Plan Review Details - Permit 08110506
Plan Review Stops For Permit 08110506
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-02-27 Cont ID  
Sent By shill Date 2009-02-27 Time 17:20 Rev Time 0.00
Received By shill Date 2009-02-27 Time 17:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-02-19 Cont ID  
Sent By shill Date 2009-02-19 Time 14:18 Rev Time 0.00
Received By shill Date 2009-02-19 Time 14:18 Sent To  
Notes
2009-02-19 14:22:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LISTS:
  
 8. AS THIS IS A THRESHOLD BUILDING, A THRESHOLD
 INSPECTOR MAY BE REQUIRED AFTER SCOPE/LOCATION OF WORK
 HAS BEEN DETERMINED.
  
 PLEASE PROVIDE A COPY OF THE THRESHOLD INSPECTOR
 AGREEMENT. THIS MUST BE APPROVED BY KEN CONRAD, CHIEF
 BUILDING INSPECTOR (561-805-6666), PRIOR TO PERMIT
 ISSUANCE.
  
 4TH REVIEW; AN AGREEMENT WAS SUBMITTED WITH THE PLAN,
 BUT KEN CONRAD INFORMED ME THAT THIS HAS NOT YET BEEN
 APPROVED BY HIM. PLEASE CONTACT KEN CONRAD, CHIEF
 BUILDING INSPECTOR TO RESOLVE THIS ISSUE. THE INSPECTOR
 MUST BE APPROVED AND APPROPRIATE PAPERWORK PROVIDED TO
 HIM. PLEASE INCLUDE A COPY OF THE APPROVED RESIDENT
 INSPECTOR AGREEMENT WHEN RESUBMITTING.
  
 IF THE AGREEMENT INCLUDED WITH THE PERMIT APPLICATION
 IS APPROVED BY KEN CONRAD, YOU MAY INFORM ME BY
 TELEPHONE SO THAT THE PERMIT CAN BE ISSUED AT THAT
 TIME.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-01-30 Cont ID  
Sent By shill Date 2009-01-30 Time 10:06 Rev Time 0.00
Received By shill Date 2009-01-30 Time 10:06 Sent To  
Notes
2009-01-30 10:06:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 8. AS THIS IS A THRESHOLD BUILDING, A THRESHOLD
 INSPECTOR MAY BE REQUIRED AFTER SCOPE/LOCATION OF WORK
 HAS BEEN DETERMINED.
  
 PLEASE PROVIDE A COPY OF THE THRESHOLD INSPECTOR
 AGREEMENT. THIS MUST BE APPROVED BY KEN CONRAD, CHIEF
 BUILDING INSPECTOR (561-805-6666), PRIOR TO PERMIT
 ISSUANCE.
  
 **NO RESUB FEE**
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-29 Cont ID  
Sent By kconrad Date 2009-01-29 Time 15:14 Rev Time 0.00
Received By kconrad Date 2009-01-29 Time 15:14 Sent To  
Notes
2009-01-29 15:17:32REQUIRE PERMIT LETTER FROM ADJACENT BANK WITH REFERENCE
 TO PROPERTY USE TO STAGE EQUIPMENT AND MATERIALS FOR
 PROPOSED REPAIR. PRE-INSPECT APPROVED AS STATED.
 REQUIRE A SIGNED THRESHOLD INSPECTOR AGREEMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-08 Cont ID  
Sent By shill Date 2008-12-08 Time 08:53 Rev Time 0.00
Received By shill Date 2008-12-08 Time 08:53 Sent To  
Notes
2008-12-08 09:27:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. A PERMIT HAS ALREADY BEEN ISSUED FOR 08030015, SAME
 ADDRESS. PLEASE EXPLAIN WHY A SEPARATE PERMIT HAS BEEN
 APPLIED FOR. IF THERE ARE TWO PERMITS FOR THE SAME
 SCOPE OF WORK, A LETTER SHOULD BE SUBMITTED REQUESTING
 THAT ONE BE VOIDED.
  
 2. THE LETTER SUBMITTED IS NOT SEALED. IN ORDER TO BE A
 PART OF THE PERMIT DOCUMENTS, THIS LETTER IS TO BE IN
 COMPLIANCE WITH FAC61G15-23, AND NEEDS TO INCLUDE AN
 IMPRESSED SEAL AS WELL AS THE CERTIFICATE OF
 AUTHORIZATION. THE LETTER IS REQUIRED OR HAVE THE
 INFORMATION INCORPORATED INTO THE SPECIFICATION.
  
 3. THE DRAWING INDEX REFERS TO TWO DETAILS, SK-1 AND
 SK-2, BUT I WAS UNABLE TO LOCATE THESE PAGES IN THE
 DOCUMENTS SUBMITTED.
  
 4. PROVIDE A TENDON LAYOUT PLAN SHOWING LOCATION OF
 REPAIR. THE SPECIFICATION STATES 4TH FLOOR. IS THIS
 LOCATED WITHIN A UNIT OR IN THE COMMON AREA?
  
 5. THE ENGINEER STATES THAT AN "EXPEDITIOUS REPAIR" IS
 RECOMMENDED, BUT THE SPECIFICATION IS DATED FEBRUARY
 15, 2008, ALMOST A YEAR AGO. IS THE STRUCTURAL
 INTEGRITY OF THE BUILDING AFFECTED?
  
 6. THE SPECIFICATION IS TO BE IN COMPLIANCE WITH
 FAC61G15-23.002. THE INDEX SHEET DOES NOT CONTAIN A
 TITLE BLOCK WITH ALL REQUIRED INFORMATION.
  
 7. PREINSPECT REQUIRED PER KEN CONRAD. THE PLANS HAVE
 BEEN ROUTED TO K. CONRAD. 561-805-6666
  
 8. AS THIS IS A THRESHOLD BUILDING, A THRESHOLD
 INSPECTOR MAY BE REQUIRED AFTER SCOPE/LOCATION OF WORK
 HAS BEEN DETERMINED.
  
 *****PLEASE CONTACT KEN CONRAD. 561-805-6666 FOR A
 PREINSPECT****
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-12 Cont ID  
Sent By adarroug Date 2009-02-12 Time 15:32 Rev Time 0.00
Received By adarroug Date 2009-02-12 Time 15:32 Sent To B
Notes
2009-02-12 15:32:45TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-22 Cont ID  
Sent By adarroug Date 2009-01-22 Time 11:38 Rev Time 0.00
Received By adarroug Date 2009-01-22 Time 11:38 Sent To B
Notes
2009-01-22 11:38:55TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-04 Cont ID  
Sent By adarroug Date 2008-12-04 Time 09:33 Rev Time 0.00
Received By adarroug Date 2008-12-04 Time 09:33 Sent To B
Notes
2008-12-04 09:34:04TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-08 Cont ID  
Sent By shill Date 2008-12-08 Time 10:50 Rev Time 0.00
Received By shill Date 2008-11-25 Time 10:33 Sent To  
Notes
2008-11-25 10:33:23TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status N Date 2008-12-03 Cont ID  
Sent By aaponte Date 2008-12-03 Time 08:26 Rev Time 0.00
Received By aaponte Date 2008-12-03 Time 08:26 Sent To  
Notes
***NONE***