Plan Review Details - Permit 08110494
Plan Review Stops For Permit 08110494
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-12-09 Cont ID  
Sent By kstevens Date 2008-12-09 Time 12:01 Rev Time 0.00
Received By kstevens Date 2008-12-09 Time 12:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-12-03 Cont ID  
Sent By kstevens Date 2008-12-03 Time 11:25 Rev Time 0.00
Received By kstevens Date 2008-12-03 Time 11:25 Sent To  
Notes
2008-12-03 11:30:07DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. SUBMIT THE FOLLOWING INFORMATION:
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (APPROX 29 FEET)
 ****RESPONSE NOTED, BUT DISTANCE IS INDICATED AT 19
 FEET AND CUT SECTIONS ADD UP TO 30 FEET. PLEASE
 CLAIRFY.
  
 5. OK (EXTERIOR)
 6. OK
 7. OK (INSPECTOR TO VERIFY COMPLIANCE)
 8. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-12-01 Cont ID  
Sent By kstevens Date 2008-12-01 Time 11:00 Rev Time 0.00
Received By kstevens Date 2008-12-01 Time 11:00 Sent To  
Notes
2008-12-01 11:11:11DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. SUBMIT THE FOLLOWING INFORMATION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. NOT ALL LENGHTS INDICATED.
  
 2. 3. TYPE OF GAS, (LP OR NATURAL). NOT INDICATED ON
 PLANS
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). -- INDICATE TOTAL BTU LOAD.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (APPROX 29 FEET)
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 8. PER TABLE 402.4(2) MAXIMUM 200,000 BTU ON 3/4" SCHED
 40. 210,000 INDICATED FOR WATER HEATER & GRILL. 3/4"
 SHOWN NOT APPROVED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721