| | APPLICATION #08110469 ELECTRICAL PLAN REVIEW |
| | 404 NORTHWOOD ROAD 11/25/08 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE |
| | PLAN. |
| | |
| | 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| | DEVICES AND FIXTURES. LOCATE ALL FIXTURES ON THE PLAN |
| | (SEE STORAGE AREAS) INDICATE IF NEW OR EXISTING. |
| | 106.3.5 FBC. |
| | |
| | 3} INDICATE THE TYPE OF LUMINAIRES AND THE WATTAGES OF |
| | SAME, BEING INSTALLED UNDER THIS PERMIT. |
| | |
| | 4} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE |
| | 13-415.1ABC.1.1FOR LIGHTING DENSITIES. ALL THAT IS |
| | REQUIRED FOR THE ELECTRICAL REVIEW IS THE BASIC |
| | PRESCRIPTIVE REQUIREMENTS. SEE 13-415.2.ABC.1 |
| | PERFORMANCE CALCULATION PROCEDURES, GENERAL. |
| | THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| | A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| | DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| | METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED |
| | INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH |
| | SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR |
| | LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| | SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE |
| | DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF |
| | THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE |
| | DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE |
| | SCHEDULE TO CORRELATE WITH THE ONES IN THE |
| | CALCULATIONS. |
| | |
| | 5} 13-415.1.ABC.1.2 SPACE CONTROL. |
| | EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| | HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| | CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| | MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| | SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. |
| | A. A CONTROL DEVICE SHALL BE INSTALLED THAT |
| | AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF |
| | ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH |
| | MULTISCENE CONTROL, IN THE FOLLOWING: |
| | 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS, |
| | LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE |
| | CLASSROOMS). |
| | 2. CONFERENCE/MEETING ROOMS. |
| | 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| | |
| | 6} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 |
| | (2003), AND CIRCUITED PER 700.12 NEC (F)(4). LOCATE |
| | SAME ON PLANS.*** NFPA-101 *7.8.1.3 |
| | THE FLOORS AND OTHER WALKING SURFACES WITHIN AN EXIT |
| | AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND EXIT |
| | DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE ILLUMINATED TO |
| | VALUES OF AT LEAST 1 FT-CANDLE (10 LUX) MEASURED AT THE |
| | FLOOR |
| | |
| | 7} THERE ARE TWO ADDRESSES ON SHEET? (NEITHER OF THE |
| | SHEETS ARE NUMBERED, LETTERED ETC.) CORRECT THE ADDRESS |
| | OF THE PROJECT ON THE PLANS AND IDENTIFY THE SHEETS. |
| | PER 106.1.1 FBC AS AMENDED. |
| | |
| | 8} 600.5(A) REQUIRED BRANCH CIRCUIT EACH COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE OUTLET |
| | IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH |
| | TENANT SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE. |
| | THE OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT |
| | RATED AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD. |
| | SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED |
| | ACCESSIBLE TO PEDESTRIANS. |
| | |
| | 9} THERE IS NO SHOW WINDOW CIRCUIT AS REQUIRED BY |
| | 210.62, IN THE PANEL SCHEDULE. |
| | |
| | 10} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN |
| | MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. |
| | FBC. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND |
| | 471 FS, RESPECTIVELY. |
| | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| | IF EXEMPTIONS APPLY. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |