| 2008-12-09 10:41:06 | BUILDING PLAN REVIEW |
| | PERMIT: 08120078 |
| | ADD: 1501 S. FLAGLER DR. 2E |
| | CONT: POTTSWORKS CONSTRUCTION LLC |
| | TEL: (561)584-2563 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION |
| | SHALL BE SHOWN ON THE PLANS. |
| | |
| | 3) 106.1.3* BUILDING PLANS SHALL BE DRAWN TO A MINIMUM |
| | 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, OR OTHER |
| | ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH |
| | THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. SUBMIT |
| | DRAFTSMAN QUALITY PLANS SHOWING THE PROPOSED WORK IN |
| | DETAIL. |
| | |
| | 4) THE PLANS SHALL INDICATE THE TYPE OF CONSTRUCTION IN |
| | ACCORDANCE WITH CHAPTER 6 AND TABLE 601 AND THE USE AND |
| | OCCUPANCY PER CHAPTER 3 AND TABLE 503. AN EXISTING |
| | FLOOR PLAN AND A PROPOSED FLOOR PLAN SHALL BE SUBMITTED |
| | TO SHOW ALL CHANGES. THE PLANS SHALL INCLUDE DETAIL |
| | ELEVATION DRAWINGS OF THE NEW SOFFIT WITH THE OPENINGS |
| | FOR THE AC DUCTS. |
| | |
| | 5) IF THE BUILDING IS EQUIPPED WITH A FIRE SPRINKLER |
| | SYSTEM, SHOW HOW THE NEW CONSTRUCTION WILL AFFECT THE |
| | LOCATION ON THE EXISTING SPRINKLER HEADS FBC |
| | 106.3.5.1.1(5)* FLORIDA STATUTES 553.79(2) |
| | |
| | 6) IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS |
| | STATE REGULATING THE PRACTICE OF ARCHITECTURE AS |
| | PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART 1, |
| | OR ENGINEERING AS PROVIDED IN CHAPTER 471, HE OR SHE |
| | SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE AND |
| | DATE TO SAID DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA. |
| | |
| | 7) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE |
| | DRAWINGS. |
| | |
| | 8) 61G15-23.002 A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, |
| | REPORTS, FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR |
| | THE OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED |
| | OR ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC |
| | RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED |
| | AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, |
| | SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. THE |
| | LETTER SUBMITTED BY THE ENGINEER IS MISSING THE |
| | INFORMATION MENTION ABOVE. |
| | |
| | 9) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 10) WILL THIS WORK BE CARRIED OUT ON EACH FLOOR AS |
| | STATED ON TWO THE SHEETS? DOES THE OVEN REALLY EXTEND |
| | INTO THE LINEN CLOSET NEXT TO THE FOYER? |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |
| | |