Plan Review Details - Permit 08120078
Plan Review Stops For Permit 08120078
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-01-20 Cont ID  
Sent By mjacobs Date 2009-01-20 Time 16:01 Rev Time 0.00
Received By mjacobs Date 2009-01-20 Time 16:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-06 Cont ID  
Sent By mjacobs Date 2009-01-06 Time 09:28 Rev Time 0.00
Received By mjacobs Date 2009-01-06 Time 09:28 Sent To  
Notes
2009-01-06 09:21:30BUILDING PLAN REVIEW
 PERMIT: 08120078
 ADD: 1501 S. FLAGLER DR. 2E
 CONT: POTTSWORKS CONSTRUCTION LLC
 TEL: (561)584-2563
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1-6-09
 REVIEW: 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **PARTIALY ADDRESSED**
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE PLANS.
  
 3) OK
  
 **PARTIALY ADDRESSED**
 4) THE PLANS SHALL INDICATE THE TYPE OF CONSTRUCTION IN
 ACCORDANCE WITH CHAPTER 6 AND TABLE 601 AND THE USE AND
 OCCUPANCY PER CHAPTER 3 AND TABLE 503. AN EXISTING
 FLOOR PLAN AND A PROPOSED FLOOR PLAN SHALL BE SUBMITTED
 TO SHOW ALL CHANGES. THE PLANS SHALL INCLUDE DETAIL
 ELEVATION DRAWINGS OF THE NEW SOFFIT WITH THE OPENINGS
 FOR THE AC DUCTS.
  
 5) OK
 6) OK
 7) OK
 8) OK
 9) OK
  
 10) OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-09 Cont ID  
Sent By mjacobs Date 2008-12-09 Time 10:41 Rev Time 0.00
Received By mjacobs Date 2008-12-09 Time 10:41 Sent To  
Notes
2008-12-09 10:41:06BUILDING PLAN REVIEW
 PERMIT: 08120078
 ADD: 1501 S. FLAGLER DR. 2E
 CONT: POTTSWORKS CONSTRUCTION LLC
 TEL: (561)584-2563
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE PLANS.
  
 3) 106.1.3* BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. SUBMIT
 DRAFTSMAN QUALITY PLANS SHOWING THE PROPOSED WORK IN
 DETAIL.
  
 4) THE PLANS SHALL INDICATE THE TYPE OF CONSTRUCTION IN
 ACCORDANCE WITH CHAPTER 6 AND TABLE 601 AND THE USE AND
 OCCUPANCY PER CHAPTER 3 AND TABLE 503. AN EXISTING
 FLOOR PLAN AND A PROPOSED FLOOR PLAN SHALL BE SUBMITTED
 TO SHOW ALL CHANGES. THE PLANS SHALL INCLUDE DETAIL
 ELEVATION DRAWINGS OF THE NEW SOFFIT WITH THE OPENINGS
 FOR THE AC DUCTS.
  
 5) IF THE BUILDING IS EQUIPPED WITH A FIRE SPRINKLER
 SYSTEM, SHOW HOW THE NEW CONSTRUCTION WILL AFFECT THE
 LOCATION ON THE EXISTING SPRINKLER HEADS FBC
 106.3.5.1.1(5)* FLORIDA STATUTES 553.79(2)
  
 6) IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS
 STATE REGULATING THE PRACTICE OF ARCHITECTURE AS
 PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART 1,
 OR ENGINEERING AS PROVIDED IN CHAPTER 471, HE OR SHE
 SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA.
  
 7) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE
 DRAWINGS.
  
 8) 61G15-23.002 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS,
 REPORTS, FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED
 OR ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. THE
 LETTER SUBMITTED BY THE ENGINEER IS MISSING THE
 INFORMATION MENTION ABOVE.
  
 9) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 10) WILL THIS WORK BE CARRIED OUT ON EACH FLOOR AS
 STATED ON TWO THE SHEETS? DOES THE OVEN REALLY EXTEND
 INTO THE LINEN CLOSET NEXT TO THE FOYER?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-01-08 Cont ID  
Sent By btrobaug Date 2009-01-08 Time 12:12 Rev Time 0.00
Received By btrobaug Date 2009-01-08 Time 11:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-11 Cont ID  
Sent By btrobaug Date 2008-12-11 Time 11:53 Rev Time 0.00
Received By btrobaug Date 2008-12-11 Time 11:18 Sent To M
Notes
2008-12-11 11:52:53 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN.
  
 2} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED, ALL SHEETS.
  
 3} 106.1.3 RESERVED. QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. NUMBER THE
 SHEETS FOR REFERENCE, USE SYMBOLS THAT ARE NATIONALLY
 RECOGNIZED IN PLACE OF ARROWS. PUT ALL PROPOSED
 ELECTRICAL WORK ON ONE SHEET. DIFFERENTIATE BETWEEN NEW
 AND EXISTING DEVICES WHERE NECESSARY SHOW CODE
 COMPLIANCE.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 5} INCLUDE THE ADDRESS OF THE PROJECT ON THE PLANS PER
 106.1.1 FBC AS AMENDED.REMOVE THE NOTE INDICATING "EACH
 FLOOR", IF WORK IS TO BE DONE IN MORE THAN ONE UNIT,
 SEPARATE PERMITS ARE REQUIRED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-01-21 Cont ID  
Sent By mwennerg Date 2009-01-21 Time 10:49 Rev Time 0.00
Received By mwennerg Date 2009-01-21 Time 10:49 Sent To  
Notes
2009-01-21 10:50:10SENT TO L MARTINEZ

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-09 Cont ID  
Sent By mwennerg Date 2009-01-09 Time 15:08 Rev Time 0.00
Received By mwennerg Date 2009-01-09 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-11 Cont ID  
Sent By mwennerg Date 2008-12-11 Time 12:58 Rev Time 0.00
Received By mwennerg Date 2008-12-11 Time 12:58 Sent To  
Notes
2008-12-11 13:13:57***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. FBC 106.1.1.
  
 3) ILLUSTRATE THE LOCATIONS OF REQUIRED SMOKE ALARMS.
 DEVICES SHALL BE LOCATED AT LEAST 3 FEET FROM AC
 DIFFUSERS.
  
 4) WILL WORK IMPACT EXISTING FIRE PROTECTION SYSTEMS?
  
 5) IF BUILDING IS PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM, THE CONSTRUCTION OF SOFFITS SHALL NOT
 INTERFERE WITH REQUIRED SPRINKLER COVERAGE.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-04 Cont ID  
Sent By adarroug Date 2009-03-04 Time 09:26 Rev Time 0.00
Received By adarroug Date 2009-03-04 Time 09:26 Sent To M
Notes
2009-03-04 09:26:34TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-14 Cont ID  
Sent By adarroug Date 2009-01-14 Time 16:33 Rev Time 0.00
Received By adarroug Date 2009-01-14 Time 16:33 Sent To  
Notes
2009-01-14 16:33:27TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-30 Cont ID  
Sent By adarroug Date 2008-12-30 Time 14:18 Rev Time 0.00
Received By adarroug Date 2008-12-30 Time 14:18 Sent To  
Notes
2008-12-30 14:20:31TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-14 Cont ID  
Sent By rregueir Date 2008-12-14 Time 12:39 Rev Time 0.00
Received By rregueir Date 2008-12-04 Time 10:34 Sent To PC
Notes
2008-12-04 10:36:33TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-03-12 Cont ID  
Sent By rregueir Date 2009-03-12 Time 20:22 Rev Time 0.00
Received By rregueir Date 2009-03-12 Time 20:22 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-02-22 Cont ID  
Sent By rregueir Date 2009-02-22 Time 14:12 Rev Time 0.00
Received By rregueir Date 2009-02-22 Time 14:10 Sent To PC
Notes
2009-02-22 14:12:53REVISION DENIED.
  
 THE PERMIT SET OF PLANS WERE PREPARED, SIGNED AND
 SEALED BY A PROFESSIONAL ENGINEER. THE PERMIT DOCUMENTS
 CAN ONLY BE REVISED OR MODIFIED BY THE DESIGNER OF
 RECORD IN ACCORDANCE WITH FS 471. PLEASE PROVIDE
 REVISED PLANS SIGNED AND SEALED BY THE DESIGNER OF
 RECORD.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 18:28 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 18:28 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-12-14 Cont ID  
Sent By rregueir Date 2008-12-14 Time 12:23 Rev Time 0.00
Received By rregueir Date 2008-12-14 Time 12:23 Sent To PC
Notes
2008-12-14 12:32:10REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2004 CODE FAMILY W/ 200 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS AND RESUBMIT:
  
 1. THIS IS A PROPOSED ALTERATION TO AN EXISTING
 BUILDING. THE OWNER OR DESIGN PROFESSIONAL SHALL
 DECLARE A LEVEL OF ALTERATION AND DECLARE ON PLANS IN
 ACCORDANCE WITH FBCEB 301.5.
  
 2. MECHANICAL PLANS INDICATE "SUITEE" AND "EACH FLOOR."
 IS THIS WORK TO TAKE PLACE ON EACH FLOOR OF THE
 BUILDING? PLEASE INDICATE THE SPECIFIC ADDRESS LOCATION
 OF THE PROPOSED WORK ON THE PLANS IN ACCORDANCE WITH
 FBCB 106.1.1.
  
 3. MECHANICAL PLAN SHOWS WHAT APPEARS TO BE A
 RECTANGULAR DUCT IN THE HALL. IS THIS DUCT NEW,
 EXISTING, BEING MODIFIED? PLEASE CLARIFY THE SCOPE AND
 DIFFERENTIATE BETWEEN NEW AND EXISTING WORK IN
 ACCORDANCE WITH FBCB 106.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]