| 2009-01-14 17:25:48 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PLLEASE SEE INSTALLATION SCHEDULE. IN THE COLUMN FOR |
| | "SPECIFIC ANCHOR TYPE", THE CONNECTION TYPE HAS BEEN |
| | WRITTEN (C2). THIS INFORMATION SHOULD BE IN THE FOURTH |
| | COLUMN, AND THIS COLUMN SHOULD SPECIFY THE SPECIFIC |
| | ANCHOR TYPE; IN THIS CASE, TAPCONS. |
| | |
| | 2. WHEN SPECIFYING TAPCONS, IF THE PRODUCT APPROVAL |
| | PROVIDES MORE THAN ONE CHOICE, PLEASE SPECIFY WHICH |
| | TYPE OF TAPCON. THE PRODUCT APPROVAL FOR ACCORDIONS |
| | INCLUDES BOTH ITW AND ELCO TAPCON. |
| | |
| | 3. 1 3/4" TAPCON SPECIFIED; PLEASE NOTE THAT THIS IS |
| | THE EMBEDMENT REQUIREMENT. A LONGER TAPCON MUST BE |
| | SPECIFIED DUE TO STUCCO AND OTHER FACTORS SUCH AS TRACK |
| | OR PANEL THICKNESS. |
| | |
| | 4. SEE SHEET 6 OF THE ACCORDION PRODUCT APPROVAL. |
| | SEVERAL NUMBERS CIRCLED, MOST WHICH DO NOT APPLY TO |
| | THIS JOB. ALSO SEE SHEET3; BUILDOUT DETAIL CIRCLED BUT |
| | THIS IS NOT SPECIFIED ON THE INSTALLATION SCHEDULE. IF |
| | DETAILS ON THE PRODUCT APPROVAL ARE CIRCLED, THIS |
| | ASSISTS WITH BOTH PLAN REVIEW AND INSPECTIONS BUT |
| | SHOULD CORRELATE WITH THE INSTALLATION SCHEDULE AND THE |
| | JOB. |
| | |
| | 5. CONCRETE SUBSTRATE SPECIFIED. SEE SHEET 6 OF THE |
| | ACCORDION PRODUCT APPROVAL. FOR THE ELCO TAPCON, |
| | 3320PSI MINIMUM CONCRETE STRENGTH REQUIRED. IF USING |
| | THE ANCHOR SPACING FOR A CONCRETE SUBSTRATE, CONTRACTOR |
| | IS TO PROVIDE EVIDENCE THAT THE SUBSTRATE MEETS THIS |
| | REQUIREMENT. ALTERNATIVELY, THE CONTRACTOR CAN USE THE |
| | HOLLOW BLOCK CHART ANCHOR SPACING ON SHEET 7. |
| | |
| | 6. CONTRACTOR HAS SPECIFIED ANCHOR SPACING WHICH |
| | EXCEEDED THE REQUIREMENTS FOR BOTH CONCRETE AND HOLLOW |
| | BLOCK FOR BOTH TYPES OF TAPCONS. THEREFORE, THE PLAN |
| | WILL BE REDLINED FOR ITEM #3. |