| 2008-12-04 15:41:42 | RESIDENTIAL (R3) INTERIOR SUNROOM REMODELING, BUILDING |
| | REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- 2 X 12 FLOOR JOISTS NEED TO BE PRESSURE TREATED OR |
| | OTHER TYPE OF WOOD AS REQUIRED BY SEC. R319.1(1) OF |
| | 2004 FLORIDA RESIDENTIAL CODE. REVISE INFORMATION ON |
| | WALL SECTION AND FLOOR FRAMING PLAN AS REQUIRED. |
| | |
| | 2- CLEARLY SPECIFY ON PLANS HOW COMPLYING WITH ALL |
| | VENTILATION REQUIREMENTS OF SEC. R408 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. INDICATE LOCATION AND SIZE OF |
| | VENTILATION OPENINGS, ACCESS, ETC. SEE SEC. R408 FOR |
| | SPECIFIC REQUIREMENTS. |
| | |
| | 2- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR STORM |
| | SHUTTERS AS REQUIRED BY CITY IMPLEMENTATION STANDARD |
| | FOR WIND-BORNE DEBRIS IMPACT PROTECTION. SEE ATTACHED |
| | INSTALLATION SCHEDULE SAMPLE AND COPY OF CITY STANDARD. |
| | NOTE: CLEARLY MARK ON SHUTTER DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS (EG: WALL MOUNTED, BUILT OUT, ETC) |
| | AND SPECIFIC ANCHOR TYPE AND SPACING TO VERIFY |
| | COMPLIANCE WITH THE PRODUCT APPROVAL AND THE DESIGN |
| | PRESSURES OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR ALL STRUCTURAL SIMPSON CONNECTORS SPECIFIED |
| | ON PLANS AND DETAILS. |
| | NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE AND PAGE WHERE CONNECTOR IS SHOWN. GO TO |
| | WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING |
| | INFORMATION. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AN APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 5- A) ENERGY CALCULATIONS NEED TO BE SIGNED AND DATED |
| | BY THE PERSON WHO PREPARED THEM. |
| | B) OWNER/AGENT NEEDS TO SIGN AND DATE BOTTOM OF ENERGY |
| | CALCULATIONS AS WELL. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |