| 2008-11-25 15:03:10 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- PROVIDE COMPLETE INSTALLATION SCHEDULE AS REQUIRED |
| | BY CITY'S IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS |
| | IMPACT PROTECTION. SEE ATTACHED COPY. |
| | PLEASE MAKE SURE ALL INFORMATION IS PROVIDED TO AVOID |
| | UNNECESSARY DELAYS. |
| | |
| | 2- CLEARLY IDENTIFY TOP AND BOTTOM CONNECTIONS. #1 WALL |
| | MOUNTING INSTALLATION WAS HIGHLIGHTED ON SHEET 5 OF 14 |
| | OF DRAWING 06-015 SUBMITTED. |
| | NOTE: #1 ONLY APPLIES TO POURED CONCRETE APPLICATIONS |
| | ONLY. IF OPENING LINTEL IS PRECAST LINTEL OR POURED TIE |
| | BEAM, THEN THE POURED CONCRETE MOUNTING CONDITION AND |
| | THE ANCHOR SCHEDULE FOR POURED CONCRETE MAY BE USED. ON |
| | THE OTHER HAND, WINDOW SILLS ARE NOT TYPICALLY POURED |
| | CONCRETE BUT FILL CELLS. USE WALL MOUNTING CONDITIONS |
| | AND ANCHOR SCHEDULE FOR CONCRETE BLOCK INSTALLATION. |
| | OTHERWISE, PROVIDE PROOF THAT OPENING SILL IS POURED |
| | CONCRETE WITH THE REQUIRED STRENGTH AS REQUIRED TO USE |
| | THE POURED CONCRETE TABLES. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301 AND COMPLIANCE WITH |
| | PRODUCT APPROVAL. |
| | |
| | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |