Plan Review Details - Permit 08110469
Plan Review Stops For Permit 08110469
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-15 Cont ID  
Sent By lmartine Date 2009-01-15 Time 15:45 Rev Time 0.00
Received By lmartine Date 2009-01-15 Time 15:45 Sent To  
Notes
2009-01-15 15:46:40REVISED ENGINEERING FOR NEW DOORWAY OPENING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-12-04 Cont ID  
Sent By lmartine Date 2008-12-04 Time 16:41 Rev Time 0.00
Received By lmartine Date 2008-12-04 Time 16:41 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-01 Cont ID  
Sent By btrobaug Date 2008-12-01 Time 14:38 Rev Time 0.00
Received By btrobaug Date 2008-12-01 Time 14:33 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-26 Cont ID  
Sent By btrobaug Date 2008-11-26 Time 10:08 Rev Time 0.00
Received By btrobaug Date 2008-11-25 Time 15:07 Sent To B
Notes
2008-11-26 10:08:22 
  
 APPLICATION #08110469 ELECTRICAL PLAN REVIEW
 404 NORTHWOOD ROAD 11/25/08
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES AND FIXTURES. LOCATE ALL FIXTURES ON THE PLAN
 (SEE STORAGE AREAS) INDICATE IF NEW OR EXISTING.
 106.3.5 FBC.
  
 3} INDICATE THE TYPE OF LUMINAIRES AND THE WATTAGES OF
 SAME, BEING INSTALLED UNDER THIS PERMIT.
  
 4} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1ABC.1.1FOR LIGHTING DENSITIES. ALL THAT IS
 REQUIRED FOR THE ELECTRICAL REVIEW IS THE BASIC
 PRESCRIPTIVE REQUIREMENTS. SEE 13-415.2.ABC.1
 PERFORMANCE CALCULATION PROCEDURES, GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 5} 13-415.1.ABC.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING.
 A. A CONTROL DEVICE SHALL BE INSTALLED THAT
 AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH
 MULTISCENE CONTROL, IN THE FOLLOWING:
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS).
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
  
 6} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 NEC (F)(4). LOCATE
 SAME ON PLANS.*** NFPA-101 *7.8.1.3
 THE FLOORS AND OTHER WALKING SURFACES WITHIN AN EXIT
 AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND EXIT
 DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE ILLUMINATED TO
 VALUES OF AT LEAST 1 FT-CANDLE (10 LUX) MEASURED AT THE
 FLOOR
  
 7} THERE ARE TWO ADDRESSES ON SHEET? (NEITHER OF THE
 SHEETS ARE NUMBERED, LETTERED ETC.) CORRECT THE ADDRESS
 OF THE PROJECT ON THE PLANS AND IDENTIFY THE SHEETS.
 PER 106.1.1 FBC AS AMENDED.
  
 8} 600.5(A) REQUIRED BRANCH CIRCUIT EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE OUTLET
 IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH
 TENANT SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE.
 THE OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT
 RATED AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD.
 SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED
 ACCESSIBLE TO PEDESTRIANS.
  
 9} THERE IS NO SHOW WINDOW CIRCUIT AS REQUIRED BY
 210.62, IN THE PANEL SCHEDULE.
  
 10} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN
 MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3.
 FBC. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND
 471 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-12-02 Cont ID  
Sent By mawillia Date 2008-12-02 Time 13:19 Rev Time 0.00
Received By mawillia Date 2008-12-02 Time 13:05 Sent To  
Notes
2008-12-02 13:14:24*****PROVISO*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
 2. INTERIOR FINISH MATERIALS SHALL BE IN ACCORDANCE
 WITH NFPA 101, LIFE SAFETY CODE, 2003 EDITION -
 CLASSIFIED AS CLASS A, CLASS B, OR CLASS C.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-12 Cont ID  
Sent By adarroug Date 2008-12-12 Time 10:25 Rev Time 0.00
Received By adarroug Date 2008-12-12 Time 10:25 Sent To P
Notes
2008-12-12 10:25:32TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-09 Cont ID  
Sent By kstevens Date 2008-12-09 Time 11:03 Rev Time 0.00
Received By kstevens Date 2008-11-24 Time 10:25 Sent To  
Notes
2008-11-24 10:25:54WAITING FOR "BOB"

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-12-18 Cont ID  
Sent By lwagner Date 2008-12-18 Time 14:58 Rev Time 0.00
Received By lwagner Date 2008-12-18 Time 14:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-09 Cont ID  
Sent By kstevens Date 2008-12-09 Time 10:24 Rev Time 0.00
Received By kstevens Date 2008-12-05 Time 16:59 Sent To  
Notes
2008-12-09 10:55:15DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 EXISTING BUILDING
 CITY WPB MUNICIPAL CODE
 FBC-2004 CHAPTER 1
  
 1. INDICATE ON THE PLANS THE CRITERIA FOR THE DESIGN OF
 THE PLANS. PLANS SHALL BE DESIGNED PER FBC-2004 WITH
 2005, 2006 & 2007 REVISIONS. SECTION 106.1.1.
  
 2. INDICATE THE LEVEL OF ALTERATION AS REQUIRED IN
 CHAPTER 3 OF THE EXISTING BUILDING CODE. SECTION
 106.1.1.
  
 3. APPLICATION INDICATES NO CHANGE OF OCCUPANCY. THE
 EXISTING SPACE WAS A MERCANTILE SPACE PREVIOUSLY AND IS
 NOW AN ASSEMBLY OCCUPANCY. PLEASE INDICATE ON THE
 APPLICATION AND SHOW THE OCCUPANCY ON THE PLANS.
 SECTION 106.1.2 AND TABLES 1004.1.2 & 403.1.
  
 4. PER SECTION 1210.2 THE WALLS WITHIN 2 FEET OF A
 WATER CLOSET OR URINAL SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE TO A HEIGHT OF 4 FEET ABOVE THE
 FLOOR. PLEASE SUBMIT A DETAIL OR A FINISH SCHEDULE TO
 SHOW COMPLIANCE.
  
 5. THE VALUE OF THE WORK IS INDICATED AS $2100.00,
 (SINCE UPPED TO $6700.00 BY L. MARTINEZ). IF IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. SECTION 108.3. - WITH THE FOLLOWING WORK
 INDICATED ON THE PLANS, I BELIEVE THE VALUATION IS
 UNDERESTIMATED.
 DEMO:
 REMOVE CEILING, NON-BEARING WALL, WALL OPENING BETWEEN
 EXISTING RESTAURANT & NEW SPACE ADDED, & DOOR.
 NEW WORK:
 CLOSE DOORWAY, FINISH OPENING BETWEEN EXISTING
 RESTAURANT & NEW SPACE, NEW TILE IN TOILET ROOMS, NEW
 TILE FLOOR AT ENTRANCE, NEW WOOD FLOOR, ENGINEERING OF
 OPENING TO NEW RESTAURANT.
 NEW WORK PLUMBING:
 REMOVE EXISTING TOILET FIXTURES AND REPLACE WITH
 NEW,(2-W/C'S & 2 LAVS). NEW SINKS AT BAR AREA, (1 HAND
 SINK, & 1 TRIPLE COMP. SINK, (INDICATED ON RISER
 DIAGRAM), OR 2 COMP. SINK, (INDICATED ON FLOOR PLAN),
 PLEASE CORRELATE. ONE ICE BIN WITH FLOOR SINK OR HUB
 DRAIN.
 NEW WORK ELECTRICAL:
 NEW TRAC LIGHTING, (7 TRACKS & 7 HANGING LIGHTS WITH
 ALL WIRING).
  
 6. THE EXISTING GREASE INTERCEPTOR WILL HAVE TO BE
 INSPECTED AND APPROVED FOR THE EXTRA LOAD INDICATED ON
 THE PLANS, (36 TABLE AND 6 BAR). PLEASE CONTACT HOLLY
 MCGRATH, LABORATORY SUPERVISOR, PUBLIC UTILITIES
 DEPARTMENT AT (561) 822-2200 EXT 2271, BY FAX (561)
 822-2279 OR BY E-MAIL [email protected]. A WRITTEN
 DERTIMINATION IS REQUIRED TO BE SUBMITTED FOR PERMIT
 APPROVAL.
  
 7 SHOW COMPLIANCE WITH SECTION 13 OF THE ENERGY CODE.
  
 8. PER SECTION 806.1 ACCESSIBILITY IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 9. SANITARY RISER DIAGRAM. PLEASE INDICATE ALL PIPE
 SIZES AND TRAP SIZES FOR THE BRANCH ARM AND FIXTURES
 FOR THE SINKS AND THE ICE BIN. TABLES 709.1 & 710.1(2)
 AND SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2008-12-05 Cont ID  
Sent By eschneid Date 2008-12-05 Time 15:45 Rev Time 0.00
Received By eschneid Date 2008-12-05 Time 15:45 Sent To  
Notes
2008-12-05 15:46:46PASSED W/PROVISO
  
 THE PLANS INCLUDED WITH THE ALCOHOL AND SIDEWALK CAFE
 LICENSES SHALL BE CORRECTED TO REFLECT THE REVISED
 LAYOUT OF THE INTERIOR AND EXTERIOR SPACE.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-03 Cont ID  
Sent By eschneid Date 2008-12-03 Time 13:55 Rev Time 0.00
Received By eschneid Date 2008-12-03 Time 13:23 Sent To  
Notes
2008-12-03 13:57:02FAILED
  
 RESPOND TO ALL COMMENTS IN WRITING:
  
 1) ALL PLANS IN THE PACKET SHALL SHOW THE SAME SCOPE OF
 WORK AND CONDITIONS.
  
 2) THE PLANS INCLUDED IN THE BUILDING PERMIT PACKET DO
 NOT MATCH THE PLANS THAT P&Z APPROVED FOR THE ALCOHOL
 AND SIDEWALK CAF? LICENSES.
  
 A. IN ORDER TO COMPLY WITH THE 4COP SRX REQUIREMENTS,
 THE NEW AREA SHALL HAVE AN INTERNAL CONNECTION TO THE
 EXISTING CAF? CENTRO. NOTE: DIFFERENT PLANS IN THE
 PACKET SHOW AN OPENING AND NO OPENING.
  
 B. THE PERMIT PLANS SHOW TWO (2) DOORS NOT ONE (1) DOOR
 LEADING TO NORTHWOOD ROAD AS SHOWN ON THE ALCOHOL AND
 SIDEWALK CAF? LICENSES. IS THERE A CHANGE BEING
 PROPOSED TO THE NORTHWOOD ROAD FA?ADE? IF SO, THEN AN
 ELEVATION PLAN OF THE NORTH FA?ADE, SHOWING COMPLIANCE
 WITH NMUD BUILDING TYPE III ARCHITECTURAL STANDARDS IS
 REQUIRED.
  
 C. THE SEATING LOCATION AND NUMBERS SHALL BE REVISED TO
 MATCH ON ALL PLANS. NOTE: IN ORDER TO COMPLY WITH THE
 4COP SRX REQUIREMENTS, AT LEAST 150 SEATS SHALL BE
 PROVIDED.
  
 D. IF THE BUILDING PERMIT PLANS SHOW THE SPACE
 CORRECTLY, THEN THE PLANS INCLUDED WITH THE ALCOHOL AND
 SIDEWALK CAF? LICENSES SHALL BE CORRECTED.
  
 3) THE PLANS STATE THAT A ?HUNG CEILING? WILL BE
 REMOVED AND A NEW WOOD FLOOR WILL BE INSTALLED. PROVIDE
 THE FLOOR TO CEILING HEIGHT PRE- AND POST-
 CONSTRUCTION. PLEASE REMEMBER THAT THE FLOOR TO CEILING
 HEIGHT SHALL BE BETWEEN 12 FEET AND 16 FEET. IF THE
 FLOOR TO CEILING HEIGHT IS CURRENTLY LESS THAN 12 FEET,
 THEN THE NEW WORK MAY NOT REDUCE THE EXISTING HEIGHT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
  