Plan Review Details - Permit 08120164
Plan Review Stops For Permit 08120164
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-17 Cont ID  
Sent By shill Date 2008-12-17 Time 14:46 Rev Time 0.00
Received By shill Date 2008-12-17 Time 14:46 Sent To  
Notes
2008-12-17 14:57:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. EITHER STRUCTURAL DRAWINGS OR DCA APPROVAL REQUIRED
 FOR THE SHED TO SHOW COMPLIANCE WITH WIND RESISTANCE
 REQUIREMENTS, FBC R301. A DCA APPROVAL MAY BE AVAILABLE
 AT WWW.FLORIDABUILDING.ORG, MANUFACTURED BUILDINGS.
  
 2. PROVIDE A SITE PLAN SHOWING PROPOSED SHED LOCATION,
 INCLUDING DISTANCE TO ALL PROPERTY LINES AND EXISTING
 STRUCTURE.
  
 3. PROVIDE STRUCTURAL DRAWINGS FOR THE SHED ANCHORING.
 THIS MUST SHOW COMPLIANCE WITH FBC2004 WITH 2007
 REVISIONS/AMENDMENTS AND WIND REQUIREMENTS OF FBC R301.
  
 4. PROVIDE A REASONABLE VALUE FOR THIS JOB.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2008-12-16 Cont ID  
Sent By btrobaug Date 2008-12-16 Time 08:47 Rev Time 0.00
Received By btrobaug Date 2008-12-16 Time 08:40 Sent To B
Notes
2008-12-16 08:47:36 
  
  
 PROVISO
  
 IF ELECTRIC IS TO BE RAN TO THE SHED AN ELECTRICAL
 PERMIT IS REQUIRED WITH PLANS PER 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-17 Cont ID  
Sent By shill Date 2008-12-17 Time 14:57 Rev Time 0.00
Received By shill Date 2008-12-09 Time 09:13 Sent To  
Notes
2008-12-09 09:15:26TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-12 Cont ID  
Sent By mcruz Date 2008-12-12 Time 11:13 Rev Time 0.00
Received By mcruz Date 2008-12-12 Time 11:00 Sent To I
Notes
2008-12-12 11:13:31PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION
 (ONLY ONE COPY WAS SUBMITTED).
  
 3. INDICATE SETBACK DIMENSIONS FROM THE PROPOSED SHED
 TO ALL ADJACENT PROPERTY LINES. NOTE: PURSUANT TO THE
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-304: ACCESSORY STRUCTURE
 SETBACK ARE AS FOLLOWS:
 --FRONT: 25 FEET
 --SIDE: FIVE FEET FROM LOT LINES.
 --CORNER: SAME AS REQUIRED FOR PRINCIPAL STRUCTURE.
 --REAR: FIVE FEET MINIMUM OR 15 FEET FROM THE
 CENTERLINE OF THE ALLEY TO A GARAGE FACING THE ALLEY,
 WHICHEVER IS GREATER.
  
 4. INDICATE THE SEPARATION DISTANCE OF THE PROPOSED
 SHED TO THE PRINCIPAL STRUCTURE. NOTE: PURSUANT TO
 SECTION 94-304(B)(3) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), ACCESSORY STRUCTURES SHALL BE
 LOCATED NO CLOSER THAN SIX (6) FEET TO THE PRINCIPAL
 STRUCTURE.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  