| Plan Review Stops For Permit 08110501 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-02-12 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-02-12 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-12-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-12-04 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-12-04 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2008-12-04 09:03:03 | BUILDING PLAN REVIEW | | | PERMIT: 08110501 | | | ADD: 1700 PBL BLVD | | | CONT: HOLT LEE CONST. | | | TEL: (561)725-4881 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS, NOT 2006. | | | | | | 2) FLORIDA STATUTES 481.2131 | | | INTERIOR DESIGN DOCUMENTS PREPARED BY A REGISTERED | | | INTERIOR DESIGNER SHALL CONTAIN A STATEMENT THAT THE | | | DOCUMENT IS NOT AN ARCHITECTURAL OR ENGINEERING STUDY, | | | DRAWING, SPECIFICATION, OR DESIGN AND IS NOT TO BE USED | | | FOR CONSTRUCTION OF ANY LOAD-BEARING COLUMNS, | | | LOAD-BEARING FRAMING OR WALLS OF STRUCTURES, OR | | | ISSUANCE OF ANY BUILDING PERMIT, EXCEPT AS OTHERWISE | | | PROVIDED BY LAW. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-02-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-18 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-18 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2009-02-18 10:09:24 | ** PROVISO** | | | | | | ** SPOKE TO DESIGNER OF RECORD. THE FOLLOWING ITEMS | | | WILL NEED TO BE REVISED. THE DESIGNER OF RECORD STATED | | | THAT PLANS WERE GOING TO HAVE SOME CHANGES ANYWAY AND | | | WILL INCORPORATE THE REVISIONS AT THAT TIME. | | | | | | | | | 1) NOTE: THE PERFORMANCE CALCULATIONS SHOWN ON PLANS | | | SHOW A LIGHTING LEVEL WATTAGE EXCEEDING THAT PERMITTED | | | PER 13-415.2,13-415.2.B.2 | | | PLEASE SEE THE CONFERENCE ROOM WHICH IS OVER. THE | | | ADDITIONAL ALLOWANCE FOR DECRETIVE LIGHTING IS | | | PERMITTED HOWEVER FIXTURES MUST BE INSTALLED SPECIFIC | | | TO THAT PURPOSE, UNDER SEPARATE CONTROL AND SHOWN ON | | | THE CALCULATIONS UNDER ADDITIONAL ALLOWANCE. | | | 13-415.2.B.2 | | | THE NEW DESIGN TO BE SHOWN WILL NOT EXCEED ALLOWANCES. | | | | | | 2) NOTE: THE PLANS CONTAIN NOTES FOR NEW CONTROLS | | | MEETING CODE SECTIONS 13-415.1.ABC.1.1-.1.3 HOWEVER NEW | | | OFFICE NEEDS TO SHOW NEW DEVICE. | | | WENT OVER WITH DESIGNER AND HE WILL CHANGE PLANS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-12-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-18 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-18 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2008-12-18 14:15:38 | ** DENIED** | | | | | | | | | | | | 1) NOTE: NEW LIGHTING CONTROL DEVICES SHALL MEET | | | 13-415.1.ABC.1.1,.1.2 AND .1.3. AS THESE DEVICES ARE | | | NOTED AS NEW PLEASE REVIEW TO COMPLY. | | | | | | 2) NOTE: PLEASE SEE 13-415.2.ABC.1.1,.1.2, | | | 13-415.2,13-415.2.B, 13-415.2.C. | | | THE LIGHTING FIXTURE LEGEND INDICATES THE WATTAGES OF | | | THE NEW FIXTURES HOWEVER DOES NOT LIST THE EXISTING | | | WATTAGE TOTALS. IN ORDER FOR NEW FIXTURES TO BE ADDED | | | TO EXISTING SPACES THE EXISTING LIGHTING DENSITY LEVELS | | | NEED TO BE FIGURED WITH NEW. | | | | | | 3) NOTE: PLEASE REVISE CODES AS FOLLOWS AS ADOPTED PER | | | FS 553.73 | | | FBC 2004 W/2007 REVISIONS. | | | | | | IF THIS WAS THE ONLY COMMENT PLANS WOULD HAVE BEEN | | | REDLINED. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-02-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-02-18 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-02-18 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2009-02-18 14:28:27 | SENT TO L. MARTINEZ |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-12-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-16 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-16 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2008-12-16 11:08:34 | ***DENIED*** | | | | | | 1) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING. | | | | | | 2) IS THIS BUILDING PROTECTED BY AN AUTOMATIC FIRE | | | SPRINKLER SYSTEM? | | | | | | 3) PLEASE SHOW THE LOCATIONS OF REQUIRED 2A-10B,C RATED | | | FIRE EXTINGUISHERS. | | | | | | 4) FIRE RATED DOOR SCHEDULE INDICATES 3/4 HOUR RATED | | | DOORS AT THE STAIRWELLS. PLEASE INDICATE THE NUMBER OF | | | STORIES FOR THIS BUILDING AND THE RATING OF THE EXIT | | | ENCLOSURES. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-02-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-04 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-04 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2009-02-04 16:15:14 | TO "COMM" BD#24 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-12-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-25 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2008-11-25 10:29:19 | TO "COMM" BD#29 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2008-12-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-12-13 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-12-13 |
Time |
16:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2009-02-10 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2009-02-10 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2009-02-10 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|