Plan Review Details - Permit 08110413
Plan Review Stops For Permit 08110413
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2009-01-15 Cont ID  
Sent By rbrown Date 2009-01-15 Time 19:58 Rev Time 0.00
Received By rbrown Date 2009-01-15 Time 19:58 Sent To  
Notes
2009-01-15 20:08:44LETTER SUBMITTED FOR PERMIT BY AFFIDAVIT PURSUANT TO
 SECTION 105.14 OF FBC CHAPTER 1

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-16 Cont ID  
Sent By dpalmer Date 2008-12-16 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2008-12-16 Time 14:32 Sent To  
Notes
2008-12-16 14:33:33* DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FLORIDA BUILDING CODE 108.3. THE
 VALUES FOR COMPLETE SCOPE OF WORK FOR ELECTRICAL SHALL
 INCLUDE ALL LABOR, MATERIALS EQUIPMENT, DESIGN COST ETC
 EVEN IF ANY OF THESE ITEMS ARE OWNER SUPPLIED. THE
 APPLIED VALUE OF $7500.00 DOES NOT COVER THE COST OF
 ELECTRICAL EQUIPMENT LET ALONE ALL OTHER ITEMS IN SCOPE
 OF WORK.
  
 2) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL RISER
 DIAGRAM FOR SCOPE OF HOOKING UP NEW ELECTRICAL SYSTEMS.
 PLEASE SHOW COMPLIANCE FOR AIC RATINGS OF EQUIPMENT.
 110.9
 PLEASE INCLUDE CONDUCTORS FOR ALL. (SERVICES, FEEDERS
 ETC) 310.16,240.4
 PLEASE COMPLETE ALL GROUNDING ON RISER TO BE SUBMITTED
 PER 250.50,250.20,250.30, 250.66 ETC
 PLEASE SEE 230.70,,71,72,76,79 FOR REQUIRED SERVICE.
 ** KEEP IN MIND THESE ARE SOME CODE SECTIONS GIVEN AND
 OTHERS MAY APPLY DEPENDING ON ELECTRICAL SCOPE WHICH IS
 NOT SHOWN AT THIS TIME.
  
 3 NOTE: PLEASE SEE 450.3B FOR MAXIMUM OCP OF 277/480V
 TRANSFORMER ON PRIMARY SIDE.
 ** SEE NOTES OF TABLE.
  
 4) NOTE: THERE IS A LETTER ATTACHED FROM HOLLIS
 ENGINEERING CONSULTANTS WHICH IS ADDRESSED TO
 MIAMI-DADE BUILDING OFFICIAL IN ELECTRICAL. THIS LETTER
 IS MADE OUT TO A MUNICIPALITY WHICH THE WORK IS NOT
 BEING APPLIED.
 PLEASE ALSO SEE THIS LETTER CONTAINS A RAISED SEAL OVER
 A PHOTO-COPIED SIGNATURE WHICH IS A VIOLATION OF FAC
 61G15-23.022 AND FS 471.025
  
 5) NOTE: LETTER AS NOTED ABOVE AS WELL AS COVER SHEET
 MENTIONS INSTALLATION TO NRTL STANDARDS HOWEVER PLEASE
 PROVIDE DOCUMENTATION ON ELECTRICAL EQUIPMENT AND
 ASSEMBLY BEING INSTALLED. THESE MUST BE A LISTED SYSTEM
 BY A NRTL NOT ONLY INSTALLED BY THEIR REQUIREMENTS OR
 STANDARDS.
 110.3,90.7
 PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS ON LISTED
 EQUIPMENT.
  
 6) NOTE: TEMPORARY INSTALLATIONS AS DEFINED IN THE NEC
 AS WELL AS FBC IS 180DAYS. (6MONTHS)
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-12-16 Time   Rev Time 0.00
Received By adarroug Date 2008-11-20 Time 11:00 Sent To  
Notes
2008-11-20 11:04:55TO "COMM" BD#50--OK NOT TO EXPEDITE PER LUIS MARTINEZ

Review Stop Z ZONING
Rev No 1 Status N Date 2008-11-25 Cont ID  
Sent By eschneid Date 2008-11-25 Time 16:09 Rev Time 0.00
Received By eschneid Date 2008-11-25 Time 16:09 Sent To  
Notes
2008-11-25 16:10:32NOT REQUIRED
  
 TEMPORARY (9 MONTH) FACILITY.