| 2008-12-15 09:36:00 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - THE CUT SECTIONS FROM THE METER TO THE |
| | FIRST TEE SERVING THE APPLIANCES IN THE HOUSE AND THE |
| | SECTION FROM THE TEE TO THE DROP FOR THE GENERATOR ARE |
| | NOT INDICATED ON THE PLANS. ALSO THE RISERS FROM THE PE |
| | PIPE TO THE GENERATOR AND TO THE GRILL ARE INDICATED AS |
| | 1 FOOT. PER SECTION 404.9 THE MINIMUM BURIAL DEPTH |
| | REQUIRED IS 12 INCHES. THAT WOULD MAKE THE GRILL SHUT |
| | OFF VALVE AND THE GENERATOR SHUT OFF VALVE AT GROUND |
| | LEVEL. PLEASE CLARIFY AND SHOW ALL CUT SECTION LENGTHS |
| | AS THEY WILL BE INSTALLED. |
| | ****NEW RISER DIAGRAM SUBMITTED. THE NEW RISER DIAGRAM |
| | STILL DOES NOT SHOW THE LENGTH OF PIPE FROM THE SECOND |
| | TEE FROM THE METER TO THE DROP TO THE HOUSE. IS THE |
| | FIRST TEE ON THE METER AS SHOWN? ALSO THE COMMENT |
| | CONCERNING THE RISERS FROM THE PE PIPE TO THE |
| | GENERATOR, GRILL AND NOW THE POOL HEATER HAS NOT BEEN |
| | ADDRESSED. PLEASE CLARIFY. |
| | |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | |
| | 5. PER SECTION 409.4 A SHUT OFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF THE REGULATORS. ALSO A |
| | UNION IS REQUIRED BY ALL REGULATORS THAT ARE NOT AT THE |
| | APPLIANCE SUCH AS THE HOUSE REGULATOR. PLEASE INDICATE |
| | ON RISER DIAGRAM. |
| | ****SHUT OFF VALVES ARE SHOWN DOWNSTREAM OF THE |
| | REGULATORS. THE SHUT OFF VALVE SHALL BE INSTALLED |
| | UPSTREAM OF THE REGULATORS. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. REGULATORS INDICATED FOR THE TANKLESS WATER HEATER, |
| | POOL HEATER & GENERATOR, MAXITROL 325-3 ARE ONLY |
| | INDICATED FOR MAXIMUM INDIVUAL LOAD AT 140,000 BTU. THE |
| | GAS FIXTURES EXCEED THE MAXIMUM. PLEASE INDICATE |
| | REGULATORS THAT COMPLY SUCH AS THE MAXITROL 325-5AL. |
| | |
| | 2B. THE TOTAL DEVELOPED LENGTH IS INDICATED AS 35 FEET, |
| | BUT THIS DOES NOT CORRELATE WITH THE CUT LENGTHS |
| | INDICATED ON THE RISER DIAGRAM AND COMMENT #1 WHEN |
| | CLARIFIED. PLEASE INDICATED THE DISTANCE FROM THE METER |
| | TO THE MOST REMOTE OUTLET. FUEL GAS APPENDIX A-USE OF |
| | CAPACITY TABLES A.3.1(4). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |