| 2008-12-17 12:29:02 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. INSTALLATION SCHEDULE STATES THAT DESIGN PRESSURES |
| | ARE +-120PSF, BUT ANCHOR SPACING FOR -62 HAS BEEN USED. |
| | |
| | 2. SEE SHEET 7 REGARDING SHUTTER TO GLASS SEPARATION, |
| | AND REVISE INSTALLATION SCHEDULE. |
| | |
| | 3. SPAN SHOULD CORRELATE WITH BLADE LENGTH. FOR |
| | INSTANCE, OPENING 1, 24" HEIGHT WITH A "7" FOR SPAN. |
| | PLEASE EXPLAIN HOW YOU'VE ARRIVED AT SPANS. |
| | |
| | 4. OPENING 14, CONCRETE SUBSTRATE REQUIRES 3320PSI |
| | CONCRETE, SEE SHEET 8 OF THE PRODUCT APPROVAL. PLEASE |
| | PROVIDE INFORMATION REGARDING HOW YOU'VE DETERMINED |
| | THAT THE EXISTING CONCRETE FLOOR MEETS THIS |
| | REQUIREMENT. |
| | |
| | 5. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE |
| | WITH THE ANCHOR CHARTS; IN THIS CASE, C1 THROUGH C5. |
| | |
| | 6. TWO IDENTICAL SETS OF PERMIT DOCUMENTS REQUIRED. |
| | ONLY ONE INSTALLATION SCHEDULE AND FLOOR PLAN WERE |
| | PROVIDED. |
| | |
| | 7. THE PRODUCT APPROVALS WERE SUBMITTED UNBOUND (LOOSE |
| | SHEETS). PLAN REVIEW WILL NOT FAIL FOR THIS REASON, BUT |
| | IT IS ADVISABLE TO SUBMIT DOCUMENTS BOUND IN TWO |
| | IDENTICAL COLLATED SETS. IF FOR SOME REASON THE SHEETS |
| | ARE OUT OF ORDER, AND TWO IDENTICAL SETS CANNOT BE |
| | EASILY PUT TOGETHER BY THE PLAN REVIEWER, THE |
| | CONTRACTOR WILL BE REQUIRED TO RESUBMIT WITH DOCUMENTS |
| | COLLATED. |