Plan Review Details - Permit 08120136
Plan Review Stops For Permit 08120136
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-03-05 Cont ID  
Sent By jgomez Date 2009-03-04 Time 16:47 Rev Time 0.00
Received By jgomez Date 2009-03-04 Time 14:21 Sent To M
Notes
2009-03-04 17:01:13BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE INFO.
 PRIOR TO INSPECTIONS TO AVOID CONFLICTS OR DELAYS):
  
 1- SPECIFY ATTIC SIZE AND LOCATION TO VERIFY COMPLIANCE
 WITH SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 2- ROOFING CONTRACTOR TO PROVIDE 2 COPIES OF PRODUCT
 APPROVALS WHEN APPLYING FOR PERMIT FOR ROOF TILE AND
 ADHESIVE. DESIGNER OF RECORD TO REVIEW AND APPROVE IT
 IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 ( NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS,
 INCLUDING THE SHUTTERS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 4- SHEET 3:
 A) DESIGN LOADS: SPECIFY THE ATTIC LIVE LOAD AS
 REQUIRED BY TABLE R301.5 2004 FL. RESIDENTIAL CODE.
  
 B) ROOF SHEATHING NAILING SPACING ON SCHEDULE TO MATCH
 INFORMATION ON ADJACENT ROOF DIAGRAM FOR ZONE 2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-30 Cont ID  
Sent By jgomez Date 2008-12-30 Time 16:00 Rev Time 0.00
Received By jgomez Date 2008-12-30 Time 16:00 Sent To PC
Notes
2008-12-30 16:04:59RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPTS IF FEES
 ARE DUE.
  
 3- SPECIFY ATTIC SIZE AND LOCATION TO VERIFY COMPLIANCE
 WITH SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF TILE.
  
 B) ADHESIVE TO BE USED FOR ROOF TILE. SEE ROOF TILE
 PRODUCT APPROVAL FOR TYPE OF ADHESIVE TO BE USED.
  
 5- A) ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING ( NOT SIGNING AND SEALING) ALL PRODUCT
 APPROVALS, INCLUDING THE SHUTTERS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 B) ARCHITECT SIGNED AND SEALED SOME PRODUCT APPROVALS.
 THIS IS NOT ALLOWED BECAUSE PRODUCT APPROVAL ARE NOT
 DESIGNED BY HIM. RE-SUBMIT PRODUCT APPROVALS WITH
 ARCHITECT'S APPROVAL IN WRITING. EG: TYPICAL SHOP
 DRAWINGS REVIEW STAMP MAY BE USED.
  
 6- OWES $ 0.76 FOR RADON FEES.
  
 7- SPECIFY ON PLANS ROOF OVERHANG TO VERIFY COMPLIANCE
 WITH TABLE 6C-2 OF ENERGY CALCULATIONS SUBMITTED.
  
 8- ENERGY CALCULATIONS:
 A) REVISE INFORMATION ON TABLE 6C-2 TO MATCH FLOOR
 PLANS AND ELEVATIONS. THERE IS MORE THAN 16% GLASS AREA
 ON THIS ADDITION. REVISE AS REQUIRED AND COORDINATE
 WITH ITEM #7 ABOVE.
  
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 C) USE LEGIBLE FORM.
  
 9- SOIL TEST REPORT:
 A) NEEDS TO HAVE THE ENGINEER'S ORIGINAL SEAL,
 SIGNATURE AND DATE AS REQUIRED BY SEC. 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA
 STATUTE.
  
 B) SCOPE OF WORK DOESN'T MATCH FLOOR PLANS. THERE IS
 NOT 2 STORY ADDITION. REVISE AS REQUIRED.
  
 10- SURVEY TO HAVE SURVEYOR'S ORIGINAL SIGNATURE, NO
 COPY OR RUBBER STAMP AS REQUIRED BY SEC. 61G17-7.0025
 OF FLORIDA ADMINISTRATIVE CODE AND CHAPTER 472 FLORIDA
 STATUTE.
  
 11- STORM SHUTTERS INSTALLATION SCHEDULE:
 A) REVISE DESIGN PRESSURES TO MATCH DESIGN PRESSURES
 SHOWN ON PLANS. COORDINATE WITH REVISED DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT. SEE ITEM #14A
 BELOW.
  
 B) REVISE SHUTTER MOUNTING CONDITION SHOWN ON COLUMN
 #4. THESE COLUMN IS FOR MOUNTING CONDITIONS. EG: WALL
 MOUNTED, BUILT OUT, ETC. SEE SHUTTER DRAWINGS.
  
 C) SHUTTER SPAN ON COLUMN #6 IS INCORRECT. THIS COLUMN
 NEEDS TO BE COORDINATED WITH THE MIN. EDGE DISTANCE ON
 COLUMN #8.
  
 D) REVISE SUBSTRATE SPECIFIED ON COLUMN #11. TOP
 CONNECTION IS CONCRETE BECAUSE OF THE TIE BEAM OR
 PRECAST LINTEL. BOTTOM CONNECTION IS TO CONCRETE BLOCK.
 REVISE AS REQUIRED TO USE PROPER ANCHOR SPACING AS
 SHOWN ON SHEETS 6 AND 7 OF SHUTTERS DRAWINGS.
  
 E) REVISE COLUMN #7. ACCORDION SHUTTERS ARE INSTALLED
 VERTICALLY NOT HORIZONTALLY.
  
 12- SHEET 1: SITE PLAN SETBACK DIMENSIONS DON'T MATCH
 SURVEY. REVISE AS REQUIRED.
  
 13- SHEET 2: SPECIFY ROOF TRUSS CONNECTORS AT EXISTING
 WALL. SEE COMMENTS ON PLANS.
 NOTE: CONNECTORS A OR B DON'T WORK FOR EXISTING WALL.
  
 14- SHEET 3:
 A) DESIGN PRESSURES SHOWN ON DOORS AND WINDOWS OPENINGS
 DON'T CORRESPOND TO "EXPOSURE C". REVISE AS REQUIRED.
  
 B) SPECIFY FIREBLOCKING MATERIAL AND LOCATION ON WALL
 SECTION DETAIL A/3 AS REQUIRED BY SEC. R602.1.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 C) DESIGN LOADS: SPECIFY THE ATTIC LIVE LOAD AS
 REQUIRED BY TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 D) REVISE PLYWOOD SHEATHING NAILING SCHEDULE. ROOF ZONE
 REQUIRES 8D RING SHANK NAILS ALSO AS REQUIRED BY SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 E) REVISE FIGURE SHOWING THE ROOF ZONES. SEE FIGURE
 R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT
 ZONES IDENTIFICATION.
  
 F) REVISE NOTE REGARDING THE EXTERIOR GLAZED OPENINGS
 IN BUILDINGS TO COMPLY WITH 2001 FLORIDA BUILDING CODE.
 CORRECT CODE YEAR IS 2004 AND CODE THAT APPLIES TO ONE
 AND TWO FAMILY DWELLINGS IS THE 2004 FLORIDA
 RESIDENTIAL CODE. THIS NOTE IS WRITTEN ON TWO LOCATIONS
 AT BOTTOM OF BUCK DETAILS. SEE COMMENTS ON PLANS AND
 REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-03-04 Cont ID  
Sent By btrobaug Date 2009-03-04 Time 08:55 Rev Time 0.00
Received By btrobaug Date 2009-03-04 Time 08:50 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-12-08 Cont ID  
Sent By btrobaug Date 2008-12-08 Time 09:06 Rev Time 0.00
Received By btrobaug Date 2008-12-08 Time 08:56 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-02-12 Cont ID  
Sent By adarroug Date 2009-02-12 Time 15:38 Rev Time 0.00
Received By adarroug Date 2009-02-12 Time 15:38 Sent To Z
Notes
2009-02-12 15:38:56TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-12 Cont ID  
Sent By adarroug Date 2008-12-12 Time 10:41 Rev Time 0.00
Received By adarroug Date 2008-12-12 Time 10:41 Sent To M
Notes
2008-12-12 10:42:19TO "SFR" "M"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-30 Cont ID  
Sent By jgomez Date 2008-12-30 Time 16:07 Rev Time 0.00
Received By jgomez Date 2008-12-05 Time 10:57 Sent To  
Notes
2008-12-05 10:57:45TO "SFR" "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2009-03-10 Cont ID  
Sent By hmoser Date 2009-03-10 Time 14:19 Rev Time 0.00
Received By hmoser Date 2009-03-10 Time 14:09 Sent To  
Notes
2009-03-10 14:23:06TALKED TO KARI NEVILLE BY PHONE SHE SAID THEY REMOVED
 MECHANICAL FROM THE PLANS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-12-18 Cont ID  
Sent By hmoser Date 2008-12-18 Time 08:43 Rev Time 0.00
Received By hmoser Date 2008-12-18 Time 08:35 Sent To  
Notes
2008-12-18 08:50:4212/18/04
 AIR CONDITIONING CONTRACTOR MUST SUBMIT PLANS AND
 ENERGY CALCULATIONS WITH THE APPLICATION .
 PLANREVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-12-16 Cont ID  
Sent By kstevens Date 2008-12-16 Time 16:18 Rev Time 0.00
Received By kstevens Date 2008-12-16 Time 16:18 Sent To M
Notes
2008-12-16 16:18:27NO PLUMBING WORK SHOWN OR INDICATED.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-02-23 Cont ID  
Sent By mcruz Date 2009-02-23 Time 18:06 Rev Time 0.00
Received By mcruz Date 2009-02-23 Time 18:03 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-12 Cont ID  
Sent By mcruz Date 2008-12-12 Time 08:46 Rev Time 0.00
Received By mcruz Date 2008-12-12 Time 08:30 Sent To I
Notes
2008-12-12 08:45:46PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR,
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 3. THE DIMENSIONS (LEGNTH/WIDTH) OF THE ADDITION SHOWN
 ON SHEET 1 DO NOT MATCH THE THE DIMENSIONS SHOWN ON
 SHEET 2. PLEASE CORRELATE ALL PLANS.
  
 4. THE SETBACK DIMENSIONS SHOWN ON SHEET 1 DO NOT MATCH
 THE SETBACK DIMENSIONS ON THE SURVEY. PLEASE VERIFY AND
 CORRELATE.
  
 5. INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION. PURSUANT TO THE ZLDR, SECTION 94-305(B):
 OVERHANGS SHALL NOT PROJECT MORE THAN THREE (3) FEET
 INTO A REQUIRED SETBACK.
  
 6. PROVIDE THE TOTAL HEIGHT OF THE PROPOSED ADDITION ON
 THE ELEVATION PLAN (SHEET 3). PURSUANT TO THE ZLDR,
 SECTION 94-611, THE HEIGHT SHALL BE MEASURED AS THE
 VERTICAL DISTANCE FROM THE AVERAGE ELEVATION OF THE
 FINISHED GRADE OF THE BUILDING TO THE MEAN HEIGHT LEVEL
 BETWEEN EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL
 ROOFS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  