| 2008-12-03 10:18:48 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | A. SUBMIT THE FOLLOWING INFORMATION FOR PERMIT: |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. -- NOT ALL LENGTHS INDICATED. (SEE |
| | HIGHLIGHTED SECTIONS OF PIPE). |
| | ****RESPONSE NOTED, BUT COMMENTS NOT ADDRESSED. NOT ALL |
| | LENGHTS WERE INDICATED AS REQUESTED. PLEASE INDICATE |
| | HOW THE DROPS FROM THE METER AND THE RISERS FROM |
| | UNDERGROUND CAN BE 1 FOOT WHEN THERE IS A REQUIREMENT |
| | FOR MINIMUM BURIAL DEPTH TO BE 1 FOOT. SECTION 404.9. |
| | SUBMIT LENGTHS OF PIPE THAT REFLECT THE INSTALLATION OF |
| | THE PIPE AND SHOW THE LENGHT FOR EACH CUT SECTION. |
| | |
| | 2. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 3. OK |
| | |
| | ****NEW COMMENT**** |
| | |
| | 1B. THE PIPE SIZE FROM THE METER SHALL BE 1-1/4" NOT 1" |
| | AS SHOWN. SOME PIPE SIZES ARE NOT CLEAR AND LEGIBLE. |
| | MAKE SURE ALL PIPE SIZES ARE LEGIBLE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |