Plan Review Details - Permit 08120196
Plan Review Stops For Permit 08120196
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-01-15 Cont ID  
Sent By mjacobs Date 2009-01-15 Time 13:58 Rev Time 0.00
Received By mjacobs Date 2009-01-15 Time 13:58 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-12 Cont ID  
Sent By mjacobs Date 2009-01-12 Time 14:22 Rev Time 0.00
Received By mjacobs Date 2009-01-12 Time 14:22 Sent To  
Notes
2009-01-12 14:22:02BUILDING PLAN REVIEW
 PERMIT: 08120196
 ADD: 550 SOUTH ROSEMARY AVE #249
 CONT: JIMERICO CONSTRUCTION INC.
 TEL: (954)467-2888
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1-12-09
 REVIEW: 2ND
 ACTION: DENIED
  
 1) OK
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) OK
  
 4) OK
  
 5) OK.
  
 **THE SAME SHEETS WERE SUBMITTED WITHOUT THE INITIALS**
 6) THE CITY PLACE APPROVAL STAMP SHALL BE INITIAL BE
 THE PERSON WHO STAMP THE PLANS. EACH PAGE IS MISSING
 THE INITIAL ON THE STAMP.
  
 7) OK
  
 NEW: ONE SET OF THE DRAWINGS IS MISSING THE ARCHITECT
 SEAL, DATE AND SIGNATURE ON SHEET A0-0.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561)805-6676
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-15 Cont ID  
Sent By mjacobs Date 2008-12-15 Time 09:26 Rev Time 0.00
Received By mjacobs Date 2008-12-15 Time 09:26 Sent To  
Notes
2008-12-15 09:26:26 
 BUILDING PLAN REVIEW
 PERMIT: 08120196
 ADD: 550 SOUTH ROSEMARY AVE #249
 CONT: JIMERICO CONSTRUCTION INC.
 TEL: (954)467-2888
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12-15-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE INDICATED ON THE PLANS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. STATE THE LEVEL OF ALTERATION ON THE
 DRAWINGS IN ACCORDANCE WITH THIS SECTION OF THE CODE.
  
 5) PROVIDE A LETTER FROM A STRUCTURAL ENGINEER STATING
 THE EXISTING STRUCTURE WILL NOT BE AFFECTED BY THE
 WEIGHT OF THE NEW CONCRETE FLOOR. THE LETTER SHALL
 INCLUDE THE SQUARE FOOTAGE AND THICKNESS OF THE NEW
 CONCRETE FLOOR; THE PLANS FAIL TO INDICATE THIS
 INFORMATION. THE LETTER SHALL ALSO MEET THE
 REQUIREMENTS OF THE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002.
  
 6) THE CITY PLACE APPROVAL STAMP SHALL BE INITIAL BE
 THE PERSON WHO STAMP THE PLANS. EACH PAGE IS MISSING
 THE INITIAL ON THE STAMP.
  
 7) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561)805-6676
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-01-08 Cont ID  
Sent By btrobaug Date 2009-01-08 Time 13:17 Rev Time 0.00
Received By btrobaug Date 2009-01-08 Time 13:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-16 Cont ID  
Sent By btrobaug Date 2008-12-16 Time 14:32 Rev Time 0.00
Received By btrobaug Date 2008-12-16 Time 14:03 Sent To  
Notes
2008-12-16 14:19:18 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE. PUT A NOTE ON THE PLAN FOR CLARITY IN THE
 FIELD. SHEET E0.1
  
 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.SEE SHEET AO-O REFERENCING 1997 STANDARD
 BUILDING CODE.
  
 3} ALL WORK DONE AT CITY PLACE REQUIRES THE PRE
 APPROVAL OF THE MANAGEMENT OFFICE AND ALTHOUGH THE
 STAMP IS ON THE PLANS, IT NEEDS TO BE INITIALED BY THE
 MANAGEMENT PER RAY KEATS.
  
 NOTE: PER 105.1 FBC AN ELECTRIC PERMIT IS REQUIRED FOR
 REMOVING AND TO SAFE OFF ALL CIRCUITS THAT MUST BE
 REMOVED FOR DEMOLITION.NO ELECTRICAL CONTRACTOR IS
 SIGNED ON THE APPLICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-13 Cont ID  
Sent By mwennerg Date 2009-01-13 Time 15:41 Rev Time 0.00
Received By mwennerg Date 2009-01-13 Time 15:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-23 Cont ID  
Sent By mwennerg Date 2008-12-23 Time 11:15 Rev Time 0.00
Received By mwennerg Date 2008-12-23 Time 11:15 Sent To  
Notes
2008-12-23 11:19:02***DENIED***
  
 1) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 2) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003.
  
 3) PLEASE CORRELATE ADDRESS INFORMATION TO REFLECT THE
 CORRECT SUITE NUMBER ON THE PLANS AND PERMIT
 APPLICATION.
  
 4) CITY PLACE STAMP IS REQUIRED TO BE INITIALED BY THE
 INDIVIDUAL APPLYING EACH STAMP.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-15 Cont ID  
Sent By mjacobs Date 2009-01-15 Time 14:04 Rev Time 0.00
Received By mjacobs Date 2009-01-15 Time 14:04 Sent To B
Notes
2009-01-15 14:09:45PLANS NEEDED THE INITIALS ON THE CITY PLACE STAMP AND
 THE SEAL AND SIGNATURE OF THE ARCHITECT ON ONE SHEET.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-06 Cont ID  
Sent By adarroug Date 2009-01-06 Time 13:13 Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 13:13 Sent To  
Notes
2009-01-06 13:16:42TO "BOB"#17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-24 Cont ID  
Sent By kstevens Date 2008-12-24 Time 09:33 Rev Time 0.00
Received By kstevens Date 2008-12-10 Time 16:16 Sent To  
Notes
2008-12-10 16:19:48TO "BOB"#6

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-01-09 Cont ID  
Sent By kstevens Date 2009-01-09 Time 16:04 Rev Time 0.00
Received By kstevens Date 2009-01-09 Time 15:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-24 Cont ID  
Sent By kstevens Date 2008-12-24 Time 09:33 Rev Time 0.00
Received By kstevens Date 2008-12-24 Time 09:33 Sent To  
Notes
2008-12-24 09:39:37DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 EXISTING
  
 1. SHT AO-O BUILLDING CODES INDICATED AS 1997 STANDARD
 BUILDING CODE. CODE CRITERIA SHALL BE FBC-2004 WITH
 2007 REVISIONS.
  
 2. INDICATE LEVEL OF ALTERATION PER CHAPTER 3 OF THE
 EXISTING BUILDING CODE.
  
 3. CITY PLACE APPROVAL NOT COMPLETE FOR EACH SHEET.
 (NOT INITIALED).
  
 4. SHT P0.1 IDENTIFY FITTINGS AT THE TOP OF THE DROP
 FOR THE WATER LINES ON THE WATER ISOMETRIC RISER
 DIAGRAM. IF THEY ARE AIR CHAMBERS THEN THEY ARE NOT
 APPROVED AND SHALL BE DELETED. SECTION 604.9. IF THEY
 ARE WATER HAMMER ARRESTORS, THEN THEY SHALL BE
 INSTALLED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE",
 NOT IN THE CEILING. PDI-WH 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-01-15 Cont ID  
Sent By eschneid Date 2009-01-14 Time 12:54 Rev Time 0.25
Received By eschneid Date 2009-01-14 Time 12:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-18 Cont ID  
Sent By eschneid Date 2008-12-18 Time 10:54 Rev Time 0.00
Received By eschneid Date 2008-12-18 Time 10:54 Sent To I
Notes
2008-12-18 13:10:58FAILED
  
 1) THE PERMIT APPLICATION LISTS THE PROPERTY AS SUITE
 249, WHILE THE THE PLANS AND THE PRIOR PERMIT FOR THIS
 SITE SHOW SUITE 244.
  
 2) PRIOR PERMIT NO. 08060343 SHALL BE VOIDED AS THIS
 PERMIT REPLACES IT.