| 2008-12-03 11:59:58 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS |
| | PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. *THE CUT SECTION OF THE EXISTING PIPE |
| | FROM THE RANGE TO THE DRYER IS NOT INDICATED AND SINCE |
| | IT APPEARS THAT IT IS A LONGER DISTANCE THAN THE 29 |
| | FEET INDICATED FOR THE NEW PIPING THE DISTANCE SHALL BE |
| | INDICATED. |
| | |
| | 2. TYPE OF GAS, (LP OR NATURAL). *INDICATE ON PLANS. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). *TO BE VERIFIED WHEN |
| | COMMENT NUMBER ONE IS ADDRESSED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |