Sent By adarroug Date 2008-12-16 Time 10:23 Rev Time 0.00
Received By adarroug Date 2008-12-16 Time 10:23 Sent To B
Notes
2008-12-16 10:27:29TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-18 Cont ID  
Sent By shill Date 2008-12-18 Time 15:56 Rev Time  
Received By btrobaug Date 2008-12-10 Time 16:34 Sent To PC
Notes
2008-12-10 16:35:00TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2008-12-15 Cont ID  
Sent By kdfreema Date 2008-12-15 Time 10:26 Rev Time 0.00
Received By kdfreema Date 2008-12-15 Time 10:26 Sent To  
Notes
2008-12-15 10:31:17NOTE THAT A LANDSCAPE PLAN MUST BE PROVIDED WITH THE
 STRUCTURE PERMIT SHOWING HOW THE REQUIREMENTS OF SEC.
 94-442(B)(2)(A) ARE MET. PLEASE CONTACT ROBERT KUSSNER,
 LANDSCAPE PLANNER, AT 561-822-1435 WITH QUESTIONS.