Plan Review Details - Permit 08110490
Plan Review Stops For Permit 08110490
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-05-14 Cont ID  
Sent By jwitmer Date 2009-05-14 Time 11:51 Rev Time 0.77
Received By jwitmer Date 2009-05-14 Time 11:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-06 Cont ID  
Sent By mjacobs Date 2009-04-06 Time 08:34 Rev Time 0.00
Received By jwitmer Date 2009-05-14 Time 11:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-04 Cont ID  
Sent By mjacobs Date 2008-12-04 Time 16:37 Rev Time 0.00
Received By mjacobs Date 2008-12-04 Time 16:37 Sent To  
Notes
2008-12-04 16:37:38BUILDING PLAN REVIEW
 PERMIT: 08110490
 ADD: 1700 N. FLORIDA MANGO ROAD.
 CONT: SUPERIOR ENERGY SYSTEMS, LTD.
 TEL: (440)236-6009
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS NOT THE IBC. THIS
 INFORMATION IS ON THE DRAWINGS.
  
 4) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G15-23.002, FLORIDA STATUTES 471 FOR ENGINEERS
 AND FL ADMIN CODE 61G16.003, FLORIDA STATUTES 481
 ARCHITECTS. THE SEALS AND SIGNATURES ON THE PLANS AND
 REPORTS SHALL BE ORIGINAL NOT PHOTO-COPIES. THE DESIGN
 PROFESSIONAL SHALL BE REGISTERED UNDER THE LAWS OF THE
 STATE OF FLORIDA.
  
 5) UNDER THE HEADING ON THE PERMIT APPLICATION
 ?DESCRIBE PROJECT IN DETAIL? STATES THE LPG FUEL TANK
 THAT WILL BE TEMPORARY (LESS THAN 180 DAYS). NOTE: IF
 THIS IS TEMPORARY STRUCTURE THE TIME LIMIT WILL BE 180
 DAYS. FBC 107.1 THE BUILDING OFFICIAL IS AUTHORIZED TO
 ISSUE A PERMIT FOR TEMPORARY STRUCTURES AND TEMPORARY
 USES. SUCH PERMITS SHALL BE LIMITED AS TO TIME OF
 SERVICE, BUT SHALL NOT BE PERMITTED FOR MORE THAN 180
 DAYS. THE BUILDING OFFICIAL IS AUTHORIZED TO GRANT
 EXTENSIONS FOR DEMONSTRATED CAUSES. PLEASE SEE FBC
 3103.1 FOR ADDITIONAL INFORMATION ON TEMPORARY
 STRUCTURES. IF THIS IS TRULY A TEMPORARY STRUCTURE,
 PROVIDE A NOTARIZE LETTER STATING THE DATE WHEN THE
 TANK WILL BE INSTALLED AND WHEN IT WILL BE REMOVED,
  
 6) PAGE #3 OF THE PROPANE TANK ANCHORAGE ANALYSIS
 INDICATES ASCE 7-05. THE ASCE REFERENCE STANDARD UNDER
 THE FBC 2004 IS ASCE 7-02 SEE CHAPTER 35 OF THE FBC
 PAGE 35.6R SHEET #2 OF THE PACKAGE ALSO MAKES REFERENCE
 TO THE 2006 IBC THIS INFORMATION IS ALSO INCORRECT. THE
 CODE USE HERE IN FLORIDA IS THE 2004 FBC WITH THE 2007
 REVISIONS. SHEET #4 SHOWS THE ?L? BRACKETS, BUT DO NOT
 CLEARLY STATE HOW THESE BRACKETS WILL BE ATTACHED TO
 THE TANK. ARE THESE BRACKETS WELDED TO THE TANK? THE
 DETAIL DOES NOT CLEARLY STATE HOW THE BRACKETS WILL
 HOLD THE TANK IN PLACE. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THE CODE. 106.1.1*
  
 7) FBC 1609.1.3STRUCTURAL MEMBERS AND SYSTEMS AND
 COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE A CONTINUOUS LOAD
 PATHS FOR THESE FORCES TO THE FOUNDATION.
  
 8) WHAT IS THE LENGTH, WIDTH AND THICKNESS OF THE
 CONCRETE SLAB? THE TYPE OF CONCRETE SHALL BE ALSO
 INDICATED, WILL IT BE 2500PSI, 3000PSI WITH 6X6 WIRE
 MESH OR WILL IT BE FIBER MESH CONCRETE? PROVIDE DETAIL
 DRAWINGS OF THE CONCRETE SLAB SHOWING THIS INFORMATION.
 PROVIDE MORE INFORMATION ON THE CRASH POSTS SHOWING HOW
 THEY ARE SECURED IN THE GROUND AND THE HEIGHT THEY ARE
 OFF THE GROUND AND THE DISTANCE FROM THE STORAGE TANK.
 WHEN ADDRESSING THE ZONING REVIEWER COMMENTS AND A
 FENCE IS CHOSEN PROVIDE INFORMATION HOW THE FENCE WILL
 MEET THE 140MPH WIND REQUIREMENTS. ADDITIONAL
 INFORMATION IS REQUIRED 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-05-15 Cont ID  
Sent By dpalmer Date 2009-05-15 Time 09:47 Rev Time 0.00
Received By dpalmer Date 2009-05-15 Time 09:47 Sent To  
Notes
2009-05-15 09:47:39ELEC PERMIT REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-04-09 Cont ID  
Sent By dpalmer Date 2009-04-09 Time 13:21 Rev Time 0.00
Received By dpalmer Date 2009-04-09 Time 13:21 Sent To  
Notes
2009-04-09 13:21:40** DENIED**
  
 1) NOTE: PLEASE KNOW THAT THE PERMIT IS APPLIED FOR
 UNDER THE 2004 FBC W/ 2007 REVISIONS. THE PLANS STATE
 DESIGNS ON ELECTRICAL AND ARCHITECTURAL SHEETS UNDER
 2007 FBC W/ 2009 REVISIONS.
 PLEASE REVISE CODES.
 WE DO NOT HAVE THE AUTHORITY TO RED-LINE PLANS FOR
 CORRECT CODES.
  
 2) NOTE: PLEASE SHOW A LAYOUT OF THE CLASS LOCATIONS
 AND LIST. IS THE CLOUDED LOCATION THE CLASS LOCATION?
 PLEASE LIST THE SPECIFIC TYPE OF LOCATION.
 NEC 500
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-17 Cont ID  
Sent By dpalmer Date 2008-12-17 Time 14:54 Rev Time 0.00
Received By dpalmer Date 2008-12-17 Time 14:54 Sent To  
Notes
2008-12-17 14:54:30** DENIED **
  
 1) NOTE: PLANS AND DOCUMENTS SUBMITTED SHALL CONTAIN
 ALL ORIGINAL SIGNATURES, AND SEALS BY LICENSED
 DESIGNERS IN THE STATE OF FLORIDA QUALIFIED FOR SUCH
 SCOPE OF WORK
 FS 471.025, FAC 61G15-23.002
 DOCUMENTS CONTAIN PHOTO-COPIED SEAL AND SIGNATURE FROM
 A DESIGNER LICENSED IN THE STATE OF CALIFORNIA.
  
 2) NOTE: PLEASE SUBMIT ANY ELECTRICAL PLANS SHOWING ANY
 SYSTEMS AND CLASS LOCATIONS ASSOCIATED WITH
 INSTALLATION.
 NEC 2005
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-05-18 Cont ID  
Sent By mawillia Date 2009-05-18 Time 15:46 Rev Time 0.00
Received By mawillia Date 2009-05-18 Time 15:31 Sent To B
Notes
2009-05-18 15:44:06*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS C-1 & C-2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-04-14 Cont ID  
Sent By mawillia Date 2009-04-14 Time 12:56 Rev Time 0.00
Received By mawillia Date 2009-04-14 Time 12:41 Sent To  
Notes
2009-04-14 12:54:41*****DENIED*****
  
 THE FOLLOWING COMMENTS (OF 5) TAKEN FROM THE PREVIOUS
 FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 3. PROVIDE AT LEAST ONE APPROVED PORTABLE FIRE
 EXTINGUISHER HAVING A MINIMUM CAPACITY OF 18 LB DRY
 CHEMICAL WITH B-C RATING. THE REQUIRED FIRE
 EXTINGUISHER SHALL BE LOCATED NO MORE THAN 50 FEET FROM
 THE STORAGE LOCATION.
  
 4. THE CYCLINDER SHALL BE IN ACCORDANCE WITH DOT
 SPECIFICATIONS AND SHALL BE MARKED AS PROVIDED IN THE
 REGULATIONS, RULES, OR CODE UNDER WHICH IT IS
 FABRICATED.
  
 5. NFPA 704 LABELS, NO SMOKING, AND PRODUCT IDENTITY
 LABELS WILL BE NEEDED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE ABOVE COMMENTS HAVE BEEN
 ADDRESSED
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-19 Cont ID  
Sent By mawillia Date 2008-12-19 Time 15:39 Rev Time 0.00
Received By mawillia Date 2008-12-19 Time 14:58 Sent To  
Notes
2008-12-19 15:39:22*****UNSAT*****
  
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMEITTED PLAN SHEET. THIS WILL CLEARLY
 DISTINGUISH THAT THE PROJECTED SCOPE OF WORK IS DONE AT
 THE REFERENCED LOCATION AND NOT AT THE OTHER ADDRESSES
 SHOWN ON THE PLAN (1616 AND 1750 NORTH FLORIDA MANGO
 ROAD).
  
 2. THE STORAGE, USE, AND HANDLING OF LIQUIFIED
 PETROLEUM GASES SHALL COMPLY WITH NFPA 58.
  
 3. PROVIDE AT LEAST ONE APPROVED PORTABLE FIRE
 EXTINGUISHER HAVING A MINIMUM CAPACITY OF 18 LB DRY
 CHEMICAL WITH B-C RATING. THE REQUIRED FIRE
 EXTINGUISHER SHALL BE LOCATED NO MORE THAN 50 FEET FROM
 THE STORAGE LOCATION.
  
 4. THE CYCLINDER SHALL BE IN ACCORDANCE WITH DOT
 SPECIFICATIONS AND SHALL BE MARKED AS PROVIDED IN THE
 REGULATIONS, RULES, OR CODE UNDER WHICH IT IS
 FABRICATED.
  
 5. NFPA 704 LABELS, NO SMOKING, AND PRODUCT IDENTITY
 LABELS WILL BE NEEDED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE ABOVE COMMENTS HAVE BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN FEVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-05-11 Cont ID  
Sent By kstevens Date 2009-05-11 Time 10:14 Rev Time 0.00
Received By kstevens Date 2009-05-11 Time 10:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-04-17 Cont ID  
Sent By kstevens Date 2009-04-17 Time 14:37 Rev Time 0.00
Received By kstevens Date 2009-04-17 Time 14:37 Sent To  
Notes
2009-04-17 14:38:50DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
  
 1) NOTE: PLEASE KNOW THAT THE PERMIT IS APPLIED FOR
 UNDER THE 2004 FBC W/ 2007 REVISIONS. THE PLANS STATE
 DESIGNS ON ELECTRICAL AND ARCHITECTURAL SHEETS UNDER
 2007 FBC W/ 2009 REVISIONS.
 PLEASE REVISE CODES.
 WE DO NOT HAVE THE AUTHORITY TO RED-LINE PLANS FOR
 CORRECT CODES. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-12-23 Cont ID  
Sent By kstevens Date 2008-12-23 Time 10:23 Rev Time 0.00
Received By kstevens Date 2008-12-23 Time 10:23 Sent To  
Notes
2008-12-23 10:35:54DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1. PLANS SHALL BE DESIGNED TO THE FBC-2004 WITH 2007
 REVISIONS. SHT 3 OF 6 FROM THE CONSULTING ENGINEER
 INDICATES IN NOTE #1 THAT ALL WORK SHALL CONFORM TO THE
 2006 IBC. PLEASE SHOW CODE CRITERIA ON PLANS FOR THE
 CORRECT CODE. SECTION 106.1.1.
  
 2. PLANS SHALL HAVE AN ORIGINAL SEAL AND SIGNATURE.
 ALSO IF THE DESIGN PROFESSIONAL IS AN ENGINEER, A TITLE
 BLOCK SHALL BE USED ON EACH SHEET CONTAINING THE
 PRINTED NAME, ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR IF APPLICABLE, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER, AND IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, THE NAME, ADDRESS AND
 CERTIFICATE OF AUTHORIZATION NUMBE OF THE ENGINEERING
 BUSINESS. FAC 61G15-23.002(2) & FS 471.025.
  
 3. THE CORRECT ADDRESS, (1700 FLORIDA MANGO ROAD),
 SHALL BE INDICATED ON THE SHEETS SHOWING AN ADDRESS FOR
 THE PROJECT. ADDRESS SHOWN RANGE FROM 1616 & 1750 WHICH
 ARE INCORRECT. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-05-01 Cont ID  
Sent By lmartine Date 2009-05-01 Time 17:05 Rev Time 0.00
Received By lmartine Date 2009-05-01 Time 17:00 Sent To  
Notes
2009-05-01 17:05:49 
  
 C-22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-16 Cont ID  
Sent By shill Date 2009-03-16 Time 16:13 Rev Time 0.00
Received By shill Date 2009-03-16 Time 16:13 Sent To  
Notes
2009-03-16 16:15:23TO "COMM" BD#51

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-23 Cont ID  
Sent By kstevens Date 2008-12-23 Time 10:36 Rev Time 0.00
Received By kstevens Date 2008-11-21 Time 11:33 Sent To  
Notes
2008-12-15 11:34:10TO "COMM" BD#4

Review Stop Z ZONING
Rev No 3 Status P Date 2009-05-08 Cont ID  
Sent By eschneid Date 2009-05-08 Time 14:16 Rev Time 0.50
Received By eschneid Date 2009-05-08 Time 14:16 Sent To  
Notes
2009-05-08 14:26:29PASSED
  
 1) THE ZONING "PASS" ONLY APPLIES TO THE TANK AND THE
 BOLLARDS.
  
 2) THE CHAIN LINK FENCE, THE DOG EARED SCREENING FENCE
 AND THE HEDGE REQUIRE ONE OF THE FOLLOWING:
  
 A. THEY SHALL BE SUBMITTED AS A SEPARATE PERMIT.
  
 B. THEY SHALL BE SUBMITTED AS A REVISION TO THIS
 PERMIT, WITH ALL APPROPRIATE DETAILS AND THE PERMIT
 VALUATION SHALL BE INCREASED AND THE APPROPRIATE
 INCREASE IN FEES PAID.
  
 3) A CERTIFICATE OF COMPLETION WILL NOT BE ISSUED FOR
 THE TANK UNTIL THE DOG EARED SCREENING FENCE AND HEDGE
 ARE INSTALLED FOLLOWING THE ISSUANCE OF BUILDING
 PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2009-04-07 Cont ID  
Sent By eschneid Date 2009-04-07 Time 15:07 Rev Time 0.25
Received By eschneid Date 2009-04-07 Time 15:07 Sent To  
Notes
2009-04-21 16:51:25UPDATE CORRECT CITATION:
  
 REPEAT COMMENT - PER SECTION 94-444(B) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, THE TANK SHALL BE
 ENCLOSED BY A MASONRY, STEEL OR WOOD WALL AND HEDGE.
 PLEASE NOTE THAT CHAIN LINK WITH SLATS IS NOT ALLOWED
 AS SCREENING MATERIAL IN WEST PALM BEACH.
2009-04-07 15:10:54FAILED
  
 1) REPEAT COMMENT - PER SECTION 94-443(B) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, THE TANK SHALL BE
 ENCLOSED BY A MASONRY, STEEL OR WOOD WALL AND HEDGE.
 PLEASE NOTE THAT CHAIN LINK WITH SLATS IS NOT ALLOWED
 AS SCREENING MATERIAL IN WEST PALM BEACH.
  
 2) THIS PERMIT WILL NOT BE APPROVED BY ZONING UNTIL THE
 PERMIT FOR THE WALL AND HEDGE IS SUBMITTED.
  
 3) A CERTIFICATE OF COMPLETION WILL NOT BE ISSUED FOR
 THE TANK UNTIL THE WALL AND HEDGE ARE INSTALLED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-04 Cont ID  
Sent By eschneid Date 2008-12-04 Time 08:49 Rev Time 0.00
Received By eschneid Date 2008-11-25 Time 16:31 Sent To  
Notes
2008-12-04 08:55:07FAILED
  
 1) PER SECTION 94-443(B) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, THE TANK SHALL BE ENCLOSED BY
 A MASONRY OR WOOD WALL AND HEDGE. PLEASE SEE PLAN
 ATTACHED TO COMMENT SHEET FOR HIGHLIGHTED MINIMUM WALL
 AND HEDGE INSTALATION AREA.
  
 2) WALL SHALL BE AS TALL AS THE TANK (SHOWN AT 6'6" ON
 PLANS).
  
 3) THIS PERMIT WILL NOT BE APPROVED BY ZONING UNTIL THE
 PERMIT FOR THE WALL AND HEDGE IS SUBMITTED.
  
 4) A CERTIFICATE OF COMPLETION WILL NOT BE ISSUED FOR
 THE TANK UNTIL THE WALL AND HEDGE ARE INSTALLED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.