Plan Review Details - Permit 08110415
Plan Review Stops For Permit 08110415
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-16 Cont ID  
Sent By dpalmer Date 2008-12-16 Time 11:26 Rev Time 0.00
Received By dpalmer Date 2008-12-16 Time 11:26 Sent To  
Notes
2008-12-16 11:27:08** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FLORIDA BUILDING CODE 108.3. THE
 VALUES FOR COMPLETE SCOPE OF WORK FOR ELECTRICAL SHALL
 INCLUDE ALL LABOR, MATERIALS EQUIPMENT, DESIGN COST ETC
 EVEN IF ANY OF THESE ITEMS ARE OWNER SUPPLIED. THE
 APPLIED VALUE OF $500 DOES NOT COVER THE COST OF
 ELECTRICAL EQUIPMENT LET ALONE ALL OTHER ITEMS IN SCOPE
 OF WORK.
  
 2) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES AS
 THE PLANS SUBMITTED BY MILLS AND COMPANY ACTUALLY
 CONTAIN A RAISED SEAL OVER PHOTO-COPIED SIGNATURES
 WHICH IS NOT PERMITTED UNDER FLORIDA STATUTES 471.025,
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002
  
 3) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL RISER
 DIAGRAM FOR SCOPE OF HOOKING UP NEW CONSTRUCTION
 TRAILERS. NO ELECTRICAL PLANS ARE IN SET WHICH ONLY
 CONTAINS PLUMBING, BUILDING AND MECHANICAL.
 PLEASE SHOW COMPLIANCE FOR AIC RATINGS OF EQUIPMENT.
 110.9
 PLEASE INCLUDE CONDUCTORS FOR ALL. (SERVICE, FEEDERS
 ETC) 310.16,240.4
 PLEASE INCLUDE LOADS. 220
 PLEASE COMPLETE ALL GROUNDING ON RISER TO BE SUBMITTED
 PER 250
 PLEASE SEE 230.70,,71,72,76,79 FOR REQUIRED SERVICE.
 ** KEEP IN MIND THESE ARE SOME CODE SECTIONS GIVEN AND
 OTHERS MAY APPLY DEPENDING ON ELECTRICAL SCOPE WHICH IS
 NOT SHOWN AT THIS TIME.
  
 4) NOTE: PLEASE KNOW IF SERVICE IS GOING TO BE
 277/480V, PLANS ARE REQUIRED TO BE DONE BY A PE.
 471.003.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-12-16 Time   Rev Time 0.00
Received By adarroug Date 2008-11-20 Time 11:06 Sent To  
Notes
2008-11-20 11:06:18TO "COMM" BD#50--OK NOT TO EXPEDITE PER LUIS MARTINEZ